Catalogue2016
Compact NS
Circuit breakers and switch-disconnectors
from 630b to 3200 A
Green Premium
TM
Over 75% of
Schneider Electric
manufactured products
have been awarded the
Green Premium ecolabel
RoHS
Schneider Electric products are subject to RoHS requirements at
a worldwide level, even for the many products that are not required
to comply with the terms of the regulation. Compliance certificates are
available for products that fulfil the criteria of this European initiative,
which aims to eliminate hazardous substances.
REACh
Schneider Electric applies the strict REACh regulation on its products
at a worldwide level, and discloses extensive information concerning
the presence of SVHC (Substances of Very High Concern) in all of
these products.
Discover what we
mean by green .
Check your products!
Compact NS
Compact NS,
simply a step ahead
Compact NS630b to 1600 A
manually operated
electrically operated
Compact NS range
Consistency
Efficiency
The Compact NS
range is available
in 2 sizes only in
order to homogenise
installation dimensions,
thus reducing
switchboard dimensions
and facilitating their
installation: volume,
depth, pole pitch and
fastening points are
the same for each size.
The Compact NS
technology satisfies
all your needs from
630b to 3200 A, with
a breaking capacity
from 50 to 200 kA.
Flexibility
Openendedness
Compact NS adapts
to all your applications:
protection of AC
installations, generator
protection, motor
protection, applications
in 1000 V, switchdisconnectors, source
changeover switches.
With Compact NS
you have the choice.
OOFF
I ON
push
push
Compact NS
evolves together
with your installation:
interchangeable trip
units, standardised
accessories, changing
of rating without
disassembling the device
and addition of indication
and control functions
make Compact NS the
most flexible solution on
the market.
discharg
ed
O OFF
012
53
IFE
I/O
IFM
FDM121
FDM128
An answer for
each type of
solutions:
Marine
II
Airports
Wind mills
sizes:
> Manual
> Manual
kA
kA
630
NS
NS
50
70
kA
15
kA
20
0
LB
800
S1
0N
0
S10
00
S16
N
250
> Electrical
> Electrical
00
800
kA
0
kA
70
kA
15
NS
NS
160
NS
NS
50
30b
10
NS
0
125
70
N
kA
85
kA
0
200
250
NS
320
NS
N
0b
160
S
N
III
Energy management
has never been simpler
Simple-to-install Smart Panels connect your building to real savings
in 3 steps
Measure
Embedded and standalone metering & control
capabilities
Connect
IV
Save
Measure
CLOUD
connect
Save
CLOUD
On-line Energy
Management services
StruXureWare Energy Operation
automates data collection via an open,
scalable, and secure energy management
information system.
With the help of the Schneider Electric energy
management services team, data is then
turned into actionable information to enable
customers to understand their facilities
performance on an ongoing basis.
Energy Operation leverages companies
current investments in their existing systems,
and can be used to communicate advanced
results and performance to a broad audience
for a shared understanding throughout an
organization.
A solution
for all application types:
Compact NS and Compact NSX
Source changeover
The Compact range proposes interlocking
solutions between two devices to perform
the source changeover switch function.
As from 100 A, a motor mechanism ensures
automatic replacement of the main source
by a secondary source in order to ensure
permanent availability of energy.
Applications are numerous: operating
theatres, emergency lighting systems,
computer rooms, bank security, etc.
Motor applications
Associated with specific control units,
the Compact range ensures motor protection
functions up to 750 kW, and includes
a dedicated product, Compact NS80H-MA,
for applications up to 37 kW.
DC applications
A specific range from 100 to 630 A with
performance up to 100 kA and 750 V for
battery or traction network type applications.
1000 V / 400 Hz
applications
The Compact range covers 1000 V / 400Hz
applications up to 630 A: road and rail
tunnels, mines, wind turbines (1000 V) and
aircraft facilities (400 Hz).
Building
@@ Hotels
@@ Hospitals
@@ Offices
@@ Retail
VI
Data Centres
and Networks
Industry
@@ Airports
@@ Oil and gas
@@ Water
@@ Electrical energy
@@ Marine
for an installation
with a longer service life
Total control of
discrimination
for optimum
continuity of
supply
The result of a
technology that has
since inspired all
major manufacturers,
Compact NS offers
an unparalleled
discrimination level
on the electrical
distribution market.
Fully incorporated
in product design,
discrimination is
available as standard
on all the range
devices, without
addition of any extra
accessories.
Should a fault occur,
only the circuit breaker
placed immediately
upstream from the
fault trips.
Highly immune
protection
system
insensitive to
disturbances
for more reliable
operation
A comprehensive
range of trip
units and
control units
to combine
measurement
and protection
Insensitive to external
disturbances, the
Compact NS range
complies with the
strictest requirements
defined by standard
IEC 60947-2
(Appendix F).
It measures accurately
network parameters,
immediately calculates
values, memorises,
logs, reports,
communicates, acts,
etc. It is both an
extremely reliable
protection device
and an accurate
measuring instrument.
With the Micrologic
E and P power
measurement and
advanced protection
functions are now
available in the
Compact NS range.
Continuity of supply
is thus guaranteed for
the other feeders.
Electrical
Energy
Industry
Building,
shopping malls
Data centres
and networks
Hospitals
VII
Environmentally
friendly products
Tools
for easy design
Distribution and
service network
Full documentation,
CAD software and
a library are available
to assist you
in all stages of
installation design.
VIII
Schneider Electric
commits itself to
an environmental
approach,
manufacturing
products in keeping
with the requirements
of European Directive
RoHS (Restriction
of Hazardous
Substances) in
non-polluting
ISO 14001 certified
manufacturing units.
General contents
Presentation
A-1
A-1
Installation recommendations
B-1
B-1
C-1
C-1
Electrical diagrams
D-1
D-1
Additional characteristics
E-1
E-1
F-1
F-1
Presentation
Compact NS,
even more applications...
DB421282.eps
Applications
Protection of LV distribution systems > pages A-2 et A-25
or
5.0 E
Micrologic
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp
Icu
(kA)
Ue
100
(V)
85
220/240
480/690
Icu
100%
Ics =
100 %
40 %
IEC
OOFF
I ON
push
push
Protection for:
bb distribution systems supplied by
transformers
bb distribution systems supplied by engine
generator sets
bb long cables in IT and TN systems.
discharged
O OFF
UTE VDE
BS
menu
alarm
long
time
.8 .9
.95
.6.7
.98
.5
1
.4 x In
Ir
short
time
Isd3 4 5
6
8
2.5
2
1.5
10
x Ir
tr
8 12
16
2
20
1
24
.5 at 6 Ir
(s) 4
Ii
tsd .4 .4 .3
(s)
.3
.2
.1
on
I t
.2
.1
instantaneous
6
4
3
2
8 1012
15
off
x In
delay
setting
DB403916.eps
012
53
Installation :
bb in power switchboards.
All circuit breakers in the CompactNS range offer
positive contact indication and are suitable for
isolation in compliance with standards IEC
60947-1 and 2.
5.0 E
Micrologic
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp
Icu
(kA)
Ue
100
(V)
85
220/240
480/690
Icu
100%
100 %
Ics =
40 %
IEC
UTE VDE
BS
menu
alarm
long
time
.8 .9
.95
.6.7
.98
.5
1
.4 x In
Ir
short
time
Isd3 4 5
6
8
2.5
2
1.5
10
x Ir
tr
8 12
16
2
20
1
24
.5 at 6 Ir
(s) 4
Ii
tsd .4 .4 .3
(s)
.3
.2
.1
on
I t
.2
.1
instantaneous
6
4
3
2
8 1012
15
off
x In
delay
setting
DB403917.eps
DB403918.eps
Service connection
CompactNS service connection circuit
breakers are specially designed for the
service-connection function:
bb lead seals and locking systems
bb tripping curves certified by utilities
bb fast overload curves to limit the power
supplied, etc.
5.0 E
Micrologic
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp
Icu
(kA)
Ue
100
(V)
85
220/240
480/690
Icu
100%
100 %
Ics =
40 %
IEC
UTE VDE
BS
menu
alarm
long
Ir
time
.8 .9.95
.6.7
.98
.5
1
.4 x In
short
time
Isd3 4 5
6
2.5
8
2
10
1.5
x Ir
tr
8 12
16
2
20
1
24
.5 at 6 Ir
(s) 4
Ii
tsd .4 .4 .3
(s)
.3
.2
.1
on
I t
.2
.1
instantaneous
6
4
3
2
8 1012
15
off
x In
delay
DB421284.eps
setting
Icu
(kA)
Ue
100
(V)
85
220/240
480/690
Icu
100%
or
I ON
push
OOFF
push
discharged
O OFF
Ics =
IEC
UTE VDE
BS
012
53
DB419928.eps
Source-changeover systems
N
OOFF
I ON
push
push
OOFF
012
53
I ON
push
push
discharged
O OFF
discharged
O OFF
012
53
Presentation
Functions
PB111801-19_r.eps
PB106360r-50.eps
PB111801-32_r.eps
Operating-assistance functions
> page A-20
Integration of measurement functions provides
operators with operating assistance functions
including alarms tripped by user-selected
measurement values, time-stamped event tables and
histories, and maintenance indicators.
Communication
PB103798_9.eps
DB416830.eps
DB416829.eps
PB104831_ME.eps
screen 2b.eps
Introduction
Presentation
General characteristics
for NS630b to 3200 range
Compliance with standards
DB421306.eps
Compact
NS1600 H
Ui 800 V
Ue (V)
Uimp 8 kV
Icu(kA) Ics(kA)
220/240 a
380/415 a
440
a
70
37
70
37
500/525 a
660/690 a
65
37
50
30
42
22
IEC 60947-2
50/60Hz
AS UNE CEI BS
UTE
VDE NEMA
Compact
NS1600 H
Ui 800 V
Ue (V)
Uimp 8 kV
Icu(kA) Ics(kA)
220/240 a
380/415 a
440
a
85
37
70
37
65
37
50
30
42
22
500/525 a
660/690 a
Pollution degree
Tropicalisation
Compact NS circuit breakers have successfully passed the tests prescribed by the
following standards for extreme atmospheric conditions:
bb IEC 60068-2-1 - dry cold (-55 C)
bb IEC 60068-2-2 - dry heat (+85 C)
bb IEC 60068-2-30 - damp heat (95 % relative humidity at 55 C)
bb IEC 60068-2-52 - salt mist (severity level 2).
Environmental protection
50/60Hz
Compact NS circuit breakers take into account important concerns for environmental
protection. Most components are recyclable and the parts of Compact NS630b to
NS3200 circuit breakers are marked as specified in applicable standards.
IEC 60947-2
AS UNE CEI BS
UTE
VDE NEMA
Ambient temperature
Discrimination
DB128013.eps
CB1
CB2
DB401831.eps
All Compact NS circuit breakers are suitable for isolation as defined in IEC standard
60947-2:
bb the isolation position corresponds to the O (OFF) position
bb the operating handle cannot indicate the OFF position unless the contacts are
effectively open
bb padlocks may not be installed unless the contacts are open.
Installation of a rotary handle or a motor mechanism does not alter the reliability
of the position-indication system.
The isolation function is certified by tests guaranteeing:
bb the mechanical reliability of the position indication system
bb the absence of leakage currents
bb overvoltage withstand capacity between upstream and downstream connections.
All Compact NS circuit breakers are class II front face devices. They may be installed
through the door of class II switchboards (as per IEC standard 60664), without
downgrading switchboard insulation. Installation requires no special operations,
even when the circuit breaker is equipped with a rotary handle or a motor
mechanism.
Degree of protection
DB128016.eps
DB128015.eps
IP40
IK07
IP40
IK07
With toggle
IP40
IK07
IP40
IK07
IP55
DB128019.eps
DB128018.eps
DB128017.eps
IP435
IP547
IK08
tripped
reset
Protection of distribution
systems
Presentation
DB417643.eps
DB417642.eps
Overview of solutions
G
DB128023.eps
Power distribution
Selection of circuit breakers from 630 to 3200 A page A-2
Rated current (A)
250
630
NS630b
400
1000
NS1000
500
1250
NS1250
640
1600
NS1600
50
70
150
200
640
50
70
150
200
800 ...
50
70
150
1000
50
70
1250
50
70
-
1600
NS1600b
2000
NS2000
2500
NS2500
3200
NS3200
70
85
70
85
PB104844_ME.eps
Compact
320
800
NS800
Breaking capacity
(kA rms)
380/415 V
N
H
L
LB
PB104845_ME.eps
Compact
Breaking capacity
(kA rms)
380/415 V
N
H
70
85
Micrologic electronic control units may be used on all Compact NS630b to NS3200 circuit
breakers and can be changed on site.
Presentation 2
A-2
A-6
A-8
A-10
A-12
A-14
Operating-assistance functions
Switchboard-display functions
Communication
Earth-leakage protection
Overview of solutions
Source-changeover systems
Presentation
Manual source-changeover systems
Electrical interlocking
IVE unit
Remote-operated systems
Source-changeover systems
Associated controllers
A-18
A-20
A-21
A-23
A-25
A-28
A-30
A-31
A-32
A-33
A-34
A-36
A-38
A-39
A-40
A-42
A-44
A-45
A-46
A-48
A-50
A-52
A-53
A-54
A-55
A-56
A-58
A-59
A-60
A-77
A-78
B-1
C-1
D-1
E-1
F-1
A-1
Protection of distribution
systems
Compact NS circuit breakers
from 630b up to 3200 A
PB104842.eps
Number of poles
Control
manual
electric
Type of circuit breaker
Connections
fixed
withdrawable (on chassis)
Electrical characteristics as per Nema AB1
Breaking capacity at 60 Hz (kA)
PB104831_ME.eps
Compact NS800L.
PB104843.eps
Compact NS1600H.
Compact NS2000H.
A-2
toggle
direct or extended rotary handle
front connection
rear connection
front connection with bare cables
front connection
rear connection
240 V
480 V
600 V
NS630b
3, 4
b
b
b (except LB)
N
H
b
b
b
b
b
b
b
b
b
b
N
H
50
65
35
50
25
50
630
630
800
8
690
N
85
50
50
40
30
50
50
50
40
30
50
50
50
40
30
37
37
37
30
22
19.2
40
b
B
10000
6000
5000
4000
2000
3
NS800
L
b
b
b
b
L
125
100
-
LB
b
b
b
LB
200
200
100
800
800
H
85
70
65
50
42
50
50
50
40
30
70
70
65
50
42
37
37
37
30
22
19.2
40
L
150
150
130
100
150
150
130
100
150
150
130
100
150
150
130
100
-
LB
200
200
200
100
75
200
200
200
100
75
-
6000
5000
4000
2000
4000
3000
3000
2000
4000
3000
3000
2000
NS1000
3, 4
b
b
b
N
b
b
b
b
b
N
50
35
25
1000
1000
800
8
690
N
85
50
50
40
30
50
50
50
40
30
50
50
50
40
30
37
37
37
30
22
19.2
40
b
B
10000
6000
5000
4000
2000
3
H
b
b
b
b
b
H
65
50
50
NS1250
L
b
b
b
b
L
125
100
-
H
85
70
65
50
42
52
52
48
37
31
70
70
65
50
42
37
37
37
30
22
19.2
40
L
150
150
130
100
150
150
130
100
150
150
130
100
150
150
130
100
-
6000
5000
4000
2000
4000
3000
3000
2000
3, 4
b
b
b
N
b
b
b
b
b
N
50
35
25
1250
1250
800
8
690
N
85
50
50
40
30
50
50
50
40
30
50
50
50
40
30
37
37
37
30
22
19.2
40
b
B
10000
5000
4000
3000
2000
3
H
b
b
b
b
b
H
65
50
50
H
85
70
65
50
42
52
52
48
37
31
70
70
65
50
42
37
37
37
30
22
19.2
40
B
NS1600
3, 4
b
b
b
N
b
b
b
b
N
50
35
25
1600
1510
800
8
690
N
85
50
50
40
30
37
37
37
30
22
50
50
50
40
30
37
37
37
30
22
19.2
40
b
B
10000
5000
2000
2000
1000
3
H
b
b
b
b
H
65
50
50
H
85
70
65
50
42
37
37
37
30
22
70
70
65
50
42
37
37
37
30
22
19.2
40
B
NS1600b
3, 4
b
N
b
N
85
65
50
1600
1550
800
8
690
N
85
70
65
65
65
65
52
65
65
65
-
NS2000
NS2500
NS3200
2000
1900
2500
2500
3200
2970
H
b
H
125
85
-
H
125
85
85
94
64
64
-
32
130
b
B
5000
3000
2000
2000
1000
3
A-3
Protection of distribution
systems
Compact NS circuit breakers
from 630b up to 3200 A
PB104831_ME.eps
long time
Ir (In x )
short time
Isd (Ir x )
instantaneous Ii (In x )
lg (In x )
In
ZSI
Earth-fault protection
Residual earth-leakage protection
Zone selective interlocking
Protection of the fourth pole
Current measurements
Power measurements
Advanced protection
Quick view
Remote communication by bus
Device-status indication
Device remote operation (2)
Transmission of settings
Indication and identification of protection devices and alarms
Transmission of measured current values
A-4
NS630b
Micrologic
2.0
5.0
b
b
b
b
b
b
b
b
b
-
b
b
-
NS630b
NS800
NS1000
NS1250
NS1600
NS1600b
NS2000
NS2500
NS3200
6.0
b
b
b
b
b
-
2.0 A
b
b
b
b
b
-
5.0 A
b
b
b
b
b
b
-
6.0 A
b
b
b
b
b
b
b
-
7.0 A
b
b
b
b
b
b
b
-
2.0 E
b
b
b
b
b
b
b
5.0 E
b
b
b
b
b
b
b
b
6.0 E
b
b
b
b
b
b
b
b
b
5.0 P (1)
b
b
b
b
b
b
b
b
-
6.0 P (1)
b
b
b
b
b
b
b
b
b
-
7.0 P (1)
b
b
b
b
b
b
b
b
b
-
b
b
-
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
NS800
NS1000
NS1250
NS1600
NS1600b
b
b
b
b
b
b
b
327 x 210 x 147
327 x 280 x 147
14
18
b
b
350 x 420 x 160
350 x 535 x 160
24
36
NS2000
NS2500
NS3200
A-5
Overview of functions
Dependability
Accessories
Current protection
Micrologic 2: basic protection
Protection:
long time
+ instantaneous
DB128024.eps
2.0 E
X Y Z
X: type of protection
bb 2 for basic protection
bb 5 for selective protection
bb 6 for selective + earth-fault protection
bb 7 for selective + earth-leakage protection.
Y: control-unit generation
Identification of the control-unit generation.
0 signifies the first generation.
Protection:
long time
+ short time
+ instantaneous
PB100772R-32.eps
PB106351A32.eps
DB128025.eps
Z: type of measurement
bb A for ammeter
bb E for energy
bb P for power meter
DB128027.eps
DB128025.eps
A-6
DB128045.eps
DB128025.eps
Micrologic without
measurement
Micrologic 2.0 E
DB128302.eps
2.0 E
Micrologic 2.0 A
100 %
100 %
40 %
40 %
menu
menu
alarm
.7
.6
.5
.4
instantaneous
Isd
2.5
2
1.5
4 5
x Ir
long time
Ir
at 6 Ir
5.0 E
100 %
100 %
40 %
40 %
x In
.7
.6
.5
.4
instantaneous
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
I t
Ii
6
4
3
2
delay
x In
x In
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
6.0 A
.7
.6
.5
.4
I t
Ii
instantaneous
6
4
3
2
.7
.6
.5
.4
Isd
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
delay
100 %
40 %
40 %
4 5
x Ir
6
8
10
tsd
. 4 .4 . 3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
Ig
D E F
G
C
H
B
I
A
I t
delay
Ii
instantaneous
4
3
Isd
8 10
12
15
off
2
x In
. 4 .4 . 3
.2
.3
.1
.2
.1 2 0
I t
6
8
10
x Ir
off
ground fault
.7
.6
.5
.4
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
Ii
instantaneous
4
3
I t
8 10
12
15
off
2
x In
delay
D E F
G
C
H
B
I
A
.4 .4 .3
.2
.3
.1
.2
.1 2 0
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
6.0 P
alarm
@ 6 Ir
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
8 10
12
15
off
x In
I t
Ii
instantaneous
4
3
off
6 8 10
12
15
off
2
x In
delay
test
Micrologic 6.0 P
4260A
N 1 2 3
100
50
I t
x Ir
off
alarm
6
8
10
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
I t
delay
.7
.6
.5
.4
Ii
instantaneous
4
3
D
C
B
A
off
ground fault
alarm
@ 6 Ir
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
Ig
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
I t
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
8 10
12
15
off
2
x In
test
tg
on
long time
Ir
at 6 Ir
4 5
D E F
G
C
H
B
I
A
I t
Ii
instantaneous
4
3
off
6 8 10
12
15
off
2
x In
delay
test
tg
F
G
H
J
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
I t
off
ground fault
7.0 P
Micrologic 7.0 A
DB128301.eps
delay
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
short time
3
2.5
2
1.5
Ig
(s)
on
Isd
test
tg
ground fault
7.0 A
I t
instantaneous
6
4
3
2
long time
Ir
alarm
at 6 Ir
4 5
Ig
(s)
on
x In
setting
test
tg
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
short time
3
2.5
2
1.5
on
long time
Ir
.7
.6
.5
.4
Ii
menu
long time
.8
.4 .4 .3
.2
.3
.1
.2
.1 2 0
Micrologic 6.0 E
100 %
.7
.6
.5
.4
alarm
at 6 Ir
tsd
(s)
setting
6.0 E
Micrologic 6.0 A
Ir
at 6 Ir
short time
3
2.5
2
1.5
alarm
N 1 2 3
tr
(s) 4 8 12
.9
16
.95
2
.98 1
20
24
1
.5
.8
x In
short time
Isd 4
5
3
2.5
6
2
8
1.5
10
x Ir
8 10
12
15
off
x In
menu
long time
Ir
4260A
100
50
long time
Ir
alarm
at 6 Ir
short time
Isd 4
5
3
2.5
6
2
8
1.5
10
x Ir
10
12
15
off
Micrologic 6.0
DB128286.eps
tr
(s) 4 8 12
.9
16
.95
2
.98 1
20
24
1
.5
.8
Micrologic 5.0 P
menu
long time
Ir
at 6 Ir
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
6.0
alarm
DB128307.eps
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
DB128300.eps
.7
.6
.5
.4
5.0 P
Micrologic 5.0 E
menu
long time
Ir
6
8
10
x Ir
setting
Micrologic 5.0 A
DB128299.eps
5.0 A
at 6 Ir
3 4 5
2.5
2
1.5
6
8
10
x Ir
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
instantaneous
Isd
setting
Micrologic 5.0
DB128374.eps
.7
.6
.5
.4
3 4 5
2.5
2
1.5
8
10
long time
Ir
at 6 Ir
instantaneous
Isd
setting
5.0
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
DB128308.eps
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
DB128306.eps
.7
.6
.5
.4
DB128309.eps
long time
Ir
Micrologic 7.0 P
DB128321.eps
DB128290.eps
2.0 A
Micrologic 2.0
DB128372.eps
2.0
4260A
N 1 2 3
100
50
100 %
40 %
menu
Ir
long time
.7
.6
.5
.4
.8
x In
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
short time
Isd
4 5
3
6
2.5
8
2
1.5
10
x Ir
setting
.4 .4 .3
.2
.3
.1
.2
.1 2 0
on
I t
off
delay
In 5 7 I 230 350
3
10
2
140
20
1
800
60
30
.5
earth leakage
alarm
long time
Ir
.7
.6
.5
.4
at 6 Ir
tsd
(s)
Ii
instantaneous
8 10
12
15
2
off
x In
6
4
3
test
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
setting
In
(A)
3
2
1
.5
alarm
@ 6 Ir
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
I t
off
delay
t
(ms)
230
10
140
20
30
60
7
Ii
instantaneous
4
3
6 8 10
12
15
off
2
x In
test
350
800
earth leakage
A-7
DB414487.eps
Protection
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection can be cancelled using a specific LT rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2) or
neutral protection at Ir (4P 4d).
Indications
Overload indication by alarm LED on the front; the LED goes on when the current
exceeds the long-time trip threshold.
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation after installing the trip unit or accessories.
Ir
long time
.7
.6
.5
.4
Isd
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
at 6 Ir
short time
3
2.5
2
1.5
4 5
x Ir
alarm
6
8
10
tsd
. 4 .4 . 3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
Ig
D E F
G
C
H
B
I
A
I t
delay
Ii
instantaneous
4
3
8 10
12
15
off
2
x In
test
tg
. 4 .4 . 3
.2
.3
.1
.2
.1 2 0
(s)
on
I t
off
ground fault
1
2
3
4
5
6
7
8
A-8
Micrologic 2.0
Long time
Current setting (A)
Ir = In x
tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
accuracy: 0 to -30 %
accuracy: 0 to -20 %
accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Isd = Ir x
1.5
Ir
tr
Isd
0
10
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98 1
Other ranges or disable by changing long-time rating plug
0.5
1
2
4
8
12
16
20
24
12.5 25
50
100 200 300 400 500 600
2
4
8
12
16
20
24
0.7(1) 1
5.5
8.3
11
13.8 16.6
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
DB128032.eps
Long time
Current setting (A)
Ir = In x
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Short time
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Settings
Time setting tsd (s)
Earth fault
Pick-up (A)
Accuracy: 10 %
2.5
24
600
24
16.6
Protection
2.5
10
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
10
12
15
off
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
I2t on
tr
I2t off
Isd
tsd
Ii
0
1.5
Ir
Micrologic 6.0
A
B
C
D
0.3
0.3
0.4
0.5
0.2
0.3
0.4
0.5
500 640 720 800
I2t Off
0
0.1
0.2
0.3
Time setting tg (s)
0.1
0.2
0.3
I2t On
20
80
140 230
Time delay (ms)
tg (max resettable time)
tg (max break time)
80
140 200 320
at In or 1200 A (I2t Off or I2t On)
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
Ig = In x
In y 400 A
400 A < In < 1250 A
In u 1250 A
Settings
DB128036.eps
Instantaneous
Pick-up (A)
accuracy: 10 %
Time delay
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98
other ranges or disable by changing long-time rating plug
0.5
1
2
4
8
12
16
20
12.5 25
50
100
200
300
400
500
0.7 (1) 1
2
4
8
12
16
20
0.7 (2) 0.69 1.38 2.7
5.5
8.3
11
13.8
20 minutes before and after tripping
DB128031.eps
Protection
A-9
DB128033.eps
"Ammeter" measurements
Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
bb settings
bb all ammeter measurements
bb tripping causes
bb maximeter readings.
Protection
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug.
Overload protection can be cancelled using a specific LT rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Residual earth-leakage protection (Vigi).
Operation without an external power supply.
q Protected against nuisance tripping.
k DC-component withstand class A up to 10 A.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
Fault indications
Test
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units,
the operation of earth-fault or earth-leakage protection can be checked by pressing
the test button located above the test connector.
A-10
Micrologic 2.0 A
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
Ammeter
Type of measurements
Instantaneous currents
tr
Isd
1.5
2.5
10
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
ANSI Code 50
Ii = In x
2.5
10
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
10
12
15
off
D
0.5
0.5
800
0.3
0.3
230
320
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
10
20
30
350
350
500
800
800
1000
I2t on
tr
I2t off
Isd
tsd
Ii
0
1.5
Ir
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
ANSI Code 51G
IDn
Micrologic 6.0 A
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500 640 720
0
0.1
0.2
0.1
0.2
20
80
140
80
140 200
Micrologic 7.0 A
0.5
1
2
Settings
Dt (max resettable time)
Dt (max break time)
60
60
140
140
140
200
230
230
320
DB128036.eps
Earth fault
Pick-up (A)
Accuracy: 10 %
Ir
DB128037.eps
Protection
Long time
ANSI Code 49
Current setting (A)
Ir = In x
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Short time
ANSI Code 51
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Settings
Time setting tsd (s)
0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98 1
Other ranges or disable by changing long-time rating plug
0.5
1
2
4
8
12
16
20
24
12.5 25
50
100 200 300 400 500 600
2
4
8
12
16
20
24
0.7(1) 1
5.5
8.3
11
13.8 16.6
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
DB128032.eps
Long time
ANSI Code 49
Current setting (A)
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Instantaneous
ANSI Code 50
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Time delay
DB128031.eps
Protection
Range
0.2 x In to 1.2 x In
I1, I2, I3, IN
0.2 x In to In
Ig (6.0 A)
0 to 30 A
IDn (7.0 A)
0.2 x In to 1.2 x In
Current maximeters of
I1, I2, I3, IN
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
Accuracy
1.5 %
10 %
1.5 %
1.5 %
A-11
DB128038.eps
Communication option
In conjunction with the COM communication option, the control unit transmits the
following:
bb settings
bb all "ammeter" and "energy" measurements
bb enable connection to FDM128
bb tripping causes
bb maximeter / minimeter readings.
Protection
14
15
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Thermal memory: thermal image before and after tripping.
Setting accuracy may be enhanced by limiting the setting range using a different
long-time rating plug. Overload protection can be cancelled using a specific LT
rating plug "Off".
Short-circuit protection
Short-time (rms) and instantaneous protection.
Selection of I2t type (ON or OFF) for short-time delay.
Earth-fault protection
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI terminal block may be used to interconnect a number of control units to provide
total discrimination for short-time and earth-fault protection, without a delay before
tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
1 long-time threshold and tripping delay
2 overload alarm (LED) at 1.125 Ir
3 short-time pick-up and tripping delay
4 instantaneous pick-up
5 earth-leakage or earth-fault pick-up and tripping delay
6 earth-leakage or earth-fault test button
7 long-time rating plug screw
8 test connector
9 lamp test, reset and battery test
10 indication of tripping cause
11 digital display
12 three-phase bargraph and ammeter
13 navigation button "quick View" (only with Micrologic E)
14 navigation button to view menu contents
15 navigation button to change menu
Programmable contacts
Fault indications
Test
(1) Display on FDM121 only.
Note: Micrologic E control units come with a transparent
lead-seal cover as standard.
A-12
A mini test kit or a portable test kit may be connected to the test connector on the
front to check circuit-breaker operation. For Micrologic 6.0 E control units, the
operation of earth-fault or earth-leakage protection can be checked by pressing the
test button located above the test connector.
Micrologic 2.0 E
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
Earth fault
Pick-up (A)
Accuracy: 10 %
Energy
Type of measurements
Instantaneous currents
Ir
tr
Isd
1.5
2.5
10
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
ANSI Code 50
Ii = In x
2.5
10
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
10
12
15
off
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
I2t on
tr
I2t off
Isd
tsd
Ii
0
1.5
Ir
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
Micrologic 6.0 E
A
B
C
0.3
0.3
0.4
0.2
0.3
0.4
500 640 720
0
0.1
0.2
0.1
0.2
20
80
140
80
140 200
D
0.5
0.5
800
0.3
0.3
230
320
DB128036.eps
Protection
Long time
ANSI Code 49
Current setting (A)
Ir = In x
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Short time
ANSI Code 51
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Settings
Time setting tsd (s)
0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98 1
Other ranges or disable by changing long-time rating plug
0.5
1
2
4
8
12
16
20
24
12.5 25
50
100 200 300 400 500 600
2
4
8
12
16
20
24
0.7(1) 1
5.5
8.3
11
13.8 16.6
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
DB128032.eps
Long time
ANSI Code 49
Current setting (A)
Tripping between 1.05 and 1.20 x Ir
Time setting
Time delay (s)
Accuracy: 0 to -30 %
Accuracy: 0 to -20 %
Accuracy: 0 to -20 %
Thermal memory
(1) 0 to -40 % - (2) 0 to -60 %
Instantaneous
ANSI Code 50
Pick-up (A)
Isd = Ir x
Accuracy: 10 %
Time delay
DB128031.eps
Protection
Range
0.2 x In to 1.2 x In
I1, I2, I3, IN
Ig (6.0 E)
0.05 x In to In
0.2 x In to 1.2 x In
Current maximeters of
I1, I2, I3, IN
0.2 x In to 1.2 x In
Demand currents of I1, I2, I3, Ig
Voltages
V12, V23, V31, V1N, V2N, V3N 100 to 690 V
Active power
P
30 to 2000 kW
Power factor
PF
0 to 1
Demand power
P demand
30 to 2000 kW
Active energy
Ep
-1010 GWh to 1010 GWh
Note: all current-based protection functions require no auxiliary source.
The test / reset button resets maximeters, clears the tripping indication and tests the battery.
Accuracy
1.5 %
10 %
1.5 %
1.5 %
0.5 %
2 %
2 %
2 %
2 %
A-13
DB128042.eps
Protection.........................................................
Protection settings
Depending on the thresholds and time delays set using the keypad or remotely using
the COM option, the Micrologic P control unit monitors currents and voltage, power,
frequency and the phase sequence. Each threshold overrun is signalled remotely via
the COM option. Each threshold overrun may be combined with tripping (protection)
or an indication carried out by an optional M6C programmable contact (alarm), or
both (protection and alarm).
Load shedding and reconnection parameters may be set according to the power or
the current flowing through the circuit breaker. Load shedding is carried out by a
supervisor via the COM option or by an M6C programmable contact.
The M6C (six contacts) auxiliary contacts may be used to signal threshold overruns
or status changes. They can be programmed using the keypad on the Micrologic P
control unit or remotely using the COM option (BCM ULP) and RSU software.
A-14
Earth fault
Pick-up (A)
Accuracy: 10 %
Time setting tg (s)
Time delay (ms)
at In or 1200 A (I2t Off or I2t On)
Residual earth leakage (Vigi)
Sensitivity (A)
Accuracy: 0 to -20 %
Time delay Dt (ms)
I2t Off
I2t On
Settings
Dt (max resettable time)
Dt (max break time)
Current
Current unbalance
Max. demand current
Earth fault alarm
Voltage
Voltage unbalance
Minimum voltage
Maximum voltage(4)
Power
Reverse power
Frequency
Minimum frequency
Maximum frequency
Phase sequence
Sequence (alarm)
2.5
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
140
140
200
230
230
320
350
350
500
10
10
12
15
off
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
10
20
30
Threshold
0.05 to 0.6 Iaverage
0.2 In to In
Delay
1 to 40 s
15 to 1500 s
It
10 to 100 % In(3)
1 to 10 s
Uunbalance
Umin
Umax
ANSI Code
47
27
59
2 to 30 % x Uaverage
1 to 40 s
100 to Umax between phases 1.2 to 10 s
Umin to 1200 between phases 1.2 to 10 s
rP
32P
5 to 500 kW
0.2 to 20 s
Fmin
Fmax
81L
81H
45 to Fmax
Fmin to 440 Hz
1.2 to 5 s
1.2 to 5 s
1/2/3 or 1/3/2
0.3 s
I
P
Threshold
0.5 to 1 Ir per phases
200 kW to 10 MW
Delay
20 % tr to 80 % tr
10 to 3600 s
Power
Type of measurements
Range
Accuracy
0.2 x In to 1.2 x In
1.5 %
Current maximeters of
Voltages
0.5 %
Power factor
PF
2%
Frequency (Hz)
DB128043.eps
800
800
1000
ANSI Code 46
Iunbalance
Imax demand : I1, I2, I3, IN,
Measured value
Current
Power
DB128044.eps
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
ANSI Code 50
Ii = In x
1.5
DB128045.eps
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
DB128046.eps
DB128047.eps
Protection
0 to 1
0.1 %
(3) In y 400 A 30 %
(4) For 690 V applications, a step-down transformer must be used if the voltage exceeds the nominal value of 690 V by more
400 A < In < 1250 A 20 %
than 10 %.
In u 1250 A 10 %
Note: all current-based protection functions require no auxiliary source.
Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker.
A-15
Measurements..........................................................
DB101134.eps
DB101133.eps
Micrologic P "power"
Default display.
The Micrologic P control unit calculates in real time all the electrical values (V, A, W,
VAR, VA, Wh, VARh, VAh, Hz), power factors and cosj factors.
The Micrologic P control unit also calculates demand current and demand power
over an adjustable time period. Each measurement is associated with a minimeter
and a maximeter.
In the event of tripping on a fault, the interrupted current is stored. The optional
external power supply makes it possible to display the value with the circuit breaker
open or not supplied.
Display of a maximum
current.
Instantaneous values
The value displayed on the screen is refreshed every second.
Minimum and maximum values of measurements are stored in memory (minimeters
and maximeters).
Currents
DB101133.eps
DB101133.eps
I rms
I max rms
Voltages
U rms
V rms
U average rms
U unbalance
Power, energy
P active, Q reactive, S apparent
E active, E reactive, E apparent
Display of a power.
DB101138.eps
DB101137.eps
Display of a voltage.
Power factor
Frequencies
F
A
A
A
A
1
E-fault
1
E-fault
V
V
V
%
12
23
31
1N
2N
3N
(U12 + U23 + U31) / 3
W, Var, VA
Wh, VARh, VAh
Totals
Totals consumed - supplied
Totals consumed
Totals supplied
PF
Total
3
N
E-leakage
3
N
E-leakage
Hz
Demand metering
The demand is calculated over a fixed or sliding time window that may be
programmed from 5 to 60 minutes. According to the contract signed with the power
supplier, an indicator associated with a load shedding function makes it possible to
avoid or minimise the costs of overrunning the subscribed power. Maximum demand
values are systematically stored and time stamped (maximeter).
Currents
I demand
I max demand
Display of a frequency.
Power
P, Q, S demand
P, Q, S max demand
A
A
A
A
1
E-fault
1
E-fault
W, Var, VA
W, Var, VA
Totals
Totals
2
2
3
N
E-leakage
3
N
E-leakage
screen 2b.eps
PME software.
A-16
Additional info
Accuracy of measurements (including sensors):
bb voltage (V) 0.5 %
bb current (A) 1.5 %
bb frequency (Hz) 0.1 %
bb power (W) and energy (Wh) 2 %.
DB101140.eps
DB117041.eps
The last ten trips and alarms are recorded in two separate history files that may be
displayed on the screen:
bb tripping history:
vv type of fault
vv date and time
vv values measured at the time of tripping (interrupted current, etc.)
bb alarm history:
vv type of alarm
vv date and time
vv values measured at the time of the alarm.
Display after tripping.
All the other events are recorded in a third history file which is only accessible
through the communication network.
bb Event log history (only accessible through the communication network)
vv modifications to settings and parameters
vv counter resets
vv system faults
vv fallback position
vv thermal self-protection
vv loss of time
vv overrun of wear indicators
vv test-kit connections
vv etc.
Note: all the events are time stampled: time-stamping is activated as soon as time is set
manually or by a supervisor. No external power supply module is required (max. drift of 1 hour
per year).
Safety
Measurement functions are independent of the protection functions.
The high-accuracy measurement module operates independently of the protection
module.
Simplicity and multi-language
Navigation from one display to another is intuitive. The six buttons on the keypad
provide access to the menus and easy selection of values. When the setting cover is
closed, the keypad may no longer be used to access the protection settings, but still
provides access to the displays for measurements, histories, indicators, etc.
Micrologic is also multi-language, including the following languages: English,
Spanish, Portuguese, Russian, Chinese, French, German...
Intelligent measurement
Measurement-calculation mode:
bb energies are calculated on the basis of the instantaneous power values, in two
manners:
vv the traditional mode where only positive (consumed) energies are considered
vv the signed mode where the positive (consumed) and negative (supplied) energies
are considered separately
bb measurement functions implement the new zero blind time concept which
consists in continuously measuring signals at a high sampling rate. The traditional
blind window used to process samples no longer exists. This method ensures
accurate energy calculations even for highly variable loads (welding machines,
robots, etc.).
Always powered
All current-based protection functions require no auxiliary source. Voltage-based
protection functions are connected to AC power via a voltage measurement input
built into the circuit breaker.
Stored information
The fine setting adjustments, the last 100 events and the maintenance register
remain in the control-unit memory even when power is lost.
A-17
Display....................................................................
DB417640.eps
Main Menu
Quick view
Metering
Control
Alarms
20.12.2011
12:00:05
S1-1 - Lighting/Level1
Quick view
Open
Alarm history
Control
OK
Ir
Maintenance
000 A
ESC
310
%
I3 302
315
%
ESC
S1-1 - Lighting/Level1
Quick view
Alarm history
Control
Maintenance
4/7
402 V
100
120
398 V
100
120
401 V
100
120
Quick view
Control
Maintenance
12:00:05
64
kW
kVar
51
kVA
Quick view
Control
ESC
Maintenance
12:00:05
kWh
8325
kVarh
Es
13035
kVAh
Quick view
Control
1/12
12:00:05
U-V
E cumul
EpIn
EpOut
Maintenance
ESC
A-18
S1-1 - Lighting/Level1
Alarm history
FDM121 display:
consumption.
Examples of measurement
screens on the FDM121
display unit.
PQS
127 kW
13 kVAr
129 kVA
Ptot
Qtot
Stot
20.12.2011
Measures
ESC
U-V
PQS
DB414403.eps
14397
V
V
V
1/10
ESC
Eq
406
415
409
The Micrologic continuously display the RMS value of the highest current of the three
phases and neutral (Imax). The navigation buttons can be used to scroll through the
main measurements.
In the event of a fault trip, the trip cause is displayed.
The Micrologic A measures phase, neutral, ground fault currents.
The Micrologic E offers voltage, power, Power Factor, measurements in addition to
the measurements provided by Micrologic A.
The Micrologic P offer frequency, cos.j in addition to the measurements provided by
Micrologic E.
Maximeters / minimeters
S1-1 - Lighting/Level1
Alarm history
PQS
20.12.2011
Measures
Ep
U-V
VL L
VL-L
V12
V23
V31
For all FDM, in addition to the information displayed on the Micrologic LCD, the FDM
screen shows demand, power quality and maximeter/minimeter values along with
histories and maintenance indicators.
Measurements.......................................................
DB414402.eps
DB112133.eps
38
A
A
A
A
1/10
ESC
S1-1 - Lighting/Level1
Measures
ESC
PQS
PQS
431
385
426
2
I1
I2
I3
IN
20.12.2011
Alarm history
U-V
I Current
DB414401.eps
DB112132.eps
U3
12:00:05
ESC
U2
The FDM121 switchboard display unit can be connected to a COM option (BCM
ULP) using a breaker ULP cord to display all measurements on a screen (1). The
result is a veritable 96 x 96 mm Power Meter.
The FMD121 display unit requires a 24 V DC power supply. The COM option (BCM
ULP) unit is supplied by the same power supply via the breaker ULP cord connecting
it to the FDM121.
Measures
U1
%
IN 23
000 A
I1
1/7
DB414400.eps
DB112131.eps
I1
Auto
Measures
Services
ESC
DB112134.eps
1/3
FDM128 display:
consumption.
PQS
E
Reset
165 kWh
45 kWh
Energy metering
The Micrologic E/P also measures the energy consumed since the last reset of the
meter. The active energy meter can be reset via Micrologic keypad or the FDM
display unit or the communication system.
Micrologic E/P also calculates demand current and power values. These calculations
can be made using a block or sliding interval that can be set from 5 to 60 minutes in
steps of 1 minute. The window can be synchronised with a signal sent via the
communication system. Whatever the calculation method, the calculated values can
be recovered on a PC via Modbus communication.
Ordinary spreadsheet software can be used to provide trend curves and forecasts
based on this data. They will provide a basis for load shedding and reconnection
operations used to adjust consumption to the subscribed power.
PB106351A13.eps
PB111801-32_r_1.eps
PB103360_r.eps
PB104831_ME_23.eps
PB104842_24.eps
Type
Display
A/E
Micrologic
LCD
FDM display
A/E
Measurements
Instantaneous rms measurements
Currents (A)
A/E
Average of phases
A/E
A/E
% Ig (pick-up setting)
A/E
- /E
Phase-to-phase
- /E
Phase-to-neutral
- /E
- /E
Average of phase-to-neutral
voltages
- /E
- /E
Phase sequence
-/-
b (3)
1-2-3, 1-3-2
Frequency (Hz)
Power system
-/-
Power
Active (kW)
P, total
- /E
P, per phase
- /E
b (2)
Reactive (kVAR)
Q, total
- /E
Q, per phase
-/-
Apparent (kVA)
S, total
- /E
S, per phase
-/-
Power Factor
PF, total
- /E
-/-
Cos.j, total
-/-
-/-
A/E
- /E
- /E
- /E
b (2)
- /E
- /E
b (2)
- /E
Cos.j
Maximeters / minimeters
Energy metering
Energy
Demand power
Calculation window
A-19
Operating-assistance functions
Micrologic A/E/P control unit
with COM option (BCM ULP)
Histories.................................................................
bb Trip indications in clear text in a number of user-selectable languages.
bb Time-stamping: date and time of trip.
Maintenance indicators.........................................
Micrologic control unit have indicators for, among others, the number of operating
cycles, contact wear P, load profile and operating times (operating hours counter) of
the Masterpact circuit breaker.
It is possible to assign an alarm to the operating cycle counter to plan maintenance.
The various indicators can be used together with the trip histories to analyse the
level of stresses the device has been subjected to.
Each circuit breaker equipped with a COM option (BCM ULP) can be identified via
the communication system:
bb serial number
bb firmware version
bb hardware version
bb device name assigned by the user.
This information together with the previously described indications provides a clear
view of the installed devices.
Type
Display
A/E
Micrologic
LCD
FDM121
display
- /E
b
b
Operating assistance
Trip history
Trips
Cause of tripping
Maintenance indicators
Counter
Indicator
Mechanical cycles
Assignable to an alarm
A/E
Electrical cycles
Assignable to an alarm
A/E
Hours
A/E
Contact wear
-/-
A /E
Load profile Hours at different load levels % of hours in four current ranges: 0-49 % In, 50-79 %
In, 80-89 % In and u 90 % In
(1) Also available via the communication system.
A-20
Switchboard-display functions
Micrologic A/E/P control unit
with COM option (BCM ULP)
Micrologic measurement capabilities come into full play
with the FDM121 switchboard display. It connects to
COM option (BCM ULP) via a breaker ULP cord and
displays Micrologic information. The result is a true
integrated unit combining a circuit breaker and a Power
Meter. Additional operating assistance functions can
also be displayed.
PB103807-32.eps
PB103582-32.eps
Main characteristics
Surface mount accessory.
PB103581-31.eps
FDM121 display.
Mounting
Connection
Connection with FDM121 display unit.
Switchboard-display functions
310
%
I3 302
315
2 Down
3 OK
4 Up
5 Context
6 Alarm LED
2 3 4
5 6
Produit Id
Micrologic 5.3A
Serial number:
Part number:
P07451
PQS
E
1.02
ESC
EpIN
5111947
kWh
EpOut
12345678
kWh
F - PF - cos
OK
Load Profile
0..49%
ESC
Services.
Control
2/3
610 H
50...79%
15 H
80..89%
360 H
90..100%
Metering: meter.
Metering
Metering: sub-menu.
DB125912.eps
Product identification.
1/3
Main menu
When powered up, the FDM121 screen automatically displays the ON/OFF status of
the device.
U-V
ESC
NonResettableEnergy
Screens
Metering
LU432091
Firmware:
Navigation
When not in use, the screen is not backlit. Backlighting can be activated by pressing
one of the buttons. It goes off after 3 minutes.
Fast access to essential information
bb Quick view provides access to five screens that display a summary of essential
operating information (I, U, f, P, E, THD, circuit breaker On / Off).
Access to detailed information
bb "Metering" can be used to display the measurement data (I, U-V, f, P, Q, S, E,
THD, PF) with the corresponding min/max values.
bb Alarms displays active alarms and the alarm history.
bb Services provides access to the operation counters, energy and maximeter reset
bb function, maintenance indicators, identification of modules connected to the
internal bus and FDM121 internal settings (language, contrast, etc.).
3H
ESC
Services.
DB416695.eps
Ethernet
Modbus-SL
- +
DB112136.eps
I2
%
IN 23
%
ESC
DB112140.eps
1 Escape
I1
- +
DB112135.eps
IFM
ETH2
IFE
OR
E
F
C
Red Black
White Blue
E1 E2 E3 E4 E5 E6
E1 E2 E3 E4 E5 E6
B / Rx+ D1
A / Rx- D0
B / Tx+ D1
0V
A-22
A Modbus network
B Ethernet network
C Breaker ULP cord
White Blue
Red Black
A / Tx- D0
Connections
bb Compact NS is connected to the ULP
devices (FDM121 display, IFM, IFE or
I/O application module) unit via the
breaker ULP cord.
vv cord available in three lengths:
0.35 m, 1.3 m and 3 m.
vv lengths up to 10 m possible using
extensions.
24 V
B / Rx+ D1
A / Rx- D0
B / Tx+ D1
0V
A / Tx- D0
24 V
D FDM121 display
E ULP termination
F ULP cable
Switchboard-display functions
Micrologic A/E/P control unit
with COM Ethernet gateway
Micrologic measurement capabilities come into full play
with the FDM128 switchboard display. It connects to
Ethernet communication via RJ45 port and displays
Micrologic information. The result is a true integrated
unit combining a circuit breaker and a Power Meter.
Additional operating assistance functions can also be
displayed.
Status indications
When the circuit breaker is equipped with the Breaker Status Command Module
(BSCM) and NSX cord, the FDM128 display can also be used to view circuit breaker
status conditions:
bb O/F: ON/OFF
bb SDE: Fault-trip indication (overload, short-circuit, ground fault)
bb CE, CD, CT cradle management with I/O application module.
When the circuit breaker is equipped with the COM option (BCM ULP) (including its
kit for connection to XF and MX1 communication voltage releases), the FDM128
display can also be used to control (open/close) the circuit breaker.
Two operating mode are available:
bb local mode : open/close commands are enabled from FDM128 while disable from
communication network
bb remote mode : open/close commands are disabled from FDM128 while, enabled
from communication network.
PB111802-32_r.eps
PB111801-32_r.eps
Remote control
FDM128 display.
Main characteristics
PB111805-32_r.eps
Mounting
Connection
A-23
Switchboard-display functions
20.12.2011
12:00:05
S1-1 - Lighting/Level1
Quick view
Measures
Alarm history
Control
Maintenance
ESC
Product ID
Information
Reset all
Counter
Operation
xxx
Trip SDE
xxx
Close command
xxx
20.12.2011
12:00:05
S1-1 - Lighting/Level1
Quick view
Energy
Measures
Ep
Eq
Es
Alarm history
Control
11 318 kWh
257 kVArh
13 815 kVAh
Maintenance
ESC
3/3
Product identification.
DB414408.eps
DB414407.eps
DB414405.eps
6/7
Navigation
Screens
Main menu
Metering: meter.
Quick view
20.12.2011
S1-1 - Lighting/Level1
Quick view
Measures
Alarm history
Control
Maintenance
ESC
Services.
Alarms
12:00:05
Product ID
Information
Reset all
Metering
Maintenance.
Load profile
0 to 49%
50 to 79%
80 to 89%
Control
90 to 100%
2/3
A-24
Protection of distribution
systems
Micrologic control units
for Compact NS630b to 3200
DB128050.eps
External sensors
06133779A.eps
Four interchangeable plugs may be used to limit the long-time threshold setting
range for higher accuracy.
The time delay settings indicated on the plugs are for an overload of 6 Ir (for further
details, see the characteristics on page A-13 and page A-17).
As standard, control units are equipped with the 0.4 to 1 plug.
Setting ranges
Standard
Ir = In x 0.4
0.5
0.6
0.7
0.8
0.9
0.95 0.98 1
Low-setting option Ir = In x 0.4
0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8
High-setting option Ir = In x 0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1
Off plug
No long-time protection (Ir = In for Isd setting)
Important: long-time rating plugs must always be removed before carrying out insulation or
dielectric withstand tests.
PB101026_SE-32A.eps
The external power-supply module makes it possible to use the display even if the
circuit breaker is open or not supplied (for the exact conditions of use, see the
electrical diagrams part of this catalogue).
This module powers both the control unit (100 mA) and the M2C and M6C
programmable contacts (100 mA).
With the Micrologic A/E control unit, this module makes it possible to display currents
of less than 20 % of In.
With the Micrologic P and H, it can be used to display fault currents after tripping.
If the COM option is used, a second dedicated power supply shall be used.
We recommend to use the AD power supply due to its low stray primary secondary
capacitance. Good operation of the Micrologic trip unit in noisy environment is not
guaranteed with other power supplies.
Characteristics
bb Power supply:
vv 110/130, 200/240, 380/415 V AC, 50/60 Hz (+10 % -15 %)
vv 24/30, 48/60, 100/125 V DC (+20 % -20 %).
bb Output voltage: 24 V DC 5 %, 1 A.
bb Ripple < 1 %.
bb Dielectric withstand : 3.5 kV rms between input/output, for 1 minute.
bb Overvoltage category: as per IEC 60947-1 cat. 4.
A-25
Protection of distribution
systems
Micrologic control units
for Compact NS630b to 3200
PB100771-24.eps
Battery module
The battery module maintains display operation and communication with the
supervisor if the power supply to the Micrologic control unit is interrupted.
It is installed in series between the Micrologic control unit and the AD module.
Battery module.
Characteristics
bb Battery run-time: 4 hours (approximately).
bb Mounted on vertical backplate or symmetrical rail.
PB100781-32_SE.eps
These contacts are optional equipment for the Micrologic P control units.
They are described with the indication contacts for the circuit breakers.
Micrologic
Type P
Characteristics
Minimum load
Breaking capacity (A)
p.f.: 0.7
M6C.
M6C
V AC 240
380
V DC 24
48
125
250
100 mA/24 V
5
3
1.8
1.5
0.4
0.15
PB100775-32.eps
Spare parts
Lead-seal covers
A lead-seal cover controls access to the adjustment dials.
When the cover is closed:
bb it is impossible to modify settings using the keypad unless the settings lockout pin
on the cover is removed
bb the test connector remains accessible
bb the test button for the earth-fault and earth-leakage protection function remains
accessible.
Lead-seal cover.
A-26
Characteristics
bb Transparent cover for basic Micrologic and Micrologic A, E control units.
bb Non-transparent cover for Micrologic P control units.
Spare battery
A battery supplies power to the LEDs identifying the tripping causes. Battery service
life is approximately ten years.
A test button on the front of the control unit is used to check the battery condition.
The battery may be replaced on site when discharged.
PB100837-68.eps
Test equipment
Hand-held test kit
The hand-held mini test kit may be used to:
bb check operation of the control unit and the tripping and pole-opening system by
sending a signal simulating a short-circuit
bb supply power to the control units for settings via the keypad when the circuit
breaker is open (Micrologic P control units).
Power source: standard LR6-AA battery.
A-27
Products overview
Ethernet has become the universal link between switchboards, computers and
communication devices inside the building. The large amount of information which
can be transferred makes the connection of Enerlin'X digital system to hosted web
services of Schneider Electric a reality. More advantages are offered to integrators
thanks to configuration web pages available remotely or on the local Ethernet network.
F
B
4
E
Ethernet
Modbus SL
ULP
A-28
Function
Port
(to device)
E
F
Cial. Ref.
(to server)
Modbus
Energy Server
Master
with Ethernet
(1)
Gateway function
Ethernet cable 6
+ WiFi
EBX200
FDM128
Ethernet LCD
colour touch screen
Ethernet
LV434128
FDM121
ULP
TRV00121
Analog. Bin.
Input
Output
Com'X 200
Bin.
Input
IFE
interface +
gateway
Ethernet interface
Modbus
Ethernet
Master & ULP
LV434011
IFE
interface
Ethernet interface
for circuit breakers
ULP
Ethernet
LV434010
Acti9
Smartlink
Ethernet
Ethernet interface
with Input/Output
functions &
Gateway
Modbus
Master
Ethernet
14
A9XMEA08
Acti9
Smartlink
Modbus
Modbus interface
with Input/Output
functions
Modbus Slave
22
11
A9XMSB11
IFM
Modbus interface
for circuit breaker
ULP
Modbus Slave
TRV00210
I/O
Input/Output
application module
for circuit breaker
ULP
ULP
LV434063
G
H
(1) Gateway: transfers data from a network to another (ie.: Modbus to Ethernet).
(2) Interface: transfers data from an equipment to a network.(ie.: ULP to Modbus).
A-29
Communication
PB113438.eps
G
O
E
A
B
F
K
J
Q
H
I
P
L
L N
0.35 m
1.3 m
3m
LV434195
LV434196
LV434197
D Modbus cable
LV434010 or LV434011
L IFE: Ethernet interface
M External 24 V DC power supply module
0.3 m
0.6 m
1m
2m
3m
5m
TRV00803
TRV00806
TRV00810
TRV00820
TRV00830
TRV00850
Q NSX cord
0.35 m
1.3 m
3m
LV434200
LV434201
LV434202
E Ethernet cable
F FDM121: Front Display Module
TRV00121
LV434128
H Smartlink
A9XMSB11
I Acti9
J ULP line terminators
TRV00880
LV434063
A-30
TRV00210
Ethernet
Modbus
ULP
24 V DC
Overview of functions
PB104863.eps
Status indications
ON/OFF (O/F)
Spring charged CH
Ready to close
Fault-trip SDE
Connected / disconnected / test position
CE/CD/CT (I/O application module only)
Controls
MX1 open
XF close
Measurements
Instantaneous measurement information
Averaged measurement information
Maximeter / minimeter
Energy metering
Demand for current and power
Power quality
Switchdisconnectors
Circuit breaker
b
b
b
b
b
S
S
S
S
S
S
A
A
A
A
A
A
E
E
E
E
E
E
P
P
P
P
P
P
b
b
S
S
A
A
E
E
P
P
A
A
E
E
E
E
E
P
P
P
P
P
A
A
A
A
E
E
E
E
P
P
P
P
b
b
b
b
b
b
Operating assistance
Protection and alarm settings
Histories
Time stamped event tables
Maintenance indicators
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating
Modbus devices (Compact NS with Modbus COM, Power Meter PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.) are installed. All types of PLCs and
microcomputers may be connected to the bus.
Addresses
The Modbus communication parameters (address, baud rate, parity) are entered
using the keypad on the Micrologic A, E, P. For a switch-disconnector, it is necessary
to use the RSU (Remote Setting Utility) Micrologic utility.
Modbus addresses
@xx
@xx + 50
@xx + 200
@xx + 100
(1 to 47)
(51 to 97)
(201 to 247)
(101 to 147)
The manager addresses are automatically derived from the circuit breaker address
@xx entered via the Micrologic control unit (the default address is 47).
Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.), the baud rate (19200 is recommended),
the volume of data exchanged and the desired response time. The RS 485 physical
layer offers up to 32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device). A drawout device uses two connection points (communication modules on
the device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).
A-31
Communication
PB106674-20.eps
BCM ULP.
Or
bb IFE, the Ethernet interface for LV circuit breaker enables an intelligent modular
unit (IMU), for example a Compact NS circuit breaker to be connected to an Ethernet
network. Each circuit breaker has its own IFE and a corresponding IP address.
bb I/O (Input/Output) application module for LV breaker, the I/O application module is
delivered with withdrawable devices ordered with the COM option, for cradle
management. It must be installed on a DIN rail near the device. It must be connected
to the ULP system and to the position contacts (CD, CT, CE) that transmit the
position of the device in the cradle.
DB416829.eps
A-32
Communication architecture
Electrical operated
Drawout devices
Modbus
24VD
24VD
ETH2
1
I
Y.ZZ
XX.Y
IFE_
IFE
bus-SL
24VD
ETH2
2
ETH
ETH1
ETH
(factory
ETH1
ETH
Modbus
Ethernet
ETH2
2
ETH
ETH1
Modbus
Ethernet
DB417122.eps
DB417121.eps
Ethernet
DB417123.eps
Fixed device
2
ETH
set)
CT
00/A
10-1
1 LK/
ETH
CT
00/A
10-1
2 LK/
us
ETH
ule Stat
Mod
us
k Stat
Networ
Y.ZZ
XX.Y
IFE_
IFE
Mod
bus-SL
(factory
set)
CT
00/A
10-1
1 LK/
ETH
CT
00/A
10-1
2 LK/
us
ETH
ule Stat
Mod
us
k Stat
Networ
IFE
bus-SL
(factory
set)
CT
00/A
10-1
1 LK/
ETH
CT
00/A
10-1
2 LK/
us
ETH
ule Stat
Mod
us
k Stat
Networ
Mod
11
LV4340
11
LV4340
or
or
Y.ZZ
XX.Y
IFE_
Mod
11
LV4340
1
ETH
or
ULP system
I1
I2
I6
I5
I4
I3
I2
I1
I4
I1
I2
I4
I3
I6
I5
I4
I3
I6
I5
I2
I1
I3
I6
I5
+
C
24VD
+
C
24VD
A1
A1
O1
O2
O3
I1
O1
O2
O3
I1
I2
I3
I4
I5
I6
APP
I2
I3
I4
I5
I6
APP
dule
dule
IO Mo
IO Mo
O3
O2
O1
13
23
33
T1
A1
T2
34
24
14
O3
O2
O1
13
A
B
C
D
F
G
H
I
J
BCM ULP
OF, SDE ... microswitches
COM terminal block (E1 to E6)
MX1 and XF communicating voltage
releases
E CE, CD and CT contacts
33
T1
A1
T2
34
24
G
F
F
B
23
14
A-33
PB112059-55.eps
The IFE interface and IFE interface + gateway enable LV circuit breakers
as Masterpact NT/NW, Compact NSX or Powerpact to be connected to an Ethernet
network.
DB416830.eps
bb Dual 10/100 Mbps Ethernet port for simple daisy chain connection.
bb Device profile web service for discovery of the IFE interface, IFE interface +
gateway on the LAN.
bb ULP compliant for localization of the IFE interface in the switchboard.
bb Ethernet interface for Compact, Masterpact and Powerpact circuit breakers.
bb Gateway for Modbus-SL connected devices (IFE interface + gateway only).
bb Embedded set-up web pages.
bb Embedded monitoring web pages.
bb Embedded control web pages.
bb Built-in e-mail alarm notification.
Mounting
The IFE interface, IFE interface + gateway are DIN rail mounting devices. A stacking
accessory enables the user to connect several IFMs (ULP to Modbus interfaces) to
an IFE interface + gateway without additional wiring.
24 V DC power supply
IFE interface + gateway, ref.: LV434011
The IFE interface, IFE interface + gateway must always be supplied with 24 V DC.
The IFMs stacked to an IFE interface + gateway are supplied by the IFE interface +
gateway, thus it is not necessary to supply them separately. It is recommended to
use an UL listed and recognized limited voltage/limited current or a class 2 power
supply with a 24 V DC, 3 A maximum.
DB406743.eps
Characteristic
Structure
Device type
Turnaround time
Maximum length of cable
Type of bus connector
A-34
Type
Method
Modbus
Ethernet
Modbus
Ethernet
Modbus
Ethernet
Modbus
Ethernet
DB417466.eps
General characteristics
Environmental characteristics
Conforming to standards
Certification
Ambient temperature
Relative humidity
Level of pollution
Flame resistance
24VDC
ETH1
ETH2
Mechanical characteristics
Shock resistance
Resistance to sinusoidal vibrations
A
I
Electrical characteristics
K
ETH1
1000 m/s2
-5 Hz < f < 8.4 Hz
ETH2
Physical characteristics
IFE
ETH1 LK/10-100/ACT
ETH2 LK/10-100/ACT
Module Status
Modbus-SL
Network Status
LV434011
C
D
E
F
Dimensions
Mounting
Weight
Degree of protection of the installed IO
Connections
bb
bb
bb
Statistics
Device information
IMU information
Read device registers
Communication check
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
bb
A-35
Functions
and characteristics
PB103798-50.eps
Function
Once connected, the circuit breaker is considered as a slave by the Modbus master.
Its electrical values, alarm status, open/close signals car be monitored or controlled
by a Programmable Logic Controller or any other system.
Characteristics
ULP port
DB417545.eps
5
3
9
0
5
6
7
4
3
2
1
2
1
6
7
C
D
Test
E
F
odbus address
B M
switches.
G Mechanical lock.
A-36
F Test button.
H ULP RJ45 connectors.
I Stacking accessory
connection.
Technical characteristics
Dimensions
Maximum number of stacked IFM
Degree of protection Part projecting beyond
of the installed
the escutcheon
module
Other module parts
Connectors
Operating temperature
Power supply voltage
Consumption
Typical
Maximum
18 x 72 x 96 mm
12
IP4x
IP3x
IP2x
-25...+70 C
24 V DC -20 %/+10 % (19.2...26.4 V DC)
21 mA/24 V DC at 20 C
30 mA/19.2 V DC at 60 C
Certification
CE
UL
CSA
IEC/EN 60947-1
UL 508 - Industrial Control Equipment
No. 142-M1987 - Process Control
Equipment
bb CAN/CSA C22.2 No. 0-M91 General requirements - Canadian Electrical
Code Part
bb CAN/CSA C22.2 No. 14-05 Industrial Control Equipment
DB406714.eps
Staking IFM
Stacking accessories
Up to 12 stacked IFM
HRB49218-01_p49.eps
A-37
Ethernet
DB417259.eps
DB419880.eps
Ethernet
24 Vdc
24 Vdc
24VDC
24VDC
ETH2
ETH1
ETH2
ETH2
ETH1
ETH1
ETH2
ETH1
I1
I2
I3
I4
I6
I5
I4
I3
I2
I1
I6
I5
+
C
24VD
A1
O1
O2
O3
dule
IO Mo
A
O3
O2
O1
13
23
33
T1
A1
T2
34
24
14
C
J
I
H
D
E
F
E
G
A
B
C
D
E
A-38
A
B
C
D
E
F
G
H
I
J
K
DB416893.eps
B
C
D
E
F
Mounting
The module is mounted on a DIN rail. A number of modules may be clipped one next
to the other. For this, a stacking accessory is available for fast clip-connection of
both the Modbus link and the 24 V DC supply.
The Modbus interface module supplies 24 V DC to the corresponding Micrologic,
FDM121 display and BSCM module. Module consumption is 60 mA / 24 V DC.
DB112084.eps
A
B
C
D
E
F
G
DB419879.eps
Modbus
DB417257.eps
I1
I2
I4
I3
I6
I5
I4
I3
I2
I1
I6
I5
+
C
24VD
A1
O1
O2
O3
dul
IO Mo
O3
O2
O1
13
23
33
T1
A1
T2
34
24
14
B
C
J
I
H
A
B
C
D
E
B
C
D
E
breaker
ULP cable
Breaker ULP cord
Circuit breaker disconnected position
contact (CD)
Circuit breaker cradle
F
G
H
I
A-39
DB416829.eps
Description
The I/O (Input/Output) application module for LV breaker is part of an ULP system
with built-in functionalities and applications to enhance the application needs. The
ULP system architecture can be built without any restrictions using the wide range of
circuit breakers.
The I/O application module is compliant with the ULP system specifications.
Two I/O application module can be connected in the same ULP network.
The ranges of LV circuit breakers enhanced by the I/O application module are:
bb Masterpact NW
bb Masterpact NT
bb Compact NS1600b-3200
bb Compact NS630b-1600
bb Compact NSX100-630 A.
Pre-defined applications
User-defined applications
Mounting
DB416827.eps
4
3
2
The application rotary switch enables the selection of the pre-defined application.
It has 9 positions and each position is assigned to a pre-defined application.
The factory set position of the switch is pre-defined application 1.
7
8
DB416828.eps
DB416828.eps
A-40
The setting locking pad on the front panel of the I/O application module enables
the setting of the I/O application module by the customer engineering tool.
DB417467.eps
General characteristics
Environmental characteristics
I1
I2
I3
I4
I5
Conforming to standards
Certification
Ambient temperature
Relative humidity
Level of pollution
Flame resistance
I6
Mechanical characteristics
Shock resistance
Resistance to sinusoidal
vibrations
A
Electrical characteristics
I1
24VDC
I2
I3
I4
I5
Resistance to electromagnetic
discharge
Immunity to radiated fields
Immunity to surges
Consumption
I6
4
3
2
APP
7
8
I1
L
K
J
AI
I2
I3
O1
I4
O2
I5
O3
I6
O2
14
23
O3
24
33
34
T1
13
E
F
LV434063
O1
13
IO
14
23
A1
T2
24
33
34
T1
T2
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
10 V/m
Conforming to IEC/EN 61000-4-5
165 mA
Dimensions
Mounting
Weight
Degree of protection of the
installed I/O application module
Connections
Digital inputs
Digital input type
019.8 V DC, 0 mA
10 m (33 ft)
Note: for a length greater than 10 m (33 ft) and up to 300 m (1,000 ft), it is mandatory to use a
shielded twisted cable. The shield cable is connected to the I/O functional ground of the I/O
application module.
Physical characteristics
C
1000 m/s2
-5 Hz < f < 8.4 Hz
Digital outputs
Bistable relay
Rated load
5 A at 250 V AC
5A
5A
10 mA at 5 V DC
Contact resistance
30 m
10 m (33 ft)
Analog inputs
The I/O application module analog input can be connected to a Pt100 temperature sensor
Range
-30 to 200 C
-22 to 392 F
Accuracy
2 C from -30 to 20 C
1 C from 20 to 140 C
2 C from 140 to 200 C
Refresh interval
5s
5s
A-41
Capture1b.eps
Introduction
Electrical Asset Manager is a software application that helps the user to manage a
project as part of designing, testing, site commissioning, and maintenance of the
project life cycle.
It enables the user to prepare the settings of the devices offline (without connecting
to the device) and configure them when connected with the devices.
Also it provides lot of other value added features for the user to manage the project
such as, safe repository in cloud, attach artifacts to each device or at the project
level, organize devices in switchboard wise, manage a hierarchical structure of the
installation etc.
Capture3b.eps
References:
Electrical Asset Manager software package can be downloaded from our website
www.schneider-electric.com.
Features
Capture4b.eps
A-42
Capture5b.eps
Functions
Offline Mode
A project can be built in offline mode through 2 different ways:
bb through BOM file import
bb through Device Selection.
Online Mode
A project can be built in online mode through device discovery also other than the
methods possible through offline method.
Once the project is built, the following functions can be performed in addition to the
functions available in offline mode:
bb compare the device parameters with project parameters
bb load parameters from project to the device and vice versa
bb firmware downloads to the device
bb monitor the measurement, maintenance, device status and I/O status
bb control functions.
User Interface
Electrical Asset Manager software provides fast direct access to the project and the
devices in the project through different tabs.
bb Project: to provide the project information including customer details, project
references and to add project artifacts (documents related to the project).
bb Configuration: to build up the tree structure of the project architecture ; to have a
table view of the devices added in the project ; to set the parameters of the devices ;
to transfer the device settings ; to view the tripping curves; to attach device artifacts
and to download the latest firmware, to do the communication test for all the devices
and generate the test report.
bb Monitoring: this allows the user to monitor the real time values of different devices
through different sub tabs namely Monitoring, Logs and Control.
bb Reports: report tab allows you to generate and print a report of the project settings
from the report tab. The user details and project characteristics are automatically
filled with the details entered in the Project page.
Capture8b.eps
Capture7b.eps
Capture6b.eps
Additionally, the user can open an existing project and modify the settings offline.
The user can do the discrimination curve check and firmware compatibility check for
devices in the project.
A-43
Motor protection
Overview of solutions
160750
NS630b to 1600
PB104839_ME.eps
Compact
DB128055.eps
Breaking
capacity (kA rms)
380/415 V
N
H
L
50
70
150
page A-12
General circuit breaker characteristics
Compact NS630b to 1600 circuit breakers equipped with Micrologic control units are
the same as those for distribution systems.
page A-20
Accompanying control units
Micrologic electronic control units may be used on all Compact NS630b to 1600
circuit breakers.
Micrologic 2.0 A and 5.0 A electronic control units provide protection against
short-circuits and overloads. Micrologic 7.0 A provides the same protection
functions, plus earth-leakage protection.
DB128056.eps
A-44
0.37
1.5
1.1
2.5
5.5
12
18.5
40
50
37
80
100
160
200
110
220
160
320
250
500
800
560
1000
750
1350
Earth-leakage protection
Overview of solutions
630...1600
1600...3200
Compact NS1600b to 3200
PB104845_ME.eps
PB104831_ME_23.eps
PB104844_ME.eps
Separate toroids
051352_32_SE.eps
PB100435-16_SE.eps
Earth-leakage relay
A-45
Circuit
breakerdisconnector
Switchdisconnector
DB414486.eps
Standardised symbols
Main power
distribution board
for industrial
applications
Main power
distribution board
for commercial
applications
Final
distribution
enclosure
for
commercial
applications
LV devices
Acti 9
NG125
Easypact
Compact NS
Masterpact NT
Micrologic
Compact INS
Compact
NSX
Compact
NSX DC
Compact
NS
Masterpact NW
Masterpact
NW DC
Compact
INS/INV
Source-changeover
A-46
Compact INV
Fupact INF
Fupact
ISFT
Fupact
ISFL
PB106359.eps
PB104837.eps
Overview of solutions
A-47
PB104837.eps
Compact switch-disconnectors
Number of poles
Control
manual
Connections
electric
fixed
toggle
direct or extended rotary handle
front connection
rear connection
front connection
rear connection
Ith
Ui
Uimp
Ue
AC 50/60 Hz
le
AC 50/60 Hz
60 C
220/240 V
380/415 V
440/480 V (1)
Compact NS1600NA manual switch-disconnector.
500/525 V
PB106359.eps
660/690 V
Short-circuit making capacity
lcm
(kA peak)
lcw
(kA rms)
0.5 s
20 s
mechanical
electrical
AC
440 V
AC23A/In
MX shunt release
MN undervoltage release
Installation
Accessories
Dimensions (mm)
fixed
3P
fixed
3P
WxHxD
Weight (kg)
4P
4P
A-48
NS630bNA
NS800NA
NS1000NA
NS1250NA
NS1600NA
3, 4
b
b
3, 4
b
b
3, 4
b
b
3, 4
b
b
3, 4
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
630
800
1000
1250
1600
800
800
800
800
800
690
690
690
690
690
AC23A
AC23A
AC23A
AC23A
AC23A
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
52
52
52
52
52
25
25
25
25
25
10000
10000
10000
10000
10000
2000
2000
2000
2000
1000
b
b
b
b
b
b
b
b
b
327 x 210 x 147
327 x 280 x 147
14
18
b
A-49
Compact switch-disconnectors
Number of poles
Control
manual
toggle
direct or extended rotary handle
electric
Connections
fixed
front connection
front connection
rear connection
rear connection
PB104838.eps
Ith
Ui
Uimp
Ue
AC 50/60 Hz
le
AC 50/60 Hz
60 C
220/240 V
380/415 V
440/480 V (1)
500/525 V
660/690 V
Short-circuit making capacity
lcm
(kA peak)
lcw
(kA rms)
3s
440 V
AC23A/In
mechanical
electrical
AC
MX shunt release
MN undervoltage release
Installation
Accessories
escutcheons
Dimensions (mm)
fixed
3P
fixed
3P
WxHxD
Weight (kg)
4P
4P
A-50
NS1600bNA
NS2000NA
NS2500NA
NS3200NA
1600
2000
2500
3200
800
800
800
800
690
690
690
690
AC23A
AC23A
AC23A
AC23A
1600
2000
2500
3200
1600
2000
2500
3200
1600
2000
2500
3200
1600
2000
2500
3200
1600
2000
2500
3200
135
135
135
135
32
32
32
32
130
130
130
130
6000
6000
6000
6000
1000
1000
1000
1000
3, 4
3, 4
3, 4
3, 4
b
b
b
b
b
350 x 420 x 160
350 x 535 x 160
23
36
-
A-51
Source-changeover systems
Presentation
PB191613-50.eps
Some installations use two supply sources to counter the temporary loss of the main
supply.
A source-changeover system is required to safely switch between the two sources.
The replacement source can be a generator set or another network.
System
Applications
Small commercial buildings and small and medium industrial activities where the
need for continuity of service is significant but not a priority.
65587-117.eps
System
Applications
Large infrastructures, industry, critical buildings & process where the continuity of
service is a priority.
P109832-104.eps
In this case, no direct human intervention is required. The time required to switch
from the S1 source to S2 source is fixed.
System
Applications
Industry & Infrastructure where continuity of service requirements are meaningful but
not a priority.
A-52
PB113831.eps
The rotary handles are padlocked with the devices in the OFF position.
The mechanism inhibits the two devices being closed at the same time, but does
allow for both to be open (OFF) at the same time.
Combinations of "Normal" and "Replacement" devices
All Compact NS630b to 1600 circuit breakers and switch-disconnectors with rotary
handles can be interlocked.
Interlocking of a Compact NS630b with a Compact NS630b to 1600 is not possible.
Interlocking uses two identical keylocks with a single key. This solution enables
interlocking between two devices that are physically distant or that have significantly
different characteristics, for example between a low and a medium-voltage device,
or between Compact NS circuit breakers and switch-disconnectors.
A system of wall-mounted units with captive keys makes possible a large number
of combinations between many devices.
PB113832.eps
DB417641.eps
DB128465.eps
FFO
h
sup
FFO
h
sup
NO h
sup
FFO
Installation
This function requires:
bb an adaptation fixture on the right side of each circuit breaker or switch-disconnector
bb a set of connecting rods with no-slip adjustments.
The adaptation fixtures, connecting rods and circuit breakers or switchdisconnectors are supplied separately, ready for assembly by the customer.
The maximum vertical distance between the fixing planes is 900 mm.
NO h
sup
FFO
O
degr
ahcs
id
degr
ahcs
id
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
The interlocked devices may be fixed or drawout, three-pole or four-pole, and have
different ratings and sizes.
O
FFO
hsup
FFO
hsup
NO h
sup
FFO
FFO
degr
ahcs
id
Interlocking with
connecting rods.
NO h
sup
O
degr
ahcs
id
Installation
This function requires:
bb an adaptation fixture on the right side of each device
bb a set of cables with no-slip adjustments.
The maximum distance between the fixing planes (vertical or horizontal) is 2000mm.
Source S1
NS630b to NS1600
Ratings 250... 1600 A
Source S2
NS630b to
NS1600
NT06 to NT16
NW08 to
NW40
NW40b to
NW63
bb
It is not possible to combine Compact NS630b to 1600 and Masterpact (NT or NW)
devices.
A-53
Electrical interlocking
IVE unit
PG134060_L50.eps
PB104831_ME.eps
IVE unit.
For Compact NS630b to NS1600, each circuit breaker must be equipped with:
bb a motor mechanism
bb an available OF contact
bb a CE connected-position contact (carriage switch) on withdrawable circuit breakers
bb an SDE contact.
DB110903.eps
QN
0
1
0
A-54
QR
0
0
1
Diagram no.
DB417641.eps
DB128465.eps
Remote-operated systems
O
sup
FFO
h
sup
NO h
sup
FFO
NO h
sup
FFO
degr
ahcs
id
PB100857_16_SE.eps
degr
ahcs
id
FFO
hsup
FFO
hsup
NO h
sup
FFO
NO h
FFO
degr
ahcs
id
sup
O
degr
ahcs
id
Control plate.
Interlocking by rods.
Interlocking by cables.
DB403810R.eps
FFO
h
In this case, changeovers between the "Normal" and "Replacement" sources under
predefined conditions are initiated by a Schneider Electric controller.
Controller.
A-55
Source-changeover systems
Associated controllers
Controller
BA
4-position switch
Automatic operation
DB403809.eps
Indications
Other functions
DB403810.eps
Communication option
Power supply
Operating thresholds
Undervoltage
Phase failure
Voltage presence
A-56
b
b
Options
UA controller
Test
BA controller.
UA
b
110 V
220 to 240 V 50/60 Hz
380 to 415 V 50/60 Hz
440 V 60 Hz
b
b
b
b
b
b
b
b
b
b
b
Controller
BA
UA
b
b
b
b
b
b
b
b
Front
Side
Connectors
Front
IP40
IP30
IP20
IK07
b
b
b
AC
AC12
8
8
8
8
5
4
-
AC13
7
7
6
6
-
AC14
5
5
4
4
-
AC15
6
5
4
3
-
DC
DC12
8
2
0.6
0.4
-
DC13
2
-
A-57
DB417254.eps
Sealable terminal
shield
Phase
barriers
Interphase barriers
Spreader
Vertical connection
adapter
Connection kit
for connectors
Rear connectors
Auxiliary contact
Spreader
Micr ologic
push
push
5.0 E
Voltage release
ON
OFF
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp
disch
Ue
(V)
40
220/2
90
480/6
100 %
arged
O OFF
Ics =
40 %
100%
Icu
(kA)
100
85
Icu
IEC
UTE VDE
BS
menu
alar m
long
tim e
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
shor
t tim
Isd3 4 5
2.5
2
1.5
012
x Ir
6
8
10
tr
8 12
16
2
20
1
24
.5 at 6 Ir
(s) 4
tsd .4 .4 .3
(s)
.3
.2
.1
on
I t
Ii
.2
.1
instantan
6
4
3
2
eous
8 10
12
15
off
x In
delay
setting
53
Communications
module
Phase
barriers
IFE
Connection kit
for connectors
I/O
IFM
Sealable terminal
shield
FDM121
FDM128
Phase
barriers
Escutcheon
I on
I on
ed
tripp
r es e
tripp
ed
r es e
0 OF
0 OF
tripped
reset
Extended rotary
handle
A-58
Direct rotary
handle
DB417425.eps
Interphase barriers
Terminal extension for
cables with lugs
IFE
Vertical connection
adapter
Spreader
Rear connectors
I/O
IFM
FDM121
FDM128
Spreader
Auxiliary contact
Micr ologic
5.0 E
H
NS 1200Uimp 12kV
Ui 1000V
8kV
Uimp
Ue
(V)
40
220/2
90
480/6
100 %
Ics =
40 %
IEC
100%
Icu
(kA)
100
85
Voltage release
Icu
UTE VDE
BS
menu
alar m
long
tim e
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
shor
t tim
Isd3 4 5
2.5
2
1.5
x Ir
6
8
10
tr
8 12
16
2
20
1
24
.5 at 6 Ir
(s) 4
tsd .4 .4 .3
(s)
.3
.2
.1
on
I t
Ii
.2
.1
instantan
6
4
3
2
eous
8 10
12
15
off
x In
delay
setting
Manual operation
Communications
module
Micr ologic
5.0 E
push
push
ON
H
NS 1200Uimp 12kV
OFF
Ui 1000V
8kV
Uimp
100 %
disch
40 %
OFF
arged
Ue
(V)
40
220/2
90
480/6
Ics =
IEC
100%
Icu
(kA)
100
85
I on
I on
Icu
UTE VDE
BS
menu
alar m
long
tim e
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
shor
t tim
Isd3 4 5
2.5
2
1.5
x Ir
tr
8 12
16
2
20
1
24
.5 at 6 Ir
tsd .4 .4 .3
(s)
.3
.2
.1
on
I t
ed
tripp
r es e
ed
eous
Ii
.2
.1
tripp
(s) 4
6
8
10
instantan
6
4
3
2
8 10
12
15
off
r es e
x In
delay
setting
012
53
0 OF
0 OF
tripped
reset
Electrical operation
Escutcheon
Extended rotary
handle
Direct rotary
handle
Transparent cover
A-59
Installation
PB104831_ME_39_r.eps
PB106360r-50_r.eps
Fixed configuration
DB128064.eps
DB128063.eps
DB128034.eps
Mounting on a backplate.
Mounting on rails.
Withdrawable configuration
059782N_I_50_SE_ME.eps
DB128065.eps
DB128067.eps
A-60
DB128068.eps
Mounting on a backplate.
DB128066.eps
Device on rails.
DB128070.eps
Connected Test
Disconnected Removed
3
4
5
6
7
8
9
10
1 mismatch protection
2 door interlock
3 racking interlock
4 keylock locking
5 padlock locking
6 position indicator
7 chassis front plate (accessible with cubicle door closed)
8 crank entry
9 reset button
10 crank storage
A-61
Connection by:
bars
DB128074.eps
DB128080.eps
DB128072.eps
DB128079.eps
DB128078.eps
DB128073.eps
DB128075.eps
DB128077.eps
DB128072.eps
DB128076.eps
Fixed device
Withdrawable device
DB128076.eps
DB128073.eps
Connection by:
bars
DB128074.eps
DB128076.eps
DB128072.eps
DB128083.eps
Front connections
Connection by:
bars
DB128074.eps
DB128080.eps
DB128072.eps
DB128084.eps
Rear connections
A-62
DB128075.eps
DB128072.eps
DB128082.eps
DB128081.eps
Connections accessories
Type of accessories
Fixed:
Front connection
DB128085.eps
Vertical-connection
adapters
Withdrawable:
Front connection
Rear connection
N, H, L
N, L, LB
N, H
N, H, L
N, H, L, LB
N, H, L, LB
N, H, L, LB
N, H, L, LB
N, H, L, LB
N, H, L, LB
N, H, L
N, H, L, LB
N, H, L, LB
N, H, L, LB
N, H, L
N, H, L, LB
(standard)
N, H, L, LB
(standard)
N, H, L
DB128087.eps
DB128086.eps
(1)
Set of bare-cable connectors
and terminal shields for
ratings y 1250 A
DB128088.eps
(1)
Interphase barriers
DB128089.eps
(2)
Spreaders
(3)
DB128091.eps
DB128092.eps
DB128090.eps
(1)
Connection shield
(4)
(1) Spreaders, vertical connection adapters and cable lugs adapters are not compatible with voltages u 500 V.
(2) Mandatory for voltages u 500 V unless using the bare-cable connector + terminal shield kit.
(3) Mandatory for fixed devices with L and LB performance levels, whatever the voltage.
(4) Mandatory for fixed front-connection versions with vertical connection adapters oriented towards the front.
A-63
DB128094.eps
DB128099.eps
DB128098.eps
DB128097.eps
Bars
Vertical-connection adapters.
DB128100.eps
DB128093.eps
DB128104.eps
DB128103.eps
Bare cables
DB128095.eps
4-cable connectors.
DB403911.eps
DB128107.eps
DB403910.eps
DB128105.eps
DB128096.eps
DB128102.eps
DB128101.eps
Spreaders.
A-64
Spreaders.
DB128105.eps
DB128112.eps
DB128111.eps
DB128110.eps
DB128100.eps
DB403912.eps
Bars
DB128096.eps
DB128113.eps
DB128114.eps
DB128109.eps
A-65
DB128097.eps
Vertical-connection adapters.
DB128100.eps
DB128116.eps
DB128115.eps
DB128120.eps
DB128094.eps
DB128096.eps
DB128105.eps
DB128117.eps
Spreaders.
A-66
DB128119.eps
DB128118.eps
DB128123.eps
Spreaders.
DB128105.eps
DB128124.eps
DB128122.eps
DB128100.eps
DB128094.eps
Bars
DB128096.eps
DB128126.eps
DB128125.eps
DB128121.eps
A-67
PB104833_ME.eps
DB128127.eps
Connection shield
Interphase barriers
Connection shield.
DB128128.eps
DB128130.eps
A-68
DB128131.eps
Safety shutters.
DB417647.eps
CAF1
CAF2
CAO1
CAO2
Fixed devices
Connections are made directly to the auxiliaries once the front has been removed.
Wires exit the circuit breaker through a knock-out in the top.
OF1
OF2
OF3
SD
DB128133.eps
MN or MX
SDE
COM
DB417648.eps
Withdrawable devices
Auxiliary circuits are connected to terminal blocks located in the top part of the
chassis.
The auxiliary terminal block is made up of a fixed and moving part. The two parts are
in contact when the device is in the test and connected positions.
SDE
OF3
OF2
OF1
MN or MX
COM
DB417649.eps
DB417650.eps
CT1
CE3
CE2
CE1
CD2
CD1
Withdrawable device.
A-69
054549-18.eps
Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
bb OF (ON/OFF) - indicates the position of the main circuit breaker contacts
bb SD (trip indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault.
vv operation of a voltage release
vv operation of the "push to trip" button
vv disconnection when the device is ON.
Returns to de-energised state when the circuit breaker is reset.
bb SDE (fault indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
bb CAF / CAO (early-make or early-break function) - indicates the position of the
rotary handle. Used in particular for advanced opening of safety trip devices (early
break) or to energise a control device prior to circuit breaker closing (early make).
Installation
bb OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker
bb CAF / CAO function - the contact fits into the rotary-handle unit (direct or
extended).
Electrical characteristics of the OF/SD/SDE/CAF/CAO auxiliary contacts
Contacts
Standard
6
100 mA at 24 V
AC12 AC15 DC12
6
6
6
6
6
2.5
6
5
0.6
6
4
0.3
6
2
6
1.5
6
0.1
-
Low level
5
1 mA at 4 V
DC14 AC12 AC15
1
5
3
0.2
5
3
0.05 5
2.5
5
2
0.03 5
5
1.5
5
1
-
DC12
5
2.5
0.6
0.3
-
056456.eps
DC14
1
0.2
0.05
0.03
-
A-70
Standard
8
100 mA at 24 V
AC12 AC15 DC12
8
6
2.5
8
6
2.5
8
5
0.8
8
4
0.3
8
3
6
0.1
-
Low level
5
2 mA at 15 V
DC14 AC12 AC15
1
5
3
0.2
5
3
0.05 5
2.5
5
2
0.03 5
5
1.5
-
DC12
5
2.5
0.8
0.3
-
DC14
1
0.2
0.05
0.03
-
PB100781-32_SE.eps
These contacts, used with the Micrologic P control units, may be programmed via
the control unit keypad or via a supervisory station with the COM communication
option. They require an external power supply module.
They indicate:
bb the type of fault
bb instantaneous or delayed threshold overruns.
They may be programmed:
bb with instantaneous return to the initial state
bb without return to the initial state
bb with return to the initial state following a delay.
Characteristics
M6C
Minimum load
Breaking capacity (A)
p.f.: 0.7
V AC
240
380
24
48
125
250
V DC
100 mA/24 V
5
3
1.8
1.5
0.4
0.15
DB101170.eps
11
4 12 10 18 16
14
24 22
20
PB104828_ME.eps
Rotary handles
PB104829_ME.eps
A-71
This function opens the circuit breaker via an electrical order. It is made up of:
bb a shunt release (2nd MX)
bb or an undervoltage release MN
bb or a delayed undervoltage release MN + delay unit.
These releases (2nd MX or MN) cannot be operated by the communication bus.
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency OFF button to obtain instantaneous opening of the circuit breaker.
Opening
order
DB128139.eps
DB128138.eps
DB128137.eps
Delayed
opening
order
10
12
Delay
unit
C2
D2
PB104831_ME.eps
D2
MN
MN
MX
C1
Instantaneous
opening
order
D1
D1
When energised, the 2nd MX voltage release instantaneously opens the circuit
breaker. A continuous supply of power to the 2nd MX locks the circuit breaker in the
OFF position. The MX release instantaneously opens the circuit breaker when
energised, the minimum duration of the pulse operating order must be 200 ms.
The MX release locks the circuit breaker in OFF position if the order is maintained
(except for MX "communicating" releases).
Characteristics
Power supply
V AC 50/60 Hz
V DC
Operating threshold
Permanent locking function
Consumption (VA or W)
Circuit breaker response
time at Un
The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on
the release, it is impossible to close the circuit breaker, either manually or
electrically. Any attempt to close the circuit breaker has no effect on the main
contacts. Circuit breaker closing is enabled again when the supply voltage of the
release returns to 85 % of its rated value.
Characteristics
Power supply
Fixed Compact NS1600.
V AC 50/60 Hz
V DC
Operating
opening
threshold
closing
Consumption (VA or W)
MN consumption
with delay unit (VA or W)
Circuit breaker response
time at Un
MN delay units
056421.eps
To eliminate circuit breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply
V AC 50-60 Hz /DC
Operating threshold
MX voltage release.
A-72
Consumption of delay
unit alone (VA or W)
Circuit breaker response
time at Un
non-adjustable
adjustable
opening
closing
pick-up: 200 (200 ms)
100/130 - 200/250
48/60 - 100/130 - 200/250 - 380/480
0.35 to 0.7 Un
0.85 Un
hold: 4.5
non-adjustable
adjustable
0.25 s
0.5 s - 1 s - 1.5 s - 3 s
The motor mechanism module is used to remotely open and close the circuit
breaker. It is made up of a spring-charging motor equipped with an opening release
and a closing release.
An electrical operation function is generally combined with:
bb device ON/OFF indication OF
bb "fault-trip" indication SDE.
Motor mechanism module
Power supply
V AC 50/60 Hz
V DC
PB104831_ME.eps
Operating threshold
Consumption (VA or W)
Motor overcurrent
Charging time
Operating frequency
Opening
order
Opening
order
Closing
order
A4
A2
Motor
mechanism
module
Fault
A2
B4
Motor
mechanism
module
A1
COM
OF
Closing
order
A4
B4
Supervisor
SDE
82
Closed
Open
84
12
14
OF1
SDE
A1
DB417155.eps
DB128140.eps
81
11
200 ms
min.
for MX
A-73
Function
Means
accessories
lock in
b OFF position
padlock
removable device
b OFF or ON position
padlock
fixed device
lock in
b OFF position
padlock
b OFF or ON position
keylock
PB104828_ME_r.eps
Required
padlock
padlock
keylock
locking
device + keylock
keylock
Locking in ON position does not prevent the device from tripping in the event of a
fault or remote tripping order.
DB128142.eps
4
O
push
push
ON
OFF
disc
1 reset of mechanical
trip indicator
2 OFF pushbutton
3 OFF position locking
4 ON pushbutton
5 springs charged
indication
6 pushbutton locking
7 contact position indication
8 operation counter
ed
harg
O OFF
6
7
012
53
PB100810A-32.eps
PB100811A-32.eps
PB104365A-32.eps
PB100812A-32.eps
Access to pushbuttons
protected by transparent
cover.
The transparent cover blocks access to the pushbuttons used to open and close the
device.
It is possible to independently lock the opening OFF button and the closing ON
button.
The pushbuttons may be locked using either:
bb padlocks (not supplied), 5 to 8 mm
bb lead seal
bb two screws.
A-74
The circuit breaker is locked in the OFF position by physically maintaining the
opening pushbutton pressed down:
bb using padlocks in standard (one to three padlocks, not supplied)
bb using a keylock (supplied).
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
bb one keylock
bb one keylock mounted on the device + one identical keylock supplied separately for
interlocking with another device.
A locking kit (without lock) is available for installation of a keylock (Ronis, Profalux,
Kirk or Castell).
DB128071.eps
Chassis locking
3
4
5
Disconnected position
locking by padlocks.
mismatch protection
door interlock
racking interlock
keylock locking
padlock locking
position indicator
chassis front plate
(accessible with cubicle
door closed)
8 crank entry
9 reset button
10 crank storage
10
PB104367A34.eps
PB104366A32.eps
6
7
8
9
1
2
3
4
5
6
7
Disconnected position
locking by keylocks.
Mounted on the chassis and accessible with the door closed, these devices lock the
circuit breaker in the disconnected position in two manners:
bb using padlocks (standard), up to three padlocks (not supplied)
bb using keylocks (optional), one or two different keylocks are available.
Profalux and Ronis keylocks are available in different options:
bb one keylock
bb one keylock mounted on the device + one identical keylock supplied separately,
using the same key, for interlocking with another device
bb one (or two) keylocks mounted on the device + one (or two) identical keylocks
supplied separately, for interlocking with another device.
A locking kit (without locks) is available for installation of one or two keylocks (Ronis,
Profalux, Kirk or Castell).
PB104352A32.eps
The connected, disconnected and test positions are shown by an indicator and are
mechanically indexed.
The racking crank blocks when the exact position is obtained.
A release button is used to free it.
As standard, the circuit breaker can be locked only in "disconnected position". On
request, the locking system may be modified to lock the circuit breaker in any of the
three positions: "connected", "disconnected" or "test".
Door interlock.
Mounted on the right or left-hand side of the chassis, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the
breaker is put in the connected position with the door open, the door may be closed
without having to disconnect the circuit breaker.
This device prevents insertion of the crank when the cubicle door is open (device
cannot be connected).
PB100815-32R_SE.eps
Racking interlock.
Mismatch protection ensures that a circuit breaker is installed only in a chassis with
compatible characteristics. It is made up of two parts (one on the chassis and one on
the circuit breaker) offering twenty different combinations that the user may select.
Mismatch protection.
A-75
PB104740-32.eps
Other accessories
Auxiliary terminal shield (CB)
Auxiliary terminal shield.
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.
PB104382A32.eps
The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible only with electrically operated devices.
Escutcheon (CDP)
DB128144.eps
Operation counter.
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40. It is available in fixed and withdrawable versions.
Optional equipment mounted on the escutcheon, the cover is hinged and secured by
a screw. It increases the degree of protection to IP54 and the degree of protection
against mechanical impacts to IK10. It may be used for withdrawable devices only.
Used with the escutcheon, this option closes off the door cutout of a cubicle not yet
equipped with a device. It may be used with the escutcheon for both fixed and
withdrawable devices.
DB128145.eps
Escutcheon.
DB128146.eps
Transparent cover.
Blanking plate.
A-76
DB417253.eps
Vertical-connection adapters
Interphase barriers
Auxiliary contact
Micr olog
ic 5.0
OF F
OF F
100 %
40 %
menu
Voltage release
alar m
long
tim e
.8 .9
.7
.9 5
.6
.9 8
.5
1
.4 x In
Ir
shor
t tim
Is d3 4 5
2. 5
2
1. 5
6
8
10
x Ir
tr
8 12
16
2
20
1
24
.5 at 6 Ir
(s ) 4
neous
Ii
ts d . 4 . 4 . 3
(s )
.3
.2
.1
on
I t
.2
.1
instanta
4
3
6
2
8 10
12
15
off
x In
delay
setting
ic 5.0
Micr olog
OF F
OF F
100 %
Circuit breaker
NS1600b / 2500A
40 %
menu
alar m
long
tim e
.8 .9
.7
.9 5
.6
.9 8
.5
1
.4 x In
Ir
shor
e
t tim
Is d3 4 5
2. 5
2
1. 5
6
8
10
x Ir
tr
8 12
16
2
20
1
24
.5 at 6 Ir
(s ) 4
ts d . 4
(s )
.3
.2
.1
on
I t
.2
.1
Communications
module
neous
Ii
.4 .3
instanta
4
3
6
2
8 10
12
15
off
x In
delay
setting
Circuit breaker
NS3200
Vertical-connection adapters
IFE
Interphase barriers
I/O
IFM
FDM121
FDM128
Escutcheon
A-77
Installation
Fixed circuit breakers
DB128151.eps
OFF
OFF
Mounting on rails.
Connection
Front connection
DB128154.eps
NS3200
DB128153.eps
DB128069.eps
NS1600 to 2500
OFF
OFF
OFF
OFF
DB128155.eps
Bars
Bars may be directly connected to the terminals of Compact NS1600b to 3200 circuit
breakers.
DB128156.eps
NS1600b to 2500
OFF
OFF
DB128159.eps
DB128158.eps
DB128157.eps
OFF
OFF
OFF
OFF
A-78
054549-18.eps
Indication contacts
Contacts installed in the device
Changeover contacts are used to remote circuit breaker status information and can
thus be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
Functions
bb OF (ON/OFF) - indicates the position of the main circuit breaker contacts
bb SD (trip indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault
vv operation of a voltage release
vv operation of the "push to trip" button
bb Returns to de-energised state when the circuit breaker is reset.
SDE (fault indication) - indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
vv an earth-leakage fault.
Returns to de-energised state when the circuit breaker is reset.
Installation
bb OF, SD and SDE functions - a single type of contact provides all these different
indication functions, depending on the position where it is inserted in the device.
The contacts clip into slots behind the front cover of the circuit breaker.
Electrical characteristics of the OF/SD/SDE auxiliary contacts
Contacts
Standard
6
100 mA at 24 V
AC12 AC15 DC12
6
6
6
6
6
2.5
6
5
0.6
6
4
0.3
6
2
6
1.5
6
0.1
-
Low level
5
1 mA at 4 V
DC14 AC12 AC15
1
5
3
0.2
5
3
0.05 5
2.5
5
2
0.03 5
5
1.5
5
1
-
DC12
5
2.5
0.6
0.3
-
DC14
1
0.2
0.05
0.03
-
A-79
Remote tripping
056421.eps
This function opens the circuit breaker via an electrical order. It is made up of:
bb a shunt release 2nd MX
bb or an undervoltage release MN
bb or a delayed undervoltage release MNR = MN + delay unit.
These releases (2nd MX or MN) cannot be operated by the communication bus.
The delay unit, installed outside the circuit breaker, may be disabled by an
emergency OFF button to obtain instantaneous opening of the circuit breaker.
Opening
order
DB128139.eps
DB128138.eps
DB128137.eps
Delayed
opening
order
10
12
Delay
unit
MX voltage release
D2
C2
Instantaneous
opening
order
MN
MN
MX
D1
D1
C1
D2
When energised, the 2nd MX voltage release instantaneously opens the circuit
breaker. A continuous supply of power to the 2nd MX locks the circuit breaker in the
OFF position.
Characteristics
Power supply
V AC 50/60 Hz
V DC
Operating threshold
Permanent locking function
Consumption (VA or W)
Circuit breaker response
time at Un
The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on
the release, it is impossible to close the circuit breaker, either manually or electrically.
Any attempt to close the circuit breaker has no effect on the main contacts. Circuit
breaker closing is enabled again when the supply voltage of the release returns to 85
% of its rated value.
Characteristics
Power supply
V AC 50/60 Hz
V DC
Operating
opening
threshold
closing
Consumption (VA or W)
MN consumption
with delay unit (VA or W)
Circuit breaker response
time at Un
90 ms5
MN delay units
To eliminate circuit breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply
V AC 50-60 Hz /DC
Operating threshold
Consumption of delay
unit alone (VA or W)
Circuit breaker response
time at Un
A-80
non-adjustable
adjustable
opening
closing
pick-up: 200 (200 ms)
100/130 - 200/250
48/60 - 100/130 - 200/250 - 380/480
0.35 to 0.7 Un
0.85 Un
hold: 4.5
non-adjustable
adjustable
0.25 s
0.5 s - 0.9 s - 1.5 s - 3 s
PB104836_ME.eps
Device locking
Function
Means
padlock
lock in OFF or ON
padlock
Required
accessories
removable device
fixed device
position
PB104835_ME.eps
Interphase barriers
Escutcheon CDP
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40.
DB128128.eps
DB128161.eps
Interphase barriers.
Escutcheon.
A-81
TOOLS
Ecodial
Ecodial software is dedicated to LV electrical installation
calculation in accordance with the IEC60364
international standard or national standards.
This 4th generation, "Ecodial Advance Calculation 4",
offers a new ergonomic and new features:
pp operating mode that allows easy calculation in case
of installation with different type of sources
(parallel transformers, back-up generators)
pp discrimination analysis associating curves checking
and discrimination tables
pp direct access to protection settings including residual
current protections
pp easy selection of alternate solutions or manual
selection of a product.
Installation recommendations
Presentation 2
Functions and characteristics
A-1
Operating conditions
B-2
Installation in switchboards
Power supply and weights
B-3
B-4
Installation example
B-5
B-6
Control wiring
B-7
Temperature derating
Compact NS devices equipped with electronic trip units
B-8
B-9
B-9
C-1
D-1
E-1
F-1
B-1
DB128162.eps
Installation
recommendations
Operating conditions
Altitude derating
(m)
2000
2000
3000
4000
5000
800
710
635
560
7.1
6.4
5.6
560
690
635
0.99 x In 0.96 x In 0.94 x In
Vibrations
Electromagnetic disturbances
DB128164.eps
B-2
Installation in switchboards
DB128165.eps
Power supply
Compact NS circuit breakers can be supplied from either the top or the bottom
without any reduction in performance. This capability facilitates connection when
installed in a switchboard.
Weights
NS630b to 1600 manual operation
3P
14
14
4P
18
18
NS630b to 1600 electrical operation
3P
14
16
4P
18
21
NS1600b to 3200
3P
24
4P
36
The table above presents the weights (in kg) of the circuit breakers and the main accesories,
which must be summed to obtain the total weight of complete configurations.
B-3
Installation in switchboards
Installation
recommendations
Safety clearances
and minimum distances
General rules
146.5
DB417671.eps
DB128166.eps
A (*)
Insulated parts
NS630b to 1600
A
0
B
0
NS1600b to 3200
A
50
B
0
A (*)
Metal parts
Live parts
120
10
180
60
170
10
230
60
DB128168.eps
B
C
40
180
F
Insulated parts
A
B
C
B-4
0
10
0
Datum
Metal parts
0
10
0
Live parts
30
60
30
Installation example
DB404158.eps
Painted sheetmetal
Direct connection by
bare cables, devices
with terminal shields.
Connection by cables
with lugs, devices with
terminal shields.
Connection by insulated
bars, devices with
terminal shields.
A
250
300
B-5
Door interlock
for Compact NS630b to 1600
DB418148.eps
Installation
recommendations
X
61
11.5
2
Dimensions (mm)
Type
NS630b to 1600 (3P)
NS630b to 1600 (4P)
(1)
135
205
Door locked
Door
F
5
23
B-6
(1)
(2)
168
168
(2)
Control wiring
12 V
24 V
2.5 mm2 1.5 mm2 2.5 mm2
MN
U source 100 %
58
U source 85 %
16
MX-XF
U source 100 %
21
12
115
U source 85 %
10
6
75
Note: the indicated length is that of each of the two wires.
1.5 mm2
35
10
70
44
48 V
2.5 mm2
280
75
550
350
1.5 mm2
165
45
330
210
24 V DC power-supply module
External 24 V DC power-supply module for Micrologic (F1-, F2+)
bb It is recommended to use the AD power supply due to its low stray primarysecondary capacitance. Good operation of the Micrologic Trip Unit in noisy
environment is not guaranteed with other power supplies.
bb The dedicated AD power supplies shall be used only for the Micrologic trip units. If
the COM option is used, a second dedicated power supply shall be used.
bb M2C and M6C modules can be supplied by Micrologic external AD power supply.
bb The consumption of a Micrologic Trip Unit is approximately 100mA.
bb The consumption of M2C and M6C modules is approximately 100mA.
bb A number of 5 devices (Micrologic control units with M2C or M6C) can be
connected to the same AD power supply. Add other AD power supply for more than 5
devices.
bb For Micrologics control units alone, a number of 10 devices can be connected to
the same AD power supply. Add other AD power supply for more than 10 Micrologics.
bb If the installation is shared between several panels, one AD power supply shall be
added for each panel.
bb AD power supply dedicated to Micrologics trip units shall not be connected to
earth. (F1-, F2+).
External 24 V DC power supply for Communication bus
bb A dedicated 24 V DC power supply shall be used for the communication devices.
bb Do not connect the positive terminal (E1) to earth.
bb The negative terminal (E2) can be connected to earth.
bb A number of communication modules (BCM, IFE, IFM, I/O, FDM) can be
connected to the same 24 V DC power supply. Refer bellow the devices
consumption table to avoid exceeding the maximum current delivered by the
24 V DC power supply.
ULP module consumption
The table below lists the ULP module consumption.
Module
Typical Consumption
Maximum Consumption
(24 V DC at 20 C / 68 F) (19.2 V DC at 60 C / 140 F)
40 mA
65 mA
30 mA
55 mA
9 mA
15 mA
15 mA
19 mA
30 mA
21 mA
30 mA
120 mA
3 A (with gateway)
165 mA
420 mA
Maintenance module
0 mA (the maintenance
0 mA (the maintenance
module has its own power module has its own power
supply)
supply)
Installation recommendation
bb The 24 V DC wires (output of the 24 V DC power supply) shall be twist together.
bb The 24 V DC wires (output of the 24 V DC power supply) must cross all power
cables perpendicularly.
bb The technical characteristics of the external 24 V DC power-supply module for
Micrologic control units are indicated on page A-28.
Note: wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be
connected to earth at both ends.
B-7
Temperature derating
Installation
recommendations
The table below indicates the maximum rated-current value for each type of connection, depending on the ambient temperature.
For mixed connections, use the same derating values as for horizontal connections.
Version
Connection
temp. Ti (2)
Fixed device
Front or horizontal rear
40
45
50
55
60
65
70
Vertical rear
40
45
50
55
60
65
70
Version
Connection
temp. Ti (2)
Withdrawable device
Front or horizontal rear
40
45
50
55
60
65
70
Vertical rear
40
45
50
55
60
65
70
60
65
70
Vertical rear
40
45
50
55
60
65
70
NS630b N/L
NS800 N/L
NS1000 N/L
NS1250 N
NS1600 N
NS630b N/L
NS800 N/L
NS1000 N/L
NS1250 N
NS1600 N
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1560
630
800
1000
1250
1520
630
800
1000
1250
1510
630
800
1000
1250
1480
630
800
1000
1250
1470
630
800
1000
1250
1430
630
800
1000
1240
1420
630
800
1000
1170
1330
630
800
1000
1090
1360
630
800
920
1000
1160
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1600
630
800
1000
1250
1560
630
800
1000
1250
1600
630
800
1000
1250
1510
630
800
1000
1250
1510
630
800
1000
1250
1420
630
800
1000
1180
1460
630
800
990
1090
1250
Fixed device
Front or horizontal rear
40
45
50
55
NS1600b N
1600
1600
1600
1600
1500
1450
1400
1600
1600
1600
1600
1600
1550
1500
NS2000 N
2000
2000
2000
2000
1900
1800
1700
2000
2000
2000
2000
2000
1900
1800
NS2500 N
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
NS3200 N
3200
3200
3200
3180
3080
2970
2860
(1) For a circuit breaker mounted in horizontal position, the derating to be applied is equivalent to that of a front or horizontal rear connected circuit breaker.
(2) Ti: temperature around the circuit breaker and its connections.
B-8
Fixed device
N
R/pole
P/pole
0.026
10
0.026
15
0.026
22
0.026
44
0.026
74
Withdrawable device
N
R/pole
P/pole
0.038
19
0.038
30
0.038
50
0.036
84
0.036
154
L
R/pole
0.039
0.039
0.039
P/pole
15
20
34
L
R/pole
0.072
0.072
0.072
P/pole
34
40
77
LB
R/pole
0.056
0.056
P/pole
15
20
LB
R/pole
0.086
0.086
P/pole
34
40
Fixed device
N
R/pole
P/pole
NS1600b
0.019
84
NS2000
0.013
84
NS2500
0.008
100
NS3200
0.008
227
B-9
TOOLS
schneider-electric.com
Presentation 2
Functions and characteristics
A-1
Installation recommendations
B-1
C-2
Mounting
C-3
Front-panel cutouts
C-4
Rotary handle
C-5
C-6
Rotary handle
C-7
C-9
C-13
C-14
C-15
C-16
C-19
C-20
C-22
C-23
C-24
C-25
C-26
C-28
D-1
E-1
F-1
C-1
Dimensions
and connection
Dimensions
Manual control
DB128174.eps
DB128173.eps
163.5
254
327
200
508
100
99.5 (3P)
169.5 (4P)
107.5
205
99.5
Y
105 (3P)
175 (4P)
DB128176.eps
DB128175.eps
105
X
117
123
107.5
210
234
113
92.5
123
35
70
140.5
146.5
205
14
Z
Electrical control
DB128178.eps
105 (3P)
175 (4P)
105
188
94
123
105
X
210
234
200
117
100
123
107.5
35
175.5
70
182
Z
C-2
99.5 (3P)
169.5 (4P)
99.5
Y
F : Datum.
Note: Dimensions for front and rear
connection on electrically operated
devices are identical to those for
manually operated devices.
Mounting
Front connection
On rails
DB128179.eps
4 6.5
DB128180.eps
On backplate
4 6.5
200
200
100
100
99.5 (3P)
169.5 (4P)
99.5 (3P)
169.5 (4P)
Rear connection
On rails
Y
4 5.5
4 R30
DB414751.eps
On backplate
DB414750.eps
99.5
99.5
4 6.5 (3P)
6 6.5 (4P)
60
107
75
75
200
100
60
99.5 (3P)
169.5 (4P)
200 (3P)
270 (4P)
107
234
117
35
99.5
70
(4P)
70
Note: Mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 3-pole device
Z is the back plane of the device.
C-3
Dimensions
and connection
Front-panel cutouts
150
(2)
Door cutout
A
DB128185.eps
124 mini
(1) (2)
(A)
(B)
(C)
DB128184.eps
DB128183.eps
Toggle control
194 mini
216 (1)
266 (2)
194 (1)
244 (2)
140.5
146.5
97 (1)
122 (2)
100.5 (1)
DB128186.eps
F : Datum.
(1) Without escutcheon.
(2) With escutcheon.
194 mini
119 (1)
144 (2)
35.5 (1)
60.5 (2)
71 (1)
121 (2)
(A)
95.5 (1)
108 (2)
Door cutout
A
DB128184.eps
DB128187.eps
Electrical control
150 mini
(1) (2)
194 mini
216 (1)
266 (2)
108 (1)
133 (2)
107.5
194 (1)
244 (2)
175.5
182
F
Z
F : Datum.
(1) Without escutcheon.
(2) With escutcheon.
C-4
97 (1)
122 (2)
90.5 (1)
181 (1)
194 mini
201(1)
108 (1)
133 (2)
107.5
Rotary handle
Direct rotary handle
(A)
124 mini
(1) (2)
(B)
141.1 mini
172.5 mini
(1)
(D)
DB128190.eps
DB421315.eps
Dimensions
Y
60
R80
X
195
24
60
25
107.5
140.5
146.6
175.5
229.5
Z
194 mini
216 (1)
266 (2)
D
Y
DB128193.eps
B
Y
DB128192.eps
DB128184.eps
Door cutout
A
194 mini
201 (1)
Y
194 mini
201 (1)
100.5 (1)
100.5 (1)
108 (1)
133 (2)
194 (1)
244 (2)
90.5 (1)
90.5 (1)
97 (1)
122 (2)
130 (1)
181 (1)
DB128196.eps
Door cutout
DB128194.eps
Dimensions
60
R100
X
24
60
25
212.5
231.5 mini
605.5 maxi
F
Z
: Datum.
C-5
Dimensions
and connection
Electrical control
210
mini
127.5 (3P)
197.5 (4P)
DB128199.eps
DB128198.eps
DB128197.eps
Manual control
210
mini
160.5
188
94
46 (*)
70 (*)
199
45.5
69
60 mini
123
60 mini
90 (3P)
160 (4P)
90
Y
Mounting
DB128202.eps
DB128200.eps
X
25
24
100
216
231
F
Cutouts
DB128204.eps
DB128203.eps
Door cutout
230 mini
259 (1)
303 (2)
234
117
161 (1)
183 (2)
109 (1)
130.8 (2)
259 (1)
307 (2)
102.5 (3P)
172.5 (4P)
102.5
: Datum.
C-6
Rotary handle
Direct rotary handle
210
mini
DB128206.eps
DB128205.eps
Dimensions
136 (*)
60
R80
X
93
24
60
60 mini
25
DB128207.eps
Door cutout
230 mini
259 (1)
303 (2)
X
109 (1)
130.8 (2)
161 (1)
259 (1) 183 (2)
307 (2)
DB128210.eps
DB128209.eps
Door cutout
DB128208.eps
Dimensions
60
E47966A
Y
R200
X
24
60
207 mini
447 maxi
17
25
F
Note: X and Y are the symmetry planes for a 3-pole device.
C-7
Dimensions
and connection
Dimensions
(A)
(B)
DB128212.eps
DB128211.eps
Dimensions
132 mini
(C)
165
330
18.5
38.5
132
162.5
168.5
222.5
368
B
Y
DB128214.eps
DB128213.eps
216 (1)
267 (2)
108 (1)
133.5 (2)
X
346 (1)
397 (2)
100.5
173 (1)
198.5 (2)
166
332
Mounting on rails
DB128216.eps
DB128215.eps
4 12
119
95.9
73
146
F : Datum.
(1) Without escutcheon.
(2) With escutcheon.
C-8
201
150
75
195 (3P)
310 (4P)
195
DB128218.eps
DB128217.eps
8
S : 0.6 mm
S : 2.5 mm
3.5
Only one wire per terminal.
2 4
DB128220.eps
DB128219.eps
88
90
105
59
88
105
DB128222.eps
DB128221.eps
24V
BAT
Input C
24VD
t
OutpuC
24VD
2 6
60
73
H4
H3
60
H1
H2
112
75
Modbus
++
Com.
58
ss
CE
CD
CT
Addre
.
sync
Rseau
shield
B B
A A
B B
A A
Breaker
Network
Fault
Disjoncteur
us
modb
CCM
90
45
54
C-9
Dimensions
and connection
External modules
I1
24VDC
I2
I3
I4
I5
I1
I2
I3
I4
I5
I6
I6
A1
O1
O2
O3
IO
45
84.8
92
115
LV434063
O1
13
DB416700.eps
DB416699.eps
O2
14
23
O3
24
33
34
T1
A1
T2
63.6
72
71
DB416702.eps
DB416701.eps
45
85
92
105
66
18
73
ETH1
DB416698.eps
DB416697.eps
IFE
ETH1 LK/10-100/ACT
45
ETH2 LK/10-100/ACT
Module Status
Modbus-SL
Network Status
84.8
92
105
LV434011
63.6
72
71
DB417077.eps
DB417076.eps
ComX 200
3
90
144
45
63
69
C-10
85
106
4 14
35 76
177
208
8 14
44
44
174
127
44
295
DB128230.eps
Installation
400/1600 (NS630b to NS1600)
C-11
Dimensions
and connection
External modules
DB128232.eps
DB128233.eps
4 9
197
115
216
280
233
71
362
DB128234.eps
DB128235.eps
381
8 9
281
242
146
160
263
72
456
470
552
572
Busbars
Busbars path
I y 1600 A
I y 3200 A
Window (mm)
280 x 115
470 x 160
Weight (kg)
14
18
M1 M2 M3
2 bars 50 x 10
DB128239.eps
DB128238.eps
4 bars 100 x 5
M1 M2 M3
2 bars 100 x 5
4 bars 125 x 5
C-12
DB114992.eps
DB114991.eps
Dimensions
96
96
Y
Mounting
DB118545.eps
DB416963.eps
DB114993.eps
Through panel
+ 0.8
92 0
+ 0.8
10.6
20.7
92 0
23
DB115122.eps
DB115121.eps
DB115270.eps
DB114996.eps
On panel
2 22.5
16.5
99.3
X
19
15
37
20
32
2 22.5
13
+
- 0.5
+0.3
-
+
- 1.5
33
17
99.3
Y
Connector (optional).
C-13
Dimensions
and connection
DB416736.eps
DB416703.eps
Dimensions
129
163
Y
Mounting
DB416738.eps
1.5...6
DB416737.eps
DB416704.eps
On panel
100
X
30.6
17.5
100
100
+0
DB416740.eps
DB416739.eps
39
22,5 -0,30
100
X
100
+0
30 -0,20
Y
C-14
Escutcheon
(A)
(C)
DB128242.eps
A
DB128241.eps
DB128240.eps
Y
X
275
154
27
27
27
131
27
253
DB128244.eps
DB128243.eps
X 313
27
27
13
27
317
DB128246.eps
DB128245.eps
275 X
137.5
202.5
27
405
C-15
Dimensions
and connection
Bars
Horizontal rear connection
70
DB128041.eps
DB128247.eps
DB128248.eps
43.5
15
70
70
67.5
67.5
123
Y
44
DB128249.eps
E47904A
123
25
9.5 12.5
15
60
12.5
31
2 11
F
Z
70
DB128051.eps
43.5
DB128251.eps
DB128250.eps
70
15
View A
97
X
97
DB128252.eps
60
12.5
9.5
12.5
31
44
F
Z
25
2 11
View A detail.
163.5
70
DB128255.eps
DB128254.eps
DB128253.eps
Front connection
70
70
30
129
N
163.5
16.5
F
DB128256.eps
Top terminal
129
44
25
9.5
15
15
2 screws M10
Z
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-16
View A
Bottom terminal
2 screws M10
15
25
44
9.5
15
DB128259.eps
DB128257.eps
DB128258.eps
70
25
25
196
181
15
View A
X
DB128260.eps
95
181
196
95
70
95
70
70
12.5
12.5
31.5
15
View A
F
Z
15
123
95
DB128263.eps
98
DB128262.eps
DB128261.eps
70
70
82.5
X
15
52.5
Y
83
DB128264.eps
123
95
95
70
95
70
70
12.5
12.5
DB128265.eps
DB128266.eps
Spreader detail
Middle left or middle right
spreader for 4P
View A detail.
: Datum.
C-17
Dimensions
and connection
Bars
70
DB128152.eps
DB128269.eps
DB128270.eps
70
15
View A
200
200
DB128271.eps
430
10
62.5
Z
: Datum.
Note: (1) two mounting possibilities for vertical-connection adapters (pitch 21 mm).
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-18
View A detail.
70
DB128274.eps
15
DB128273.eps
DB128272.eps
70
View A
250
200
15
DB128275.eps
530
200
250
View A detail.
15
10
150
DB128276.eps
DB128277.eps
20.5 : 240 mm
23 : 300 mm
DB128278.eps
Lugs
89.5
10
11.5
25
31
70
DB128281.eps
DB128279.eps
DB128280.eps
199
398
413
206.5
DB128282.eps
199
70
206.5
N
70
16.5
35
61
F
Z
: Datum.
C-19
Dimensions
and connection
Bars
49
70
DB128285.eps
DB128283.eps
DB128284.eps
70
70
67.5
228
15
267.5
44
DB128249.eps
67.5
114
25
9.5 12.5
60
12.5
2 11
70
DB128289.eps
DB128288.eps
DB128287.eps
70
70
15
View A
97
X
N
DB128252.eps
97
267.5
F
60
12.5
9.5
12.5
44
2 11
25
View A detail.
DB128291.eps
DB128292.eps
15
12.5
DB128293.eps
Front connection
70
70
70
View A
171
N
X
336
235
DB128294.eps
140
Top terminal
12.5
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-20
Bottom terminal
95
DB128297.eps
DB128295.eps
DB128296.eps
70
70
View A
238
223
95
DB128298.eps
192
207
70
95
95
70
70
12.5
View A
12.5
250
F
N
DB128265.eps
Spreader detail
Middle left or middle right
spreader for 4P
View A detail.
F
: Datum.
C-21
Dimensions
and connection
50
70
DB128305.eps
DB128303.eps
DB128304.eps
15
70
70
View A
15
71
292
N
21
583
21
15
DB128275.eps
171
140
261
71
View A detail.
50
15
193.5
20.5 : 240 mm
23 : 300 mm
DB128277.eps
DB128276.eps
Lugs
DB128278.eps
89.5
10
25
F : Datum.
Note: X and Y are the symmetry planes for a 3-pole device.
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-22
11.5
31
115
DB128312.eps
DB128310.eps
DB128311.eps
115
20
View A
DB128313.eps
150
165
OFF
OFF
115
F
Z
View A detail.
DB418147.eps
DB418145.eps
DB128315.eps
115
80
115
80
80
230
142.5
X
View A
142.5
OFF
OFF
DB128317.eps
230
25
40
Z
View A detail.
115
DB128320.eps
DB418146.eps
DB128319.eps
115
230
142.5
142.5
OFF
OFF
230
View A
DB128317.eps
25
40
Z
View A detail.
F : Datum.
Note: Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
C-23
Dimensions
and connection
12.5
DB128325.eps
9.5 12.5
DB128326.eps
44
25
DB128327.eps
DB128329.eps
DB128322.eps
DB128324.eps
Rear connection
60
2 11
DB128336.eps
DB128335.eps
DB128334.eps
DB128333.eps
DB128331.eps
DB128332.eps
60
12.5
9.5
12.5
44
25
Front connection
Top terminal
25
2 M10 screws
C-24
Bottom terminal
9.5
15
15
2 M10 screws
25
44
9.5
15
15
DB128342.eps
DB128341.eps
44
DB128325.eps
DB128322.eps
DB128322.eps
2 11
DB128325.eps
DB128324.eps
DB128346.eps
DB128322.eps
DB128350.eps
DB128349.eps
DB128348.eps
DB128351.eps
DB128347.eps
DB128350.eps
DB128351.eps
DB128349.eps
C-25
Dimensions
and connection
Compact circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors (flexible or rigid bars, cables).
In the event of a short-circuit, thermal and electrodynamic stresses will be exerted on
the conductors. They must therefore be correctly sized and maintained in place
using supports.
Electrical connection points on all types of devices (switch-disconnectors,
contactors, circuit breakers, etc.) should not be used for mechanical support.
Any partition between upstream and downstream connections of the device must be
made of non-magnetic material.
The table below indicates the maximum distance between ties depending on the
prospective short-circuit current.
The maximum distance between ties attached to the switchboard frame is
400 mm.
DB128355.eps
Type of
tie
"Panduit" ties
Width: 4.5 mm
Maximum load: 22 kg
Colour: white
27
35
DB128356.eps
DB128357.eps
Maximum distance
200
100
50
between ties (mm)
Short-circuit
10
15
20
current (kA rms)
2
Note: For cables u 50 mm , use 9 mm-wide ties.
"Sarel" ties
Width: 9 mm
Maximum load: 90 kg
Colour: black
45
50 (double
ties)
100
Connection of bars
DB128358.eps
Bars must be adjusted to ensure correct positioning on the terminals before bolting (B).
Bars must rest on a support firmly attached to the switchboard frame, such that the
circuit breaker terminals do not bear any weight (C).
Electrodynamic forces
The first spacer between bars must be positioned within a maximum distance (see
table below) of the connection point to the circuit breaker. This distance is calculated
to resist the electrodynamic stresses exerted between the bars of each phase during
a short-circuit.
C-26
DB128360.eps
DB128359.eps
150
150
Connections
The quality of bar connections depends, among other things, on the tightening
torques used for the nuts and bolts. Over-tightening may have the same
consequences as under-tightening.
The correct tightening torques for the connection of bars to the circuit breaker
terminals are indicated in the table below.
The values below are for copper bars (Cu ETP-NFA51-100) and steel nuts and bolts
(class 8.8).
The same values apply to AGS-T52 quality aluminium bars
(French standard NFA 02-104 and American National Standard H-35-1).
DB128364.eps
DB128363.eps
DB128362.eps
11
50
Bar drilling
DB128367.eps
DB128366.eps
DB128365.eps
Examples
Insulation distance
DB128368.eps
1
2
3
4
5
6
Dimensions (mm)
Utilisation voltage
X minimum
Ui y 600 V
8 mm
Ui y 1000 V
14 mm
Bar bending
Bars must be bent according to the table below. A tighter bend may cause cracks.
DB128369.eps
DB128361.eps
r
e
Dimensions (mm)
e
5
10
Radius r
Minimum
5
15
Recommended
7.5
18 to 20
C-27
Dimensions
and connection
Sizing of bars
DB128370.eps
Compact
NS630b
NS630b
NS800
NS1000
NS1250
Maximum Ti: 40 C
Ti: 50 C
service
Number of bars
Number of bars
current
5 mm thick
10 mm thick 5 mm thick
400
630
800
1000
1250
10 mm thick
Ti: 60 C
Number of bars
5 mm thick
2b.30 x 5
1b.30 x 10
2b.30 x 5
1b.30 x 10
2b.30 x 5
2b.40 x 5
1b.40 x 10
2b.40 x 5
1b.40 x 10
2b.40 x 5
2b.50 x 5
1b.50 x 10
2b.50 x 5
1b.50 x 10
2b.50 x 5
3b.50 x 5
1b.63 x 10
3b.50 x 5
2b.50 x 10
3b.63 x 5
3b.50 x 5
2b.40 x 10
3b.50 x 5
2b.50 x 10
3b.63 x 5
2b.80 x 5
2b.40 x 10
2b.80 x 5
NS1600/1600b 1400
2b.80 x 5
2b.40 x 10
2b.80 x 5
2b.50 x 10
3b.80 x 5
NS1600/1600b 1600
3b.80 x 5
2b.63 x 10
3b.80 x 5
2b.63 x 10
3b.80 x 5
NS2000
1800
3b.80 x 5
2b.63 x 10
3b.80 x 5
2b.63 x 10
3b.100 x 5
NS2000
2000
3b.100 x 5
2b.80 x 10
3b.100 x 5
2b.80 x 10
3b.100 x 5
NS2500
2200
3b.100 x 5
2b.80 x 10
3b.100 x 5
2b.80 x 10
4b.80 x 5
NS2500
2500
4b.100 x 5
2b.100 x 10
4b.100 x 5
2b.100 x 10
4b.100 x 5
NS3200
2800
4b.100 x 5
3b.80 x 10
4b.100 x 5
3b.80 x 10
5b.100 x 5
NS3200
3000
5b.100 x 5
3b.80 x 10
6b.100 x 5
3b.100 x 10
8b.100 x 5
NS3200
3200
6b.100 x 5
3b.100 x 10
8b.100 x 5
3b.100 x 10
Note: With Compact NS630b to NS1600, it is recommended to use 50 mm wideness bars (see "Recommended busbars drilling").
C-28
10 mm thick
1b.30 x 10
1b.40 x 10
1b.63 x 10
2b.50 x 10
2b.50 x 10
2b.63 x 10
3b.50 x 10
2b.80 x 10
3b.63 x 10
2b.100 x 10
3b.80 x 10
3b.100 x 10
4b.80 x 10
4b.100 x 10
DB128371.eps
Compact
NS630b
NS630b
NS800
NS1000
NS1250
NS1600
NS1600
Maximum Ti: 40 C
Ti: 50 C
service
Number of bars
Number of bars
current
5 mm thick
10 mm thick 5 mm thick
400
630
800
1000
1250
1400
1600
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
2b.63 x 5
2b.80 x 5
3b.63 x 5
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
1b.63 x 10
1b.80 x 10
2b.50 x 10
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.50 x 5
3b.50 x 5
2b.80 x 5
3b.63 x 5
10 mm thick
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.50 x 10
2b.40 x 10
2b.50 x 10
2b.50 x 10
Ti: 60 C
Number of bars
5 mm thick
2b.30 x 5
2b.40 x 5
2b.50 x 5
2b.63 x 5
3b.50 x 5
3b.63 x 5
3b.80 x 5
10 mm thick
1b.30 x 10
1b.40 x 10
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.50 x 10
2b.63 x 10
C-29
TOOLS
Ecodial
Ecodial software is dedicated to LV electrical installation
calculation in accordance with the IEC60364
international standard or national standards.
This 4th generation, "Ecodial Advance Calculation 4",
offers a new ergonomic and new features:
pp operating mode that allows easy calculation in case
of installation with different type of sources
(parallel transformers, back-up generators)
pp discrimination analysis associating curves checking
and discrimination tables
pp direct access to protection settings including residual
current protections
pp easy selection of alternate solutions or manual
selection of a product.
Electrical diagrams
Presentation 2
Functions and characteristics
A-1
Installation recommendations
B-1
Dimensions and connection
C-1
D-2
D-4
D-6
D-8
D-10
D-11
Connection to the I/O application module and communication interface module D-12
D-13
E-1
F-1
D-1
Electrical diagrams
MN
MX
Micrologic
BPF
B4
BPO
A2
AT
D2
Q3
Q2
Q1
Z5
Z4
Z3
Z2
Z1
VN
M6C
A4
DB128373.eps
Z5
Z4
Z3
Z1
Downstream cb
Z5
Z4
Z3
Z2
Upstream cb
Z1
DB128378.eps
Power
N L1 L2 L3
Remote operation
C2
Control unit
Z2
Power
Motor-mechanism
module
A1
C1
D1
F2+
T4/F1
T3
T2
T1/M3
M2
M1
or
24 V DC
A
b
E
b
P
b
Control unit
E1-E6 communication
b
b
Remote operation
MN :
undervoltage release
or
MX :
shunt release
Motor-mechanism module (*)
A4 :
electrical opening order
A2 :
electrical closing order
B4, A1 : power supply for control devices and gear motor
(*) Spring-charging motor 440/480 V AC
(380 V motor + additional resistor)
DB128380.eps
Basic
b
CN1 a - 440/480 V
9 11
R
A4
A2
B4
Motor-mechanism
module
E : energy
A : digital ammeter.
P : A + power meter + additional protection.
A1
CN2 a - 440/480 V
D-2
Electrical diagrams
White
Yellow
Brown
Black
Red
Blue
E6 E5 E4 E3 E2 E1
MN/MX
F1 F2
M1M2M3
Z1 Z2 Z3 Z4 Z5
T1 T2 T3 T4
512
514
522
524
Open
534
532
544
Closed
542
Fault
94
92
84
82
14
12
Fault
DB128376.eps
Closed
24
22
34
Open
32
OF1
11 12 14
D1/C1
OF2
D2/C2
21 22 24
OF3
531
SD :
trip indication contact
(manual operation)
541
511
81
521
532
542
512
522
534
544
514
524
82
84
SDE
White
Yellow
Brown
Black
Red
Blue
Indication contacts
SDE :
fault-trip indication contact
(short-circuit, overload, earth fault)
91 92 94
511
521
91
31 32 34
SD
CAO2 CAO1
CAF1
531
CAF2
SD
541
SDE
81
OF1
11
OF2
21
OF3
31
DB128375.eps
Indication contacts
E6 E5 E4 E3 E2 E1
Z1 Z2 Z3 Z4 Z5
MN/MX
F1 F2
M1M2M3
T1 T2 T3 T4
D1/C1
D2/C2
31
21
11
82
32
22
12
84
34
24
14
B4 A4 A2 A1
D-3
Electrical diagrams
Q
MN
Micrologic
B4
BPF
C2
D2
Q3
Q2
Q1
Z5
Z4
Z3
Z2
Z1
VN
BPO
A2
AT
M6C
A4
Z5
Z4
Z3
Z1
Downstream cb
Z5
Z4
Z3
Z2
Upstream cb
Z1
DB128378.eps
Power
N L1 L2 L3
Remote operation
Z2
Power
Motor-mechanism
module
MX
A1
C1
D1
F2+
T4/F1
T3
T2
T1/M3
M2
M1
or
24 V DC
Control unit
Com
UC1
UC2
E5 E6
Z5 M1 M2 M3 F2+
Q3
544
E3 E4
Z3 Z4
T3 T4
VN
Q2
542
E1 E2
Z1 Z2
T1 T2
F1
Q1
541
Basic A
b
b
E
b
P
b
Control unit
Com: E1-E6 communication
UC1:
b
b
b
b
b
UC2:
UC3:
M6C:
UC3
Remote operation
M6C / CAF2
MN / MX
/
D2
C2
D1
A : digital ammeter.
P : A + power meter + additional protection.
MT1
A4
A2
C1
A1
Remote operation
MN
: undervoltage release
or
MX
: shunt release
MT2
B4
Terminal-block marking
CN1 a - 440/480 V
9 11
R
A4
A2
B4
Motor-mechanism
module
A1
CN2 a - 440/480 V
D-4
Electrical diagrams
SD
CAO2
CAO1 OF3
914
Test
CT1
OF1
Carriage switches
911
311
CE1
321
CE2
331
811
821
511
OF2
CE3
CD2
CD1
CE3
CE2
CE1
CT1
Q3
544
534
84
94
524
514
34
24
14
824
814
334
324
314
914
Q2
542
532
82
92
522
512
32
22
12
822
812
332
322
312
912
Q1
541
531
81
91
521
511
31
21
11
821
811
331
321
311
911
Indication contacts
OF3 / OF2 / OF1 : indication contacts
SDE
: fault-trip indication contact
(short-circuit, overload, earth fault)
912
DB128382.eps
DB128188.eps
314
312
324
322
334
CD1
332
824
812
CD2
Connected
814
822
512
514
522
524
534
Disconnected
CAO2 CAO1
521
541
Open
531
532
544
542
94
92
84
Indication contacts
Closed
CAF2 CAF1
SD
81
11
SDE
Fault
91
OF1
82
14
12
24
22
OF2
Fault
DB128150.eps
Carriage switches
Closed
21
OF3
34
32
Open
31
DB128381.eps
Indication contacts
Carriage switches
CD2 : disconnected
CD1 position
CE3 : connected
CE2 position
CE1
CT1 : test
position
SD
: trip indication contact
(manual operation)
CAF2/CAF1 * : early-make contact
(rotary handle)
CAO2 / CAO1 : early-break contact
(rotary handle)
Legend
Connected
(only one wire per connection point).
D-5
Electrical diagrams
MN
C2
AT
D2
Z5
Z4
Z3
Z5
Z2
Z4
Z1
Z5
Downstream cb
Z2
Z4
Z1
Z3
Z2
Upstream cb
Z1
DB128390.eps
Power
N L1 L2 L3
Remote operation
DB128391.eps
Control unit
Z3
Power
MX
Micrologic
C1
D1
F2+
T4/F1
T3
T2
T1/M3
M2
M1
or
24 V DC
(basic)
b
A E
b b
Control unit
E1-E6 communication
D-6
Remote operation
MN
: undervoltage release
or
MX
: shunt release
Electrical diagrams
Fault
94
92
84
82
14
12
24
Fault
DB128393.eps
Terminal-block marking
Closed
22
34
Open
32
E6 E5 E4 E3 E2 E1
F1 F2
M1M2M3
T1 T2 T3 T4
Z1 Z2 Z3 Z4 Z5
MN/MX
OF1
D1/C1
D2/C2
OF2
OF3
SD
SDE
11 12 14
21 22 24
31 32 34
91 92 94
91
SD
81
OF1
11
OF2
21
OF3
31
DB128392.eps
Indication contacts
81
82
84
SDE
Indication contacts
OF3 / OF2 / OF1 : ON / OFF indication contacts
SDE
: fault-trip indication contact
(short-circuit, overload, earth fault)
SD
D-7
Electrical diagrams
DB414726.eps
Shield Drain
Z5
Z4
Z3
Z2
Z1
DB128387.eps
H1
H2
D-8
PE
1
3
10 11
MiDGF module
13
14
F2+
T3
T2
T1/M3
6
T4/F1
12 5
X1
X2
M2
M1
Micrologic 6
9
8
Electrical diagrams
Z5
Z4
Z2
Z1
Z3
N L1 L2 L3
DB128388.eps
Q
I
F2+
T4/F1
T3
T2
T1/M3
M1
M2
Micrologic 7
M1
M2
M3
Neutral protection
bb three pole circuit breaker:
vv neutral protection is impossible with Micrologic A,E
vv with Micrologic P, an external neutral transformer is
necessary; the connection diagram is the same as for
residual earth-fault protection.
bb four pole circuit breaker:
vv Compact equipped with Micrologic A,E,P
vv the current transformer for external neutral is not
necessary.
DB128389.eps
tsd = 0.3
Fault 1
B
tsd = 0.2
Fault 2
Downstream
circuit break
D-9
Electrical diagrams
Communication
DB418136.eps
24 V DC
Modbus
A
24 V DC
24 V DC
I
+24V
0V
Eth2
Eth1
+24V
0V
+24V
0V
Eth2
Eth1
Eth2
Eth1
I
I
I1
I2
I3
I4
I6
I5
I4
I3
I2
I1
I6
I5
+
DC
24V
A1
O1
O2
O3
dule
IO Mo
I3
I2
I1
I4
I6
I5
O3
I6
I1
O2
I6
I5
I3
I2
I1
O1
13
I2
23
33
T1
A1
T2
34
24
14
+
DC
24V
I1
I2
I6
I5
I3
+
DC
24V
T1
O2
O1
13
T1
O2
O1
13
23
23
A1
T2
24
14
A1
T2
24
14
A FDM121 (TRV00121)
Masterpact NT/NW
J FDM128 (LV434128)
C IFE (LV434010)
G Compact NS630b-3200
D IFM (TRV00210)
H Compact NSX
(1) Modbus termination is mandatory, see ULP system user guide TRV99101.
D-10
(1)
N Modbus Termination
(VW3A8306DRC)
ULP cable
NSX cord
Ethernet
Modbus
Electrical diagrams
DB416707.eps
FDM
Color
Red
E1
24 V
Black
E2
0V
White
E5
Blue
E6
Breaker ULP
cord
Black
Red
White Blue
E1 E2 E3 E4 E5 E6
B / Rx+ D1
A / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
24 V
Ethernet
Modbus-SL
ULP cable
24VDC
ETH1
ETH2
IFE
IFM
ULP Termination
ULP Termination
OR
D-11
- +
Withdrawable
Compact NS630b to 3200
Electrical diagrams
DB417695.eps
FDM
24VDC
Color
Red
E1
24 V
Black
E2
0V
White
E5
Blue
E6
I/O
application
module
ULP cable
Breaker ULP
cord
Red Black
White Blue
E1 E2 E3 E4 E5 E6
B / Rx+ D1
A / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
24 V
Modbus-SL
Ethernet
24 V DC
24 V DC
24VDC
ETH1
IFE
IFM
ULP Termination
ULP Termination
OR
D-12
ETH2
Electrical diagrams
DB417452.eps
Connection of the 24 V DC
external power supply AD module
bb The 24 V DC external power-supply (AD module) for the Micrologic control unit
(F1- F2+) is not required for basic protections LSIG.
bb The 24 V DC external power-supply (AD module) for the programmable contact
M2C/M6C is required.
bb The 24 V DC external power-supply for the BCM ULP communication module
(E1-E2) is required.The same 24 V DC external power supply can be used for the
communication devices (IFE, IFM, I/O, FDM).
bb If the 24 V DC external power supply (AD module) is used to supply Micrologic
control unit, this power supply shall be used only for supplying Micrologic control
units and M2C/M6C.
bb The dedicated AD power supplies shall be used only for the Micrologic trip units. If
the COM option is used, a second dedicated 24 V DC external power supply shall be
used.
bb With Micrologic A/E, it is recommended to connect 24 V DC external power-supply
(AD module) to the Micrologic control unit (F1- F2+) in order to keep available
the display and the energy metering, even if Current < 20 % In.
Note: in case of using the 24 V DC external power supply (AD module), maximum cable length
between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
The BAT battery module, mounted in series upstream of the AD module, ensures
an uninterrupted supply of power if the AD module power supply fails.
The internal voltage taps are connected to the botton side of the circuit breaker.
With Micrologic P/H, external voltage taps are possible using the PTE option.
With this option, the internal voltage taps are disconnected and the voltage taps are connected
to terminals VN, V1, V2, V3.
The PTE option is required for voltages less than 220 V and greater than 690 V (in which case
a voltage transformer is compulsory). For three-pole devices, the system is supplied with
terminal VN connected only to the control unit (Micrologic P).
When the PTE option is implemented, the voltage measurement input must be protected against
short-circuits. Installed as close as possible to the busbars, this protection function is ensured
by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117).
This voltage measurement input is reserved exclusively for the control unit and must not ever be
used to supply other circuits outside the switchboard.
Connection
The maximum length for each conductor supplying power to the trip unit or M6C
module is 10 m.
Do not ground F2+, F1-, or power supply output:
bb the positive terminal (F2+) on the trip unit must not be connected to earth ground
bb the negative terminal (F1-) on the trip unit must not be connected to earth ground
bb the output terminals (- and +) of the 24 V DC power supply must not be grounded.
Reduce electromagnetic interference:
bb the input and output wires of the 24 V DC power supply must be physically
separated as much as possible
bb the 24 V DC wires (output of the 24 V DC power supply) shall be twisted together.
bb the 24 V DC wires (output of the 24 V DC power supply) must cross all power
cables perpendicularly
bb power supply conductors must be cut to length. Do not loop excess conductor.
D-13
TOOLS
schneider-electric.com
Additional characteristics
Presentation 2
Functions and characteristics
A-1
Installation recommendations
B-1
Dimensions and connection
C-1
Electrical diagrams
D-1
Tripping curves
Compact NS630b to 3200
Current-limiting curves
Catalogue numbers and order forms
E-2
E-3
F-1
E-1
Additional characteristics
Tripping curves
DB128395.eps
Micrologic 2.0
It ON
It OFF
0.4
0.3
0.2
0.1
0
(1)
In < 400 A
0.3
0.3
0.4
0.5
0.6
0.7
0.8
0.9
400 A y In y 1200 A
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
In > 1200 A
500
640
720
800
880
960
Ig = In x
E-2
DB128398.eps
Additional characteristics
Current-limiting curves
(Isc)
Prospective
Isc peak
Prospective
current
Prospective
Isc
Limited Isc
peak
Actual
current
Limited
Isc
The exceptional limiting capacity of the Compact NS range greatly reduces the
forces created by fault currents in devices.
The result is a major increase in breaking performance. In particular, the service
breaking capacity Ics is equal to 100 % of Icu for limitor circuit breaker.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
the following operations:
bb break three times consecutively a fault current equal to 100 % of Icu
bb check that the device continues to function normally:
vv it conducts the rated current without abnormal temperature rise
vv protection functions perform within the limits specified by the standard
vv suitability for isolation is not impaired.
Thermal effects
Less temperature rise in conductors, therefore longer service life for cables.
Mechanical effects
Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
being deformed or broken.
Electromagnetic effects
Less disturbances for measuring devices located near electrical circuits.
Cascading is a technique directly derived from current limiting. Circuit breakers with
breaking capacities less than the prospective short-circuit current may be installed
downstream of a limiting circuit breaker. The breaking capacity is reinforced by the
limiting capacity of the upstream device.
It follows that substantial savings can be made on downstream equipment and
enclosures.
Current-limiting curves
E-3
Current-limiting curves
Additional characteristics
Current-limiting curves
NS630bN
NS800N
NS1000N
NS1250N
NS1600N
Voltage 660/690 V AC
Limited short-circuit current (k peak)
DB419930.eps
DB419929.eps
NS1600bN
NS630bH
NS2000N
NS800H
NS2500N
NS1000H
NS3200N
NS1250H
NS630bN NS1600H
NS800N
NS1000N
NS1250N
NS630bLB
HB2
NS1600N
NS800LB
NSX630
NS630bL
NSX400
R
NS800L
L
HB1
NS1000L
S
HB2 NSX250
H
R
NS630bL
NS800L NS630bLB
NS1000L NS800LB
N
N
H
H
S
S
NSX630
NSX400
NSX250
NSX100
NSX160
F, N
NSX100
NSX160
HB1
N, H
Thermal-stress curves
DB419932.eps
DB419931.eps
Voltage 660/690 V AC
Limited energy
NS630bH
NS800H
NS1000H
NS1250H
NS1600H
NS630bN
NS800N
NS1000N
NS1250N
NS1600N
NS630bH
NS800H
NS1000H
NS1250H
NS1600H
NS630bN
NS800N
NS1000N
NS1250N
NS1600N
NS1000L
NS630bL
NS800L
NS630bLB
NS800LB
R
N
E-4
NS630bL
NS800L
NS1000L
NSX630
NSX400
F, N
NSX250
NSX100
NSX160
N, H
NS1600bN
NS2000N
NS2500N
NS3200N
NS630bLB
NS800LB
NSX630
NSX400
L
R
HB1 HB2
HB2
NSX250
HB1
NSX100
NSX160
Catalogue numbers
and order forms
Presentation 2
Functions and characteristics
A-1
Installation recommendations
B-1
Dimensions and connection
C-1
Electrical diagrams
D-1
Additional characteristics
E-1
F-2
F-4
F-5
F-6
F-7
Connection
Electrical auxiliaries
Installation accessories
Micrologic control unit, external sensor
Locking and accessories
Chassis locking and accessories
Mechanical interlocking for source changeover
F-12
F-13
F-14
F-15
F-16
F-17
F-18
F-19
F-20
F-21
F-22
F-23
F-24
F-25
F-26
F-27
F-28
F-29
F-30
F-31
F-1
Catalogue numbers
Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33460
33466
33472
33478
33482
4P
33463
33469
33475
33480
33484
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33461
33467
33473
33479
33483
4P
33464
33470
33476
33481
33485
3P
33462
33468
33474
4P
33465
33471
33477
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33546
33552
33558
33564
33568
4P
33549
33555
33561
33566
33570
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33547
33553
33559
33565
33569
4P
33550
33556
33562
33567
33571
3P
33548
33554
33560
4P
33551
33557
33563
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33886
33893
33909
33919
33925
4P
33888
33896
33917
33923
33927
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33887
33894
33916
33922
33926
4P
33889
33901
33918
33924
33928
Compact NS type H
Compact NS type L
Compact NS type N
Compact NS type H
Compact NS type L
Compact NS type N
Compact NS type H
F-2
Version : 2.6
04/02/2016
554E5100
Catalogue numbers
Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33223
33233
33243
33253
33263
4P
33227
33237
33247
33257
33267
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33228
33238
33248
33258
33268
4P
33229
33239
33249
33259
33269
3P
33497
33498
33499
4P
33500
33501
33502
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33323
33333
33343
33353
33363
4P
33327
33337
33347
33357
33367
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33328
33338
33348
33358
33368
4P
33329
33339
33349
33359
33369
3P
33516
33517
33518
4P
33519
33520
33521
NS630b
NS800
NS1000
NS1250
NS1600
3P
34400
34404
34408
34412
34416
4P
34402
34406
34410
34414
34418
NS630b
NS800
NS1000
NS1250
NS1600
3P
34401
34405
34409
34413
34417
4P
34403
34407
34411
34415
34419
NS630b
NS800
NS1000
NS1250
NS1600
3P
34420
34424
34428
34432
34436
4P
34422
34426
34430
34434
34438
NS630b
NS800
NS1000
NS1250
NS1600
3P
34421
34425
34429
34433
34437
4P
34423
34427
34431
34435
34439
NS630b
NS800
NS1000
NS1250
NS1600
3P
33486
33487
33488
33489
33490
4P
33491
33492
33493
33494
33495
Compact NS type H
Compact NS type L
Compact NS type N
Compact NS type H
Compact NS type L
Compact NS type N
Compact NS type H
Compact NS type N
Compact NS type H
DB128404.eps
Front-connected switch-disconnector
Note: select in addition the connection accessories, device accessories and auxiliaries, control-unit accessories and communications option, as required.
554E5100
Version : 2.6
04/02/2016
F-3
Catalogue numbers
DB128407.eps
Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33220
33230
33240
33250
33260
4P
33224
33234
33244
33254
33264
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33221
33231
33241
33251
33261
4P
33225
33235
33245
33255
33265
3P
33222
33232
33242
4P
33226
33236
33246
3P
48952
48953
4P
48955
48956
Compact NS type H
Compact NS type L
Compact NS type LB
DB128408.eps
Basic switch-disconnector
Micrologic 2.0
Micrologic 5.0
Micrologic 6.0
"ammeter" A
basic protection
selective protection
selective + earth-fault protection
3P/4P
33504
33511
33515
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A
"energy" E
basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
33505
33512
33513
33514
Micrologic 2.0 E
Micrologic 5.0 E
Micrologic 6.0 E
"power meter" P
basic protection
selective protection
selective + earth-fault protection
3P/4P
33535
33537
33539
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
65290
65291
65292
Compact NS type NA
3P
33420
33422
33424
33426
33428
4P
33421
33423
33425
33427
33429
Top
Bottom
Top
Bottom
Top
Bottom
3P
33598
33599
33600
33601
33602
33603
4P
33608
33609
33610
33611
33612
33613
Top
Bottom
Top
Bottom
3P
33604
33605
33606
33607
4P
33614
33615
33616
33617
NS630b
NS800
NS1000
NS1250
NS1600
Front connection
630-1000 A - NA/N/H
1250 A - NA/N/H
630-1000 A - L
1600 A - NA/N/H
Rear connection
Vertical NA/N/H/L/LB
Horizontal
NA/N/H/L/LB
F-4
Version : 2.6
04/02/2016
554E5100
Catalogue numbers
Compact NS type N
OOF F
I ON
pus h
pus h
dis charged
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33270
33280
33290
33300
33310
4P
33274
33284
33294
33304
33314
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33271
33281
33291
33301
33311
4P
33275
33285
33295
33305
33315
3P
33272
33282
33292
4P
33276
33286
33296
Compact NS type H
O OFF
Compact NS type L
Basic switch-disconnector
basic protection
selective protection
selective + earth-fault protection
3P/4P
33504
33511
33515
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A
"energy" E
basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
33505
33512
33513
33514
Micrologic 2.0 E
Micrologic 5.0 E
Micrologic 6.0E
"power meter" P
basic protection
selective protection
selective + earth-fault protection
3P/4P
33535
33537
33539
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
65290
65291
65292
Compact NS type NA
DB128411.eps
OOF F
Micrologic 2.0
Micrologic 5.0
Micrologic 6.0
"ammeter" A
3P
4P
NS630b
33440
33441
NS800
33442
33443
NS1000
33444
33445
NS1250
33446
33447
NS1600
33448
33449
Note: the characteristics of the motor mechanism module for electrical operation are specified
separately by selecting a part number from the table at the bottom of this page.
I ON
pus h
pus h
dis charged
O OFF
Front connection
630-1000 A - NA/N/H
1250 A - NA/N/H
630-1000 A - L
1600 A - NA/N/H
Rear connection
Vertical NA/N/H/L
Horizontal
NA/N/H/L
Top
Bottom
Top
Bottom
Top
Bottom
3P
33598
33599
33600
33601
33602
33603
4P
33608
33609
33610
33611
33612
33613
Top
Bottom
Top
Bottom
33604
33605
33606
33607
33614
33615
33616
33617
AC 50/60 Hz
U
48 V
100/130 V
220/240 V
380/415 V
Standard
33691
33687
33688
33689
(*)
(*)
(*)
(*)
Communicating
33698
33694
33695
33696
DC
(*)
(*)
(*)
(*)
24/30 V
48/60 V
100/130 V
200/250 V
Standard
33690
33691
33692
33693
(*)
(*)
(*)
(*)
Communicating
33697
33698
33699
33700
(*)
(*)
(*)
(*)
554E5100
Version : 2.6
04/02/2016
F-5
Catalogue numbers
DB128413.eps
Compact NS type N
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33320
33330
33340
33350
33360
4P
33324
33334
33344
33354
33364
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33321
33331
33341
33351
33361
4P
33325
33335
33345
33355
33365
3P
33322
33332
33342
4P
33326
33336
33346
3P
48967
48968
4P
48971
48972
Compact NS type H
Compact NS type L
Compact NS type LB
DB128414.eps
Basic switch-disconnector
Micrologic 2.0
Micrologic 5.0
Micrologic 6.0
"ammeter" A
basic protection
selective protection
selective + earth-fault protection
3P/4P
33504
33511
33515
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A
"energy" E
basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
33525
33532
33533
33534
Micrologic 2.0 E
Micrologic 5.0 E
Micrologic 6.0 E
"power meter" P
basic protection
selective protection
selective + earth-fault protection
3P/4P
33536
33538
33540
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
65293
65294
65295
Compact NS type NA
NS630b
NS800
NS1000
NS1250
NS1600
DB128415.eps
Chassis
630-1250 A - NA/N/H
1600 A - NA/N/H
630/800 A - LB
630-1000 A - L
+ connection
DB128417.eps
DB128416.eps
Front connection
Top NA/N/H/L/LB
Bottom NA/N/H/L/LB
Rear connection
Vertical NA/N/H/L/LB
Horizontal
NA/N/H/L/LB
Top
Bottom
Top
Bottom
3P
33430
33432
33434
33436
33438
4P
33431
33433
33435
33437
33439
3P
33722
33723
4P
33725
33726
3P
4P
33727
33728
33733
33734
33729
33730
33731
33732
33735
33736
33737
33738
F-6
Version : 2.6
04/02/2016
554E5100
Catalogue numbers
Compact NS type N
OOF F
I ON
pus h
pus h
dis c
Icu = 50 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33370
33380
33390
33400
33410
4P
33374
33384
33394
33404
33414
Icu = 70 kA at 220/415 V
NS630b
NS800
NS1000
NS1250
NS1600
3P
33371
33381
33391
33401
33411
4P
33375
33385
33395
33405
33415
3P
33372
33382
33392
4P
33376
33386
33396
Compact NS type H
harged
O OF F
Compact NS type L
Basic switch-disconnector
pus h
3P/4P
33504
33511
33515
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A
"energy" E
basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
33525
33532
33533
33534
Micrologic 2.0 E
Micrologic 5.0 E
Micrologic 6.0 E
"power meter" P
basic protection
selective protection
selective + earth-fault protection
3P/4P
33536
33538
33540
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
65293
65294
65295
3P
4P
NS630b
33450
33451
NS800
33452
33453
NS1000
33454
33455
NS1250
33456
33457
NS1600
33458
33459
Note: the characteristics of the motor mechanism module for electrical operation are specified
separately by selecting a part number from the table at the bottom of this page.
ON
OF F
dis c
basic protection
selective protection
selective + earth-fault protection
Compact NS type NA
DB128419.eps
pus h
Micrologic 2.0
Micrologic 5.0
Micrologic 6.0
"ammeter" A
harged
O OF F
Chassis
630-1250 A - NA/N/H
1600 A - NA/N/H
630-1000 A - L
+ connection
DB128417.eps
DB128416.eps
Front connection
Top NA/N/H/L
Bottom NA/N/H/L
Rear connection
Vertical NA/N/H/L
Horizontal
NA/N/H/L
AC 50/60 Hz
48 V
100/130 V
220/240 V
380/415 V
Top
Bottom
Top
Bottom
Standard
33831
33827
33828
33829
(*)
(*)
(*)
(*)
Communicating
33838
33834
33835
33836
DC
(*)
(*)
(*)
(*)
24/30 V
48/60 V
100/130 V
200/250 V
554E5100
Version : 2.6
04/02/2016
3P
33722
33723
4P
33725
33726
3P
4P
33727
33728
33733
33734
33729
33730
33731
33732
33735
33736
33737
33738
Standard
33830
33831
33832
33833
(*)
(*)
(*)
(*)
Communicating
33837
33838
33839
33840
(*)
(*)
(*)
(*)
F-7
Catalogue numbers
Accessories for
NS630btoNS1600 fixed
devices
Connection accessories
Front connection
DB128420.eps
DB128421.eps
DB128422.eps
Vertical-connection adapters
DB128423.eps
240 mm2
300 mm2
DB128425.eps
Interphase barriers
DB128426.eps
3P (3 parts)
4P (4 parts)
33640
33641
3P
4P
33628
33629
3P (3 parts)
4P (4 parts)
33642
33643
3P (3 parts)
4P (4 parts)
33644
33645
33644
33645
3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)
33013
33014
33015
33016
33013
33014
33015
33016
33646
33646
33648
33648
3P
4P
64907
33597
64908
3P/4P (2 parts)
33622
33623
3P
4P
DB128427.eps
Rear connection
33622
33623
Electrical auxiliaries
DB128428.eps
Indication contacts
6 A - 240 V
Low level
OF, ON/OFF indication contacts
33108
33109
SD, trip indication contact for manually operated devices
33004
33008
SDE, fault indication contact operated devices
33011
33012
Up to 3 OF, 1 SD and 1 SDE can be connected (the SDE contact is standard for electrically operated devices).
DB128429.eps
DB128431.eps
DB128430.eps
Installation accessories
ref. 33717
ref. 33718
65319
MN
Delay unit
R (non-adjustable) Rr (adjustable)
33668
33669
33670
33671
48/60 V AC/DC
100/130 V AC/DC 33684
200/250 V AC/DC 33685
33680
33681
33682
33673
380/480 V AC/DC
33683
33717
33718
Blanking plate
DB128432.eps
33858
F-8
Version : 2.6
04/02/2016
554E5100
Accessories for
NS630btoNS1600
withdrawable devices
Catalogue numbers
Connection accessories
Front connection
DB128423.eps
DB128422.eps
Vertical-connection adapters
DB128424.eps
240 mm2
300 mm
Interphase barriers
3P (3 parts)
4P (4 parts)
33642
33643
3P (3 parts)
4P (4 parts)
33644
33645
33644
33645
3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)
33013
33014
33015
33016
33013
33014
33015
33016
33768
DB128433.eps
3P/4P (3 parts)
Spreaders
33622
33623
3P (3 parts)
4P (4 parts)
DB128427.eps
Rear connection
33622
33623
Chassis accessories
DB128434.eps
DB128435.eps
3P
4P
33763
33764
3P
4P
33765
33766
Electrical auxiliaries
OF ON/OFF indication contacts
DB128436.eps
6 A - 240 V
Low level
OF, ON/OFF indication contacts
33801
33804
SD, trip indication contact for manually operated devices
33800
33803
SDE, fault indication contact operated devices
33799
33802
Up to 3 OF, 1 SD and 1 SDE can be connected (the SDE contact is standard for electrically operated devices)
DB128437.eps
DB128438.eps
6 A - 240 V
Low level
Up to 3 CE, 1 CT, 2 CD per device
33170
33171
65320
DB128439.eps
MX
33809
33810
33811
33812
33813
33814
33815
MN
Delay unit
33819
33820
33821
33822
48/60 V AC/DC
100/130 V AC/DC 33684
200/250 V AC/DC 33685
33680
33681
33682
33824
380/480 V AC/DC
33683
47071
47072
47900
554E5100
R (non-adjustable) Rr (adjustable)
Version : 2.6
04/02/2016
F-9
Catalogue numbers
Accessories for
NS630btoNS1600
withdrawable devices
Chassis locking
Keylocking in disconnected position
DB128440.eps
By Profalux keylocks
Profalux
DB128441.eps
Door interlock
64909
64910
64911
33173
33174
33175
64912
64913
64914
33189
33190
33191
33192
33779
33769
33770
33771
33772
33786
33787
33788
33767
Installation accessories
Escutcheon
DB128430.eps
33857
33859
Blanking plate
DB128432.eps
33858
F-10
Version : 2.6
04/02/2016
554E5100
Accessories for
NS630btoNS1600 fixed and
withdrawable devices
Catalogue numbers
44936
DB128448.eps
Locking by 3 padlocks
32631
DB128449.eps
Locking by 3 padlocks
ed
tripp
reset
0 OFF
DB128451.eps
Mechanical interlocking
OFF position
OFF and ON positions
I on
ed
tripp
reset
0 OFF
Profalux
33869
33871
33868
33890
33863
33864
33866
Ronis
33870
33872
33868
I on
33878
33879
33880
ON
tripped
reset
OFF
DB128453.eps
Control accessories
Fixed
Withdrawable
33882
33883
33884
33885
Pushbutton locking
DB128455.eps
DB128456.eps
33897
By Profalux keylocks
Profalux
33902
33904
33895
33173
33174
33175
33903
33905
33189
33190
33191
33192
33898
33899
47517
47518
9
0039
554E5100
Version : 2.6
04/02/2016
F-11
Catalogue numbers
Accessories for
NS630b to 1600 fixed and
withdrawable devices
Mechanical interlocking
33910
33913
FFO
h
sup
NO h
sup
FFO
O
degr
ahcs
id
FFO
hsup
NO h
sup
FFO
O
degr
ahcs
id
33911
33914
33915
FFO
h
sup
NO h
sup
FFO
O
degr
ahcs
id
FFO
hsup
NO h
FFO
sup
O
degr
ahcs
id
F-12
Version : 2.6
04/02/2016
554E5100
Catalogue numbers
Communication options
DB417414.eps
DB111441.eps
DB417415.eps
IFE
LV434010
LV434011
TRV00210
LV434063
DB128457.eps
Ethernet interface
for LV breaker
Ethernet interface
for LV breakers and gateway
COM (BCM-ULP)
Eco COM module (BCM-ULP)
COM (BCM-ULP)
Eco COM module (BCM-ULP)
+ chassis
I/O application module
Manually operated
33702
33703
Electrically operated
33708
33709
Manually operated
33842
33714
Electrically operated
33848
33713
64915
64915
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s)
2
1
.5
8 12
16
20
24
Ir
@6
Standard
Low setting
High setting
Without long-time protection
0.4 to 1 x Ir
0.4 to 0.8 x Ir
0.8 to 1 x Ir
OFF
33542
33543
33544
33545
65317
65316
33576
33573
33579
48891
DB128460.eps
DB128460.eps
DB128459.eps
External sensors
DB128461.eps
Test equipment
DB128463.eps
DB128464.eps
554E5100
24/30 V DC
48/60 V DC
100/125 V DC
110/130 V AC
200/240 V AC
380/415 V AC
54440
54441
54442
54443
54444
54445
33594
33595
34559
34560
33590
Version : 2.6
04/02/2016
F-13
Catalogue numbers
Circuit breaker
DB128467.eps
Compact NS type N
3P
34000
34006
34012
34018
4P
34003
34009
34015
34021
3P
34001
34007
34013
34019
4P
34004
34010
34016
34022
Compact NS type H
OFF
OFF
Switch-disconnector
Micrologic 2.0
Micrologic 5.0
Micrologic 6.0
"ammeter" A
basic protection
selective protection
selective + earth-fault protection
3P/4P
33504
33511
33515
Micrologic 2.0 A
Micrologic 5.0 A
Micrologic 6.0 A
Micrologic 7.0 A
"energy" E
basic protection
selective protection
selective + earth-fault protection
selective + earth-leakage protection
3P/4P
33505
33512
33513
33514
Micrologic 2.0 E
Micrologic 5.0 E
Micrologic 6.0 E
basic protection
selective protection
selective + earth-fault protection
3P/4P
33535
33537
33539
DB128468.eps
Compact NS type NA
3P
34024
34027
34030
34033
NS1600b
NS2000
NS2500
NS3200
4P
34025
34028
34031
34034
OFF
OFF
1600/2500 A
33975
33976
3P (3 parts)
4P (4 parts)
Electrical auxiliaries
DB128428.eps
Indication contacts
6 A - 240 V
33108
33004
33011
DB128429.eps
Locking
12 V DC
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
277 V AC
380/480 V AC
MX
33658
33659
33660
33661
33662
33663
33664
MN
Delay unit
48/60 V AC/DC
100/130 V AC/DC 33684
200/250 V AC/DC 33685
33680
33681
33682
33673
380/480 V AC/DC
33683
33996
DB128448.eps
Locking by 3 padlocks
32631
Locking by 3 padlocks
DB128449.eps
R (non-adjustable) Rr (adjustable)
33668
33669
33670
33671
F-14
Low level
33109
33008
33012
Version : 2.6
04/02/2016
554E5100
Catalogue numbers
Accessories for
NS1600btoNS3200
Communication option
Ethernet interface
LV434010
for LV breaker
Ethernet interface
LV434011
for LV breakers and gateway
IFM Modbus-SL interface module
TRV00210
I/O application module
LV434063
DB128462.eps
IFE
COM (BCM-ULP)
OFF
33986
OFF
33988
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s)
2
1
.5
8 12
16
20
24
Ir
@6
DB128460.eps
DB128460.eps
DB128459.eps
External sensors
Standard
Low setting
High setting
Without long-time protection
33542
33543
33544
33545
0.4 to 1 x Ir
0.4 to 0.8 x Ir
0.8 to 1 x Ir
OFF
34036
33574
33579
48891
DB128461.eps
Test equipment
DB128463.eps
DB128464.eps
24/30 V DC
48/60 V DC
100/125 V DC
110/130 V AC
200/240 V AC
380/415 V AC
54440
54441
54442
54443
54444
54445
33594
33595
34559
34560
33590
Installation accessories
Escutcheon
DB128444.eps
33929
33998
554E5100
Version : 2.6
04/02/2016
F-15
Catalogue numbers:
spare parts
Connection
Connections for circuit breakers and switch-disconnectors
DB401441.eps
Top
Bottom
Top
Bottom
3P
33598
33599
33600
33601
4P
33608
33609
33610
33611
Top
Bottom
33602
33603
33612
33613
3P
33584
33148
4P
33585
DB401442.eps
Connection accessories
Bare-cable connectors + 1 connector shield for 4 cables (240 mm)
DB128420.eps
3P
4P
Installation manual
33628
33629
3P
4P
DB128422.eps
DB128421.eps
3P
4P
Installation manual
DB128425.eps
3P
4P
Installation manual
64907
33597
33148
3P/4P
64908
DB128427.eps
33622
33623
33148
3P
4P
Installation manual
DB128424.eps
33644
33645
33148
Front connection
33646
33646
33148
300 mm
Installation manual
F-16
33642
33643
33148
3P/4P top
3P/4P bottom
Installation manual
DB101032.eps
DB128426.eps
33640
33641
33148
3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)
33013
33014
33015
33016
33148
Rear connection
33648
33648
Catalogue numbers:
spare parts
6 A - 240 V
Low level
OF, ON/OFF indication contacts
29450
29452
SD trip indication contact for manually operated devices
29450
29452
SDE fault indication contact operated devices
29450
29452
Up to 3 OF, 1 SD and 1 SDE can be connected (the SDE contact is standard for electrically operated devices).
Installation manual
33148
DB128429.eps
MX
12 V DC
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
277 V AC
380/480 V AC
Installation manual
DB128431.eps
DB128143.eps
DB128432.eps
DB419924.eps
DB128447.eps
33658
33659
33660
33661
33662
33663
33664
33149
MN
Delay unit
R (non-adjustable)
Rr (adjustable)
33668
33669
33670
33671
48/60 V AC/DC
100/130 V AC/DC
200/250 V AC/DC
33684
33685
33680
33681
33682
33673
380/480 V AC/DC
33683
33717
Escutcheon for:
- device with toggle (large cutout)
- device with rotary handle
- electrically operated device
33718
Blanking plate
33858
Installation manual
33148
Toggle extension
46996
33195
F-17
Catalogue numbers:
spare parts
Long-time rating plug (limits setting range for higher accuracy) / 1 part
Standard
Low-setting option
High-setting option
Without long-time protection
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s)
2
1
.5
8 12
16
20
24
Ir
@6
DB128353.eps
Battery + cover
Battery (1 part)
Cover (1 part)
0.4 at 1 x Ir
0.4 at 0.8 x Ir
0.8 at 1 x Ir
off
33542
33543
33544
33545
For Micrologic A, E
For Micrologic P
33593
33592
47067
LV434010
LV434011
Communication option
DB417414.eps
DB111441.eps
DB417415.eps
IFE
TRV00210
LV434063
DOCA0084EN-00
DOCA0055EN-00
DB128460.eps
DB128460.eps
DB128459.eps
External sensors
33576
33573
33579
48891
DB128461.eps
DB128464.eps
F-18
24-30 V DC
48-60 V DC
100-125 V DC
110-130 V AC
200-240 V AC
380-415 V AC
54440
54441
54442
54443
54444
54445
33594
33595
34559
34560
33590
Catalogue numbers:
spare parts
44936
Installation manual
33148
DB128449.eps
DB128448.eps
Locking by 3 padlocks
32631
Installation manual
33148
33866
Ronis
33870
33872
33868
33150
33890
DB128352.eps
Conversion accessory
Locking by keylocks
CNOMO
OFF position
OFF and ON positions
DB128451.eps
Mechanical interlocking
Profalux
33869
33871
33868
33897
Installation manual
47103
By Profalux keylocks
Profalux
33902
33904
33895
Installation manual
47103
DB128456.eps
33173
33174
33175
33903
33905
33189
33190
33191
33192
33898
33899
47517
47518
47103
F-19
Catalogue numbers:
spare parts
33910
FFO
h
sup
NO h
sup
FFO
O
degr
ahcs
id
FFO
hsup
NO h
sup
FFO
O
degr
ahcs
id
FFO
h
sup
NO h
sup
FFO
O
degr
ahcs
id
FFO
hsup
NO h
FFO
sup
O
degr
ahcs
id
F-20
33911
33915
Catalogue numbers:
spare parts
DB128416.eps
Connection
Front connection / Replacement kit (6 or 8 parts)
DB128417.eps
DB401444.eps
3P
4P
33588
33589
33586
33587
33149
Vert. mounting.
Connection accessories
Vertical connection adapters for front-connected chassis / Replacement kit (3 or 4 parts)
33642
33643
33149
DB128422.eps
3P
4P
Installation manual
33644
33645
33149
DB128423.eps
3P
4P
Installation manual
DB401447.eps
33768
Installation manual
33149
33622
33623
33149
DB128427.eps
3P
4P
Installation manual
240 mm
300 mm
Installation manual
33013
33014
33015
33016
33149
3P (6 lug kit)
4P (8 lug kit)
3P (6 lug kit)
4P (8 lug kit)
Chassis accessories
DB128434.eps
DB401445.eps
3P
4P
Installation manual
33763
33764
33149
3P
4P
Installation manual
33765
33766
47104
64906
Compact NS - 3P
NA - N
630
12
800
12
1000
12
1250
12
1600
18
Note: the minimum order is 6 parts.
DB418007.eps
DB417990.eps
DB401446.eps
Clusters
L
18
18
18
Compact NS - 4P
NA - N
16
16
16
16
24
L
24
24
24
47554
F-21
Catalogue numbers:
spare parts
Electrical auxiliaries
Electrical auxiliaries
SD trip indication contact for manually operated devices / 1 part
DB128436.eps
6 A - 240 V
Low level
OF, ON/OFF indication contacts
33801
33804
SD trip indication contact for manually operated devices
33800
33803
SDE fault indication contact operated devices
33799
33802
Up to 3 OF, 1 SD and 1 SDE can be connected (the SDE contact is standard for electrically operated devices).
Installation manual
47103
33170
33171
DB128437.eps
6 A - 240 V
Low level
Up to 3 CE, 1 CT, 2 CD per device
Installation manual
DB128429.eps
DB128354.eps
DB401448.eps
3 wires.
F-22
6 wires.
MX
33658
33659
33660
33661
33662
33663
33664
47103
47104
MN
Delay unit
R (non-adjustable) Rr (adjustable)
33668
33669
33670
33671
48/60 V AC/DC
100/130 V AC/DC
200/250 V AC/DC
33684
33685
33673
380/480 V AC/DC
33680
33681
33682
33683
33098
33099
47900
47103
Catalogue numbers:
spare parts
Installation accessories
DB128430.eps
Escutcheon / 1 part
DB128445.eps
DB128432.eps
33857
33859
33858
F-23
Catalogue numbers:
spare parts
Long-time rating plug (limits setting range for higher accuracy) / 1 part
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s)
2
1
.5
8 12
16
20
24
Ir
@6
DB128353.eps
Battery + cover
Standard
Low-setting option
High-setting option
Without long-time protection
Battery (1 part)
Cover (1 part)
0.4 at 1 x Ir
0.4 at 0.8 x Ir
0.8 at 1 x Ir
off
33542
33543
33544
33545
For Micrologic A, E
For Micrologic P
33593
33592
47067
LV434010
LV434011
Communication option
DB417414.eps
DB111441.eps
DB417415.eps
IFE
TRV00210
LV434063
DOCA0084EN-00
DOCA0055EN-00
DB128460.eps
DB128460.eps
DB128459.eps
External sensors
33576
33579
48891
33573
DB128461.eps
DB128464.eps
F-24
24-30 V DC
48-60 V DC
100-125 V DC
110-130 V AC
200-240 V AC
380-415 V AC
54440
54441
54442
54443
54444
54445
33594
33595
34559
34560
33590
Catalogue numbers:
spare parts
Locking by 3 padlocks
44936
Installation manual
33148
DB128449.eps
Locking by 3 padlocks
32631
Installation manual
33148
Conversion accessory
Locking by keylocks
DB128451.eps
Mechanical interlocking
CNOMO
OFF position
OFF and ON positions
Keylock kit (without keylocks)
Installation manual
33866
Ronis
33870
33872
33868
Profalux
33869
33871
33868
33150
33890
33897
Installation manual
47103
By Profalux keylocks
Profalux
DB128456.eps
33902
33904
33173
33174
33175
33903
33905
33189
33190
33191
33192
33898
33899
47517
47518
47103
33895
Installation manual
47103
F-25
Catalogue numbers:
spare parts
Chassis locking
Keylocking in disconnected position / 1 part
DB128440.eps
By Profalux keylocks
Profalux
Adaptation kit
(without keylock):
DB403913.eps
64909
64910
64911
33173
33174
33175
64912
64913
64914
33189
33190
33191
33192
33769
33770
33771
33772
33172
Installation manual
47104
DB403914.eps
Installation manual
DB128443.eps
33788
47104
33767
47104
33913
FFO
h
sup
NO h
sup
FFO
O
degr
ahcs
id
FFO
hsup
NO h
sup
FFO
O
degr
ahcs
id
FFO
h
sup
NO h
sup
FFO
O
degr
ahcs
id
FFO
hsup
NO h
FFO
sup
O
degr
ahcs
id
F-26
33914
33915
Catalogue numbers:
spare parts
Instructions
Chassis accessories
Circuit breaker accessories
Fixed and drawout circuit breaker
NS630b user manual
French
English
Micrologic user manual
20/50 (French)
20/50 (English)
2A/7A (French)
2A/7A (English)
2E/6E (French)
2E/6E (English)
5P/7P (French)
5P/7P (English)
Modbus communication notice for manual
Manual
Electrical
Manual
Electrical
47104
33148
33149
33148
33149
33159
33160
33076
33077
33079
33080
33079
33080
33082
33083
33088
F-27
Catalogue numbers:
spare parts
Communication options
DB417414.eps
DB111441.eps
DB417415.eps
IFE
LV434010
LV434011
TRV00210
LV434063
TRV00121
TRV00128
LV434128
LV434195
LV434196
LV434197
VW3A8306DRC (2)
TRV00870
TRV00880
DB417489.eps
DB111445.eps
DB111444.eps
DB115623.eps
DB111443.eps
DB127985.eps
F-28
TRV00803
TRV00806
TRV00810
TRV00820
TRV00830
TRV00850
Catalogue numbers:
spare parts
Spare parts:
Compact NS1600b to 3200
Connection, locking and installation
accessories
1600/2500/3200 A
33975
33976
3P
4P
33969
Installation manual
Electrical auxiliaries
Indication contacts (1 part)
29450
29452
6 A - 240 V
Low level
Note: up to 3 OF, 1 SD and 1 SDE can be connected.
Installation manual
DB128428.eps
DB128429.eps
12 V DC
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
277 V AC
380/480 V AC
Installation manual
Locking
MX
33658
33659
33660
33661
33662
33663
33664
33969
DB128448.eps
MN
Delay unit
R (non-adjustable) Rr (adjustable)
33668
33669
33670
33671
48/60 V AC/DC
100/130 V AC/DC 33684
200/250 V AC/DC 33685
33680
33681
33682
33673
380/480 V AC/DC
33683
Locking by 3 padlocks
33996
Installation manual
33969
33969
Locking by 3 padlocks
32631
Installation manual
33969
Installation accessories
Escutcheon / 1 part
DB128444.eps
33929
DB128446.eps
DB128338.eps
33998
Installation manual
33969
33997
Installation manual
33969
OFF
F-29
Catalogue numbers:
spare parts
Spare parts:
Compact NS1600b to 3200
Long-time rating plug (enhanced accuracy by limiting the setting range) / 1 part
alarm
long
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
tr
(s)
2
1
.5
8 12
16
20
24
Ir
@6
Standard
Low setting
High setting
Without long-time protection
0.4 to 1 x Ir
0.4 to 0.8 x Ir
0.8 to 1 x Ir
OFF
33542
33543
33544
33545
DB128460.eps
DB128460.eps
DB128459.eps
External sensors
34036
33579
48891
33574
DB128461.eps
DB128464.eps
F-30
24-30 V DC
48-60 V DC
100-125 V DC
110-130 V AC
200-240 V AC
380-415 V AC
54440
54441
54442
54443
54444
54445
33594
33595
34559
34560
33590
Order form:
Compact NS630b to NS3200
Order form
NS630b to NS1600
NS1600b to NS3200
A
N, H, L, LB
NA
3 or 4
Fixed
Withdr. with chassis
Withdr. without chassis
(moving part only)
Compact type
Rating
Circuit breaker
Switch-disconnector
Number of poles
Device
NS630b/3200
NS630b/1600
Indication contacts
NS630b/3200
Remote operation
Electrical operation
(NS630b/1600)
Voltage releases
Basic protection
A - ammeter
E - energy
2.0
5.0
6.0
2.0
5.0
6.0
2.0
5.0
6.0
7.0
Communication
Cradle
management with
I/O application
module (Chassis)
Mounting accessories
Communicating
DC
DC
DC
Ajustable
Extended
Indication auxiliary
Locking
V
V
V
Non ajustable
Black
Toggle (1 to 3 padlocks)
Rotary handle
using a keylock
(NS630b/1600)
For electrically
operated devices
(NS630b/1600)
Removable system
Fixed system
OFF position
ON and OFF positions
Ronis 1351B.500
Profalux KS5 B24 D4Z
Keylock kit (without keylock)
VBP - ON/OFF pushbutton locking
(by transparent cover +padlocks
OFF position locking:
VCPO - by padlocks
VSPO - by keylocks:
Keylock kit (w/o keylock)
Profalux
1 keylock
Profalux
2 identical keylocks, 1 key
Profalux
Chassis locking in "disconnected" position:
VSPD - by keylocks
Keylock kit (w/o keylock)
Profalux
Kirk
1 keylock
Profalux
2 identical keylocks, 1 key
Profalux
2 keylocks, different keys
Profalux
Optional connected/disconnected/test position locking
VPEC - door interlock
On right-hand side of chassis
On left-hand side of chassis
VPOC - racking interlock
VDC - mismatch protection
Accessories
NS630b/1600 connection
AC
AC
AC
Direct
P - power
only for NS630b/1600
5.0
6.0
7.0
AD - external power-supply module
V
ENVT - External Neutral Voltage Temp. (3P + N and Micrologic P)
TCE - external sensor (CT) for neutral protection
Rectangular sensor
NS630b/1600
280 x 115 mm
for earth-leakage protection NS1600b/3200
470 x 160 mm
TCW - external sensor for SGR protection
LR - long-time rating plug
Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
Hight setting 0.8 to 1 Ir
LT OFF
COM module
Device
(BCM-ULP)
Standard
Power supply
MX
MN
MN delay unit
Ronis
Ronis
Ronis
Ronis
Castell
Ronis
Ronis
Ronis
NS - withdrawable as standard
NS1600b/3200 connection
Front connections
Vertical connection adaptor
NS - FC fixed
optional for NS1600b/2500
(standard for NS3200)
F-31
Note
F-32
Note
F-33
Note
F-34
10-31-1247
01-2016