ElectricalIsolationRequirementandNeutralWire
Jan6,2016
132views
7Likes
0Comments
Thecontroversialtopicofisolationrequirementandallthosequestionsthat
comeswithit:
IsitsufficienttoisolatetheactiveconductorsonlyinAlternatingCurrent
(AC)system?
DoesneutralrequiretobeisolatedinACsingleorthreephasesystems?
DoyouhavetoisolatebothnegativeandpositiveinDCsystem?
Regardlessofinwhichcountrywepractice,usaselectricalengineersmusttake
thismatterseriously.TheanswerisnotasimpleYesorNo.Assessmentmustbe
donecasebycase.IwilltakeyouthroughnumberofNationalandinternational
standardstofurtherclarifythematter.Hopefullythiswillshedsomelighton
isolationimplicationinourindustry.
InthisarticleIwillmainlyfocusonroleofNeutralconductorforisolation
purposes.Ingeneraltheintentof"neutral"conductoristoprovideareturnpath
fortheunbalancedportionofthecircuitcurrentandalsoinsomecasesa
protectiveearthlingsystem.
https://www.linkedin.com/pulse/electricalisolationrequirementneutralwirefaraz
1/20
2/18/2016
ElectricalIsolationRequirementandNeutralWire|FarazMirzaaghaMIEAustCPEngNER|LinkedIn
ACSystem
Toisolateadevice/plantitisstatedinAustralianStandard(AS3000)andIEC
60364,allactiveconductorsofanACshallbecapableofbeingisolated.
Nowthequestionisthis:WhatisanActiveconductor?
TheactiveconductorisdefinedasAnyconductorthatismaintainedata
differenceofpotentialfromtheneutralorearthedconductor.Inasystemthat
doesnotincludeaneutralorearthedconductor,allconductorsshallbe
consideredtobeactiveconductors.ThisisquiteclearbutwhataboutNeutral?
Weallseenneutralbecomeactive(figurativelyspeaking).
Nowtherearetwoscenarios,oneisyoudonotswitchtheneutralduringisolation
andtheotherwhenyoumay.Notewhenitcomestoswitchingitislefttoyou
decideasperyoursystemconfiguration.
A)NotswitchingtheNeutral
1.Iftheconductorsuppliesthemain(distributiontransformerorsimilar)
2.Iftheneutralactasprotectiveearthandneutral(PEN),someofyoumay
knowitasTNC.ThisalsoappliestoTNCSsystemwherepartofthesystem
usesacombinedPENconductor,whichatsomepointwillsplitupinto
separatePEandNlines.ThissystemalsoknownasProtectiveMultipleEarth
(PME)inUKandMultipleEarthedNeutral(MEN)inAU,seefigurebelow.
OneofthereasonweusePME/MEN
systemistoreducetheriskofelectric
shockintheeventofabrokenPEN
conductor.Lookingattheleftschematic,if
yourisolationdevice(e.g.CB)isonthered
lineyoucanarguetheprotectiveearthis
notbrokenduringisolationalthoughyou
isolatedtheneutral.
Soaslongasthatneutralisgroundedatonepointanditisusedasaprotective
earthlingattheloadend,wearenotpermittedtoswitchit.
B)SwitchingtheNeutral
https://www.linkedin.com/pulse/electricalisolationrequirementneutralwirefaraz
2/20
2/18/2016
ElectricalIsolationRequirementandNeutralWire|FarazMirzaaghaMIEAustCPEngNER|LinkedIn
IfyouhavenotsatisfiedtheconditionsaboveinsectionA,youmaynow
operateyourNeutralconsideringbelowfactorsapply:
1.Iftheneutralconductorisconnectedtoamultipoleswitch/breakeralong
withotheractiveconductors.Thatswitchshallhaveappropriateshortcircuit
breakingandmakingcapacity.Allpolesarelinkedtogetherintheswitch
whereallactiveandtheneutralconductorareoperatedatthesametime.
2.Iftherearemultipleswitcheswithoneneutralswitchortheneutralswitchis
physicallyseparatetoitscorrespondingactiveswitch.Youmayoperatethat
neutralswitchaslongasneutralcontactcannotremainopenwhentheactive
contactsareclosed.
Youmayoperatetheneutralpoleiftheneutralisoperatedatthesametimewith
othercorrespondingactiveconductorsoriftheneutralpoledoesnotopenbefore
anddoesnotcloseaftertheactivepole.Youcannowstarttoseethereasoning
behindoperatingandnotoperatingtheNeutral.
TheAustralianstandardstatesWhereanitemofswitchgearisrequiredto
disconnectallliveconductorsofacircuit,itshallbeofatypesuchthattheneutral
conductorcannotbedisconnectedorreconnectedwithouttherespectiveactive
conductorsalsobeingdisconnectedorreconnected
Floatingneutral
TheneutralshouldonlybeconnectedtogroundatonepointsuchasMEN.This
willcreateapathforcurrenttoreturntoserviceviaground.Ina3phasesystem
thegroundedneutralwillstabilizeallthreephases.Incaseofgroundbreakage
voltagepotentialwillbepresent.Similarlyifduringisolationweonlybreakthe
neutral,wewillhavefloatingneutral.Duringthisprocesswearedisturbingthe
currentpathwhichwouldreturnfromeachphasevianeutral.Inthisscenario
usuallythecurrentwillreturnviatheothertwophaseswhichresultsinvoltage
imbalance.Thisiswhenyouwillreadunexpectedhighvoltage(~100vinathree
phase415Vsystem)acrossyourEarthandNeutral,whichisquitedangerousand
unsafe.
Therearemanyreasonforfloatingneutralthemostcommonone,Iwouldsayis
sharedneutralwiring.Whereelectriciantrytosavetimeandmoney.Inbuildings
thesedaysmostelectricalequipmentarenonlinearwithcertainlevelof
harmonic(digitalworld!).Nothavingdedicatedneutralwirewillmeansallthese
currentwilladdupandreturnonsingleline.Alinethatisnotadequatelyrated
andwillleadtooverheatingandhighneutraltogroundvoltageandultimately
limitingyoursupplyvoltage.
Seebelowexampletofurtherclarifythematter.Letssaythetechnicianwould
https://www.linkedin.com/pulse/electricalisolationrequirementneutralwirefaraz
3/20
2/18/2016
ElectricalIsolationRequirementandNeutralWire|FarazMirzaaghaMIEAustCPEngNER|LinkedIn
liketoperformmaintenanceonLoadA,i.e.singlephasesupplywithNeutralwire
andlocalearth.
ThetechnicianwillisolateplantAbyopeningSwitchA.Itispossibleforthe
techniciantobeelectrocutedviaNeutralconductor.Thatcanoccurdueto
existingpotentialdifferenceorafaultatloadBwhichcreatesapotential
differencebetweendistributionboard,LoadAorLoadB.Therearemanyother
scenarioswherethereissystemvulnerability.Thesesituationsusuallywill
happeninplaceswitholdwiringandbadpracticeswheretheelectriciantryto
savetimeandmoney!
Forthesamereasonnofuseshallbeinsertedinaneutralconductor.Soincaseof
faultyouwontloseyourneutralandmaintaincontinuity.Protectivedevicesthat
incorporateaswitchingfunctionintheneutralconductorshallcomplywiththe
requirementsofsectionB.
Whataboutatransferswitch?
Neutralswitchingwouldbe'required'(bycodessuchasNECandAS),ifthetwo
sourcesareindependentlygroundedi.e.separatelyderivedsystems.Thisisto
avoidmultipleneutralgroundingandproperfunctioningofgroundfaultcurrent
sensing/protection.
Home
Profile
MyNetwork
WhatabouttheACswitchdiscounterforaPVinverter?
Searchforpeople,jobs,companies,andmore...
Advanced
Jobs
Interests
BusinessServices
TryPremiumforfree
AsperBS60947andAS,toisolatewemustswitchallliveandneutral
Pulse
ElectricalIsolationRequirement
andNeutralWire
FarazMirzaaghaMIEAust...
IsUberredefiningthework
week?
OliviaBarrow
TwoWordsThatWillKillAny
Conversation
conductors.
Publishapost
DCsystem
GenerallyspeakingboththenegativeandpositiveinDCcircuitshallbecapableof
beingisolated.Inthefollowingscenariosyoumayonlyoperateonepolefor
isolation:
https://www.linkedin.com/pulse/electricalisolationrequirementneutralwirefaraz
4/20
2/18/2016
ElectricalIsolationRequirementandNeutralWire|FarazMirzaaghaMIEAustCPEngNER|LinkedIn
Conversation
MarshallGoldsmith
ExtralowvoltageDCsystem
Whereoneofthepolesisconnectedtoearth.E.g.someUPSsystem,earthed
BigCos,NewCos,andtheNine
TrendsRemakingBusiness
JohnBattelle
WhatMostPeopleDont
UnderstandAboutHowStartup
CompaniesareValued
D.C.negativeinbatterybanksandmidpointofPVstring.
Note:earthingonepolewillincreasepossibleearthfaultpaths,andpossible
problemswithcommonlyavailableEuropeaninvertertypesandinternalearth
faultdetectioncircuitry.
MarkSuster
GivingaPresentation?Three
WaystoLeaveYourFingerprint
PowerDistribution, ElectricalEngineering,
Reportthis
SafetyEngineering
JackWelch
More"Conversations"Not
MoreHealthITAreWhat's
NeededToIncreasePatient
StephenWilkinsMPH...
EngagementAndImprove
Writtenby
FarazMirzaaghaMIEAustCPEngNER
Like
Comment
Follow
7likes 0comments
Bethefirsttocommentandstarttheconversation!
AvoidTheseRelationshipsLike
thePlague
Dr.TravisBradberry
UbersCEOsaysregulators
doomedacompanyjustlikehis
100yearsagoandhewon
ChipCutter
letithappenagain
3ReasonsNottoReadThis
ArticleonReversePsychology
A.J.Jacobs
VinoeDigitas:Understanding
Complexity
LouisD.LoPraeste
Thisyear'sgiftbagatTEDis
almostembarrassinglylarge
here'severythingitincludes
OliviaBarrow
Follow
ReporteratMilwaukeeBusinessJournal
IsUberredefiningtheworkweek?
Feb16,2016
455,226views
1,074Likes
306Comments
The9to5jobhasbeenoutofpopularityforseveralyears.Employerswhowant
toattractthetoptalentknowandtheyveknownforseveralyearsthat
theyvegottoofferflexibleschedulesasmuchaspossibleinordertoretainthe
mostindemandworkers.
https://www.linkedin.com/pulse/electricalisolationrequirementneutralwirefaraz
5/20