Title Specification For Distribution Transformer Pole Mounted Phase Oil
Title Specification For Distribution Transformer Pole Mounted Phase Oil
Title Specification For Distribution Transformer Pole Mounted Phase Oil
TITLE:
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Doc.No.
KP1/6C.1i13fTSP/10/001 02
Issue No.
Revision No.
Date of Issue
Page 30 of 55
2015-09-02
relevant
copies of the Manufacturer's catalogues, brochures, drawings, technical data & calculations, sales
records for past five years, four customer reference letters, details of manufacturing capacity, the
manufacturer's experience, copies of complete type test reports and accreditation certificate to
ISO/IEC 17025 for the third party testing laboratory for tender evaluation, all in English
Language)
TENDER NO................................. .BIDDER'S NAME & ADDRESS ..........................
I
Clause
Number
Description
4.1.1
4.1.2.1
4.1.2.3
4.2
4.2.1
4.2.2
4.2.3
4.2.4
General Requirements
Outdoor, oil type, ONAN and core type
Design Service Life
Two winding, three phase integral unit
Types of transformers offered
1.
2
3
4.2.4.1
4.2.4.2
SOkVA
BIDDER'S OFFER
100kVA 200kVA 315kVA
temperature
range,
pollution and isokeraunic level)
Systemhumidity,
Characteristics
Signed:
(( LL ').l
Signed:
- Cib-
"t ...
Date:2015-09-02
TITLE:
4.2.6
4.2.7
4.2.8
4.2.9
4.2.10
4.2.11
4.2.12
4.2.13
4.2.14
4.2.15
4.2.16
4.2.17a)
to g)
KP1/6C.1/13fTSP/10/001-02
5
Revision No.
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
4.2.5
Doc.No.
Issue No.
Date of Issue
2015-09-02
Page 31 of 55
Description
BIDDER'S OFFER
SOkVA 100kVA 200kVA 31SkVA
<L:U
..(\-:i -:-;
v
Date: 2015-09-02
C42-
..-
TITLE:
4.3.1
4.3.2
4.3.3
4.3.4
Date of Issue
Page 32 of 55
Description
Indicate KVA & voltage ratings in columns on the right
Alldesign drawings MUST BE stamped and signed by the
manufacturer's authorised personnel.
KVA, no-load voltage ratings and frequency
Top Oil
Temperature
Rise
I
I
KP1/6C.1/13/TSP/10/001-02
5
SPECIFICATION FOR
Kenya Power
Clause
Number
Doc.No.
Issue No.
1
2015-09-02
SOkVA
BIDDER'S OFFER
100kVA 200kVA 315kVA
Windings
60076-5
Short circuit current density (Aimm.:) HV winding
Short circuit current density (A/mm") LV winding
Average temperature a, attained by each windni g after
short circuit (calculation of temperature as per clause
4.1.5 of IEC
60076-5)
4.3.5
60076-5
4.3.6
4.4
4.4.1.1
4.4.1.2
4.4.1.3
4.4.2
4.4.2.1
4.4.2.2
HVwinding density, LV
winding
2
A/mm
Signed:
Signed:
Date: 2015-09-02
c:r::: J.d.d\UY.
Date: 2015-09-02
'
TITLE:
DISTRIBUTION TRANSFORMER
Part 2: Pole Mounted Three
Phase Oil Type Distribution
Transformer
Revision No.
Date of Issue
2015-09-02
Page 33 of 55
Description
4.4.2.3
KP1/6C.1/131TSP/10/001-02
5
SPECIFICATION FOR
Kenya Power
Clause
Number
Doc.No.
Issue No.
50kVA
BIDDER'S OFFER
100kVA 200kVA 315kVA
HVwinding
LV winding
HVwinding
LV winding
I
I
HVwinding
LV winding
Characteristics of copper wire and aluminium wire
Standard of manufacture
Type designation or grade
Specific heat at 100
(Jikg"C)
Copper
Density at 100
(kg/m..)
oc
c
Resistivity at 100 oc (IJOm)
Standard of manufacture
Type designation or grade
Aluminium Specific heat at 1oo
(J/kg "C)
Density at 1oo c (kg/m..)
oo c
Resistivity at 1
(IJOm)
Characteristics of copper and aluminium foil/strip
Standard of manufacture
Type designation or grade
Ultimate tensile strength, N/mm"
Copper
Density in 20uC, kg/dm..
Elongation,%, min
Maximum resistance at 20uC, Omm"/m
Aluminium
4.4.2.4
4.4.3.1
4.4.3.2
Standard of manufacture
Type designation or grade
Ultimate tensile strength, N/mm"
Density in 20uC, kg/dm..
Elongation, % min
Maximum resistance at 20uC, Omm"/m
Stage inspection by Kenya Power
Insulating material
Separation of windings for cooling and ease of repair
Insulation sleeves material
lnterlayer insulation material
Double layerinsulation
Temperature class of insulation
Standard of manufacture
Crepe
paper
Type designation or grade
-.
Date:2015-0902
:J
v
- ce= de==---
Date:2015-09-02
TITLE:
KP1/6C.1/13/TSP/10/00102
5
Revision No.
Date of Issue
2015-09-02
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Part 2: Pole Mounted
Three Phase Oil Type
Distribution Transformer
Kenya Power
Clause
Number
Doc.No.
Issue No.
Page 34 of 55
Description
Indicate KVA & voltage ratings in columns on the right
Apparent density,
Grammage
Conductivity of aqueous extract
Electric strength in oil
50kVA
BIDDER'S OFFER
100kVA 200kVA 315kVA
I Machine
Tensile strength
Presspaper
- Grade
type
direction
Standard of manufacture
Type designation or
grade Apparent density,
Grammage
Conductivity of aqueous extract
Electric strength in oli
Tensile strength
I Machine direction
I Cross machine direction
Krapt
paper/
Celullosic
paper
4.4.4
4.4.4.1
4.4.4.2
4.5
4.5.1
4.5.2.
4.5.2.1
4.5.2.3
4.5.2.4
4.6
4.6.1
4.6.1.1
4.6.1.2
Standard of manufacture
Type designation or grade
Apparent density
Conductivity
Air permeability
Standard of manufacture
Radial
spacer
Type designation or
grade
blocks
Electrical and mechanical properties
Connections
Windings, joints & connections braced/brazed?
Drying in vacuum & impregnat ng with hot oil
Tapping
Tapping range
Tapping method and design
Standard of manufacture
Type designation or grade
Tap changer (ratio tapMode of operation
switch)
Shank diameter
Height of ratio tap-switch
Gap between ratio tap-switch top to the inside of the tank
Tap switch position number 1, orientation
Core and Flux Density
Core
Standard of manufacture of core material
Type designation or Grade of core steel
Insulating material for CRGO to prevent corrosion
Thickness of each single lamination
(<; . l
'6:SQ:;:)
Signed:
/I).
Date:2015-09-02
-.1-
'
Dnte:2015-09-02
TITLE:
KP1/6C.1/13/TSP/10/001-02
5
Revision No.
Date of Issue
2015-09-02
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
Doc.No.
Issue No.
Page 35 of 55
Description
50kVA
BIDDER'S OFFER
100kVA
200kVA 315kVA
4.6.1.3
4.6.1.4
4.6.1.5
4.6.1.6
4.6.1.7
4.6.1.8
4.6.1.9
4.6.1.10
4.6.2
4.6.2.1
4.6.2.2
4.6.2.3
4.6.2.4
4.6.2.5
4.7
4.7.1
Signed:
'
Date:2015-09-02
Issued by: Head of Section, Standard developm ent
Signed:
Short-circuit lmpendence,%
Resistance at 75uC of HV Winding in ohms
(at normal & extreme taps)
Resistance at 75C of LV Winding in ohms
Minimum efficiency at 100% load (unity power factor), at
75C
Total losses (no-load+ load losses) at 100% load
No-load Losses at 75C
Load Losses at 50% load,75C
Load Losses at 75% load, 75C
Load Losses at 100% load,
75C
I"'R component of load losses at 100% load,
75C Load Losses at 125% load, 75C
Stray Losses at 50% load, 75% load, 100% load and 120%
load, all at 75C
Total losses at maximum tap Total losses at Minimum tap all
at 75C 4.7.2 Sound power level
--
..._
. , Standards
Date:
A utho2015-09-02
rized by: Head of Department
TITLE:
KP1/6C.1/13/TSP/10/001..02
Issue No.
SPECIFICATI ON FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
4.7.3
4.7.4
4.8
4.8.1.1
4.8.1.2
4.8.1.3
4.8.1.4
'
Doc. No.
Revision No. 1
Date of Issue
Page 36 of 55
Description
Indicate KVA & voltage ratings in columns on the right
SOkVA
No-load and Load Losses shall be submitted in the tender
Capitalization
Bushings and clearances
Open, outdoor & weatherproof bushings to IEC 60137
Bushings to be changed without opening transformer
HV bushings to be polymeric or porcelain.Specify
33kV Bushings complete with surge diverter bracket and
arcing horns
4.8.1. 5 LV bushings shall be two part,bottom in toughened epoxy
and top in porcelain, brown
4.8.1.6 Neutralbushing identicalto LV phase bushing
4.8.1.7 Spacing & clearances
4.8.1.8
Creepage distance of bushings: HV, LV, N
Coastal regions Creepage distance of bushings: HV, LV, N
4.8.1.9 Clamp type bushing terminals for aluminum conductor
Materials, size and drawings for terminal connectors
4.8.1.10 Marking and method of marking of terminals
4.8.1.11 Continuous current rating of each bushing
4.8.2
Clearances
4.8.2.1 External air clearances
4.8.2.1.1 Adequate to withstandimpulse withstand test voltages
4.8.2.1.2 Position of fittings & accessories not to interfere
with externalconnection to bushing terminals
4.8.2.1.3 Minimum externalclearances & creepage
LV, mm
Phase to phase
(cable box) Phase to earth
Creepage distance
Phase to phase
11kV, mm
(cable box) Phase to earth
Creepage distance
Phase to phase
33kV, mm
(open)
Phase to earth
Creepage distance
4.8.2.2
Internal clearances
Minimum radial clearance of LV coil and core,mm
Minimum radialclearance of LV coil and earth, mm
Minimum radial clearance between LV and HV, mm
Minimum electricalclearance between the surface of
the tank and tapping leads, mm
Minimum radial clearance between HV and HV
windings, mm
4.9
Insulation Levels (internal)
2015.09..02
BIDDER'S OFFER
100kVA 200kVA 315kVA
I
i
Signed:
Signed:
<:(.....
..
Date: 2015-09-02
Date: 2015-09-02
TITLE:
KP1/6C.1/13/TSP/10/001-02
5
Revision No.
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
Doc.No.
Issue No.
BIDDER'S OFFER
50kVA 100kVA 200kVA 31SkVA
Description
Indicate KVA & voltage ratings in columns on the right
(b)
4.12.1
Earthing Terminals: location & to have stainless
steelbolt, (c)
nut & washer and tinned copper terminal lug for
2
50mm
conductor
4.12.1
Separate Lifting lugs for core,top cover, conservator
& (d)
complete transformer
4.12.1
Off-circuit tap changer & location
(e)
4.12.1 (f) Tinned copper jumper size and materials
Signed:
@rl,-
Signed:
_.C""B
II
Date:
2015-09-02
v-
Date:2015-09-02
TITLE:
KP1/6C.1/13/TSP/10/001-02
5
Revision No.
Date of Issue
2015-09-02
SPECIFICATION FOR
Kenya Power
Clause
Number
4.12.1
(g)
4.12.1
Doc. No.
Issue No.
DISTRIBUTION TRANSFORMER
Part 2: Pole Mounted Three
Phase Oil Type Distribution
Transformer
Page 38 of 55
Description
BIDDER'S OFFER
SOkVA 100kVA 200kVA 315kVA
(h)
d-:TJA
Signed:
-Cb1=
Date: 2015-09-02
IC
;(::
TITLE:
Kenya Power
Clause
Number
5.5
5.6
6.
6.1
6.2
6.3
6.4
6.5
7.1
7.2
Other
details
required
with the
tender
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Part 2: Pole Mounted Three
Phase Oil Type Distribution
Transformer
Doc.No.
KP1/6C.1/13/TSP/10/001-02
Issue No.
Revision No.
Date of Issue
2015-09-02
Page 39 of 55
Description
Indicate KVA & voltage ratings in columns on the right
Complete test reports for approval before shipment
Inspection or test by KPLC during delivery before
acceptance to stores
Marking,Labeling & Packing
Packing: mounted & bolted on wooden base blocks
Dispatch fully assembled & oil filled
Assemble & package of items suitably marked
Permanent Rating & Diagram plate indelibly marked (by
etching, engraving or stamping)
Content of marking
Tender submitted with all technical documents
Successfulbidder to submit documents/details for approval
before manufacture
Weight of complete transformer, kg
Weight of tank, kg
Material of tank
Weight of oil, kg
Weight of core, kg
Weight of HV windings (without insulation), kg
Weight of LV windings (without insulation), kg
Weight of insulation, kg
Manufacturer's experience
Detailed list of all the required fittings and accessories
indicating type/model number, manufacturer and quantities
List catalogues,brochures and technical data submitted to
support offer
Deviations from tender specifications (indicate supporting
documents submitted)
50kVA
BIDDER'S OFFER
100kVA 200kVA 315kVA
'
I
.............................................................................................................
Manufacturer's Name,Signature, Stamp and Date
(<;;
-'
Date: 2015-09-02
Signed:
- '
II(
TITLE:
'l
Kenya Power
Doc.No.
Issue No.
KP116C.11131TSPI101001-02
Revision No.
Date of Issue
2015-09-02
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Part 2: Pole Mounted Three
Phase Oil Type
Distribution
Transformer
Page40 of 55
B) 33kV TRANSFORMERS
ANNEXA:
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR
OFFERED TRANSFORMER (to be filled and signed by the Manufacturer and submitted together
with relevant
copies of the Manufacturer's catalogues, brochures, drawings, technical data & calculations,
sales records for past five years, four customer reference letters, details of manufacturing
capacity, the manufacturer's experience, copies of complete type test reports and accreditation
certificate to ISOIIEC 17025 for the third party testing laboratory for tender evaluation, all in English
Language)
I'
Description
BIDDER'S OFFER
Indicate KVA & voltage ratings in columns on the right
50kVA 100kVA 200kVA
Name and address of the Manufacturer
Country of manufacture
Manufacturer's Letter of Authorization
Modelfrype Reference No. of the offered transformer
Drawni g Reference Number
Manufacturer's warranty and guarantee certificate
for the offered transformer
1.
Scope:
a) Design, manufacture, test, ship and deliver
ground mounted three phase distribution transformer
to KPLC store/site as per specification and terms of
contract.
b) Ensure adequacy of the design, good workmanship,
good engni eering practice and adherence to
standards, specifications and applicable
regulationsStandards
in the manufacture of the transformers
2
Applicable
3
Terms and Definitions
4.1.1
Operating Service Conditions:indicate altitude,
temperature range, humidity, pollution and isokeraunic
level)
4.1.2.1- System Characteristics
4.1.2.3
4.2
General Requirements
4.2.1
Outdoor, oiltype,ONAN and core type
4.2.2
Design Service Life
Two
winding,three phase integral unit
4.2. 3
Types of transformers offered
4.2.4
4.2.4.1
315kVA
Signed:
Date: 2015-09-02
,Y 2)_
Signed:
--CfJ
TITLE:
4.2.4.2
4.2.5
4.2.6
4.2.7
4.2.8
4.2.9
'
4.2.10
4.2.11
4.2.12
4.2.13
4.2.14
4.2.15
4.2.16
4.2.17a)
to g)
KP1/6C.1/13/TSP/10/001-02
5
Revision No.
Date of Issue
Page 41 of 55
2015-09-02
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
Doc.No.
Issue No.
Description
Indicate KVA & voltage ratings in columns on the right
Active parts submerged in oil and provision for oil
expansion
Free breathing type, conservator with cobalt free
dehydrating breather& oil gauge
Design to facilitate operation,inspection, maintenance
& repairs
Safety & Regulatory Requirements
No water pockets, rain water do not collect on top,
cover with 10mm overlap to conceal gasket
Corresponding parts to be interchangeable
Fittings & accessories secured from inside or have
openings that do not allow oil siphoning
Test certificates for transformer components and
materials - Attach for verification
All connections & contacts of ample section and
surface for required currents
Materials used do not lead to acidity in oil
State value of maximum noise level (BS EN 50464-1)
orNEMA TR1
Transportation to withstand 1g beyond gravitational
acceleration
Suitable for ground with mounting, steel channelunder
base
Drawings of offered transformer
Overall dimensions of offered transformer (length,
width & height) in mm
Design drawings for approval before manufacture
Overall dimensions of the transformer and relevant
electrical clearances. This shall include all
perspectives and respective:
(i)
Weight of oil,
(ii)
Weight of LV winding conductor
(iii)
Weight of HV winding conductor
(iv)
Core material,
(v)
Copper/aluminium winding materia,l
(vi)
Insulating materials and
(vii)
Steeltank/core clamp structure.
Core/coil/insulation dimensions, clearances (internal
and external) and stacking/coil winding sequence
detail.
Drawing of nameplate to scale.
Dimensionaldrawing of bushings, tap-changer and
;(::l.A
.,
--:J
.
"
v
BIDDER'S OFFER
50kVA 100kVA 200kVA
315kVA
<""::D.
.1 ..'
TITLE:
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Part
2:
Pole Mounted
Three
Phase Oil Type
Distribution
Transformer
Clause
Number
Description
Indicate KVA & voltage ratings in columns on the right
4.3.1
4. 3.2
clamps.
Legend for all technical engineering drawings with
manufacturer name, logo, model number,
revision/drawing number and key
Detailed drawing of arcing horns where applicable.
Detailed drawing of arcing horns where applicable.
All design drawings MUST BE stamped and signed by
the manufacturer's authorised personne.l
KVA, no-load voltage ratings and frequency
Top Oil
Temperature
Rise
4.3.3
4.3.4
4.3.5
4.3.6
4.4
4.4.1.1
4.4.1.2
Doc.No.
KP1/6C.1/13/TSP/10/001-02
Issue No.
2015-09-02
BIDDER'S OFFER
50kVA 100kVA 200kVA
31SkVA
Windings
Signed:
Date: 2015-09-02
cr - -
Signed:
Date:2015-09-02
..
TITLE:
KP1/6C.1/131TSP/10/001-02
Revision No.
Date of Issue
2015-09-02
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
4.4.1.3
Description
Indicate KVA & voltage ratings in columns on the right
Insulating material shall not soften, ooze, shrink
or collapse during service. The material shall be
non- catalytic & chemically inert in transformer oil
4.4.2
Primary windings
4.4.2.1 Secondary windings
4.4.2.2
Current
HVwinding
density,
LV winding
2
Almm
Material of
HVwinding
winding
LV winding
Conductor
HVwinding
area of
LV winding
winding
2
mm
Resistance
HVwinding
at 20C
LV winding
4.4.2.3
Characteristics of copper wire and aluminium wire
Standard of manufacture
Type designation or grade
Copper
Specific heat at 100 c (J/kg q
Density at 100 c (kg/m")
Resistivity at 100 c
(JJOm)
Standard of manufacture
Type designation or grade
Specific heat at 100 c (J/kg c)
Aluminium
Density at 100 c (kg/m")
Resistivity at 100 c (JJOm)
Characteristics of copper and aluminium foil/strip
Standard of manufacture
Type designation or grade
Ultimate tensile strength, N/mm
Copper
Density in 20uC,kg/dm"
Elongation,% , min
Maximum resistance at 20uC, Omm /m
4.4.2.4
Doc.No.
Issue No.
&
Page43 of 55
BIDDER'S OFFER
SOkVA
100kVA
200kVA
315kVA
Date: 2015-09-02
Signed:
.1.-
:1
TITLE:
Doc.No.
KP1/6C.1/13/TSP/10/001-
Issue No.
02
SPECIFICATION FOR
Kenya Power
Clause
Description
Number Indicate KVA & voltage ratings in columns on the right
Separation of windings for cooling and ease of repair
4.4.3.1
Insulation sleeves material
lnterlayer insulatoi n
material
4.4.3.2
Double layer insulation
Temperature class of insulation Standard
of manufacture Type
designation or grade
Apparent density,
Grammage
Crepe paper Conductivity of aqueous extract
Electric strength in oil
Machine direction
Tensile strength
Cross machine
direction
Standard of manufacture
Type designation or grade
Apparent density,
Presspaper Grammage
-Grade
Conductivity of aqueous extract
type
Electric strength in oil
Machine direction
Tensile strength
Cross machine
direction
Krapt paper/ Standard of manufacture
Celullosic
Type designation or grade
paper
Apparent density
Conductivity
Air permeability
Standard of manufacture
Radial
spacer
Type designation or grade
blocks
Electrical and mechanical properties
4.4.4
Connections
4.4.4.1 Windings, joints & connections braced/brazed?
4.4.4.2 Dryni g in vacuum & impregnating with hot oil
4.5
Tapping
4.5.1
Tapping range
4.5.2.
Tapping method and design
4.5.2.1
Standard of
manufacture
Tap changer (ratio tapType designation or
switch)
grade
Mode of operation
BIDDER'S OFFER
SOkVA 100kVA
200kVA
315kVA
Signed:
Date:2015-09-02
JAnt
-;a ,
Signed:
a:=CD
Date: 2015-09-02
TITLE:
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
Description
Indicate KVA & voltage ratings in columns an the right
Shank diameter
Height of ratio tapswitch
4.5.2.3 Gap between ratio tap-switch top to the inside of the
tank
4.5.2.4
Tap switch position number 1, orientation
4.6
Core and Flux Density
4.6.1
Core
Standard of manufacture of core material
4.6. 1.1 Type designation or Grade of core steel
Insulating material for CRGO to prevent corrosion
4.6.1.2 Thickness of each single lamination
Net core area, mm"'
Number ofturns on LV,per phase
Stack factor/Building factor
Weight of core, kg
Specific loss in watts/kg (at 1.6T flux density)
4.6.1.3 Static discharges & local heating
4.6.1.4 Assembled core free from distortion
4.6.1.5 Cooling for core
4.6.1.6
Movement of core during transportation or in service
4.6.1.7 Core clamping
4.6.1.8 Lifting lugs for core, winding and complete transformer.
Factor of safety at least 2.
4.6.1.9 Oil pockets & trapping of air
4.6.1.10 Insulation withstand of core to bolts and core to frame
4.6.2
Flux density
4.6.2.1 Effect of primary voltage variations on flux density
4.6.2.2
Maximum flux density
Lowest limit of flux density
4.6.2.
Allowable maximum flux density :in
3
4.6.2.4
4.6.2.5
4.7
4.7.1
Doc.No.
KP1/6C.1/13/TSP/10/001-02
Issue No.
Revision No.
Date of Issue
Page 45 of 55
2015-09-02
BIDDER'S OFFER
SOkVA 100kVA
200kVA
Short-circuit lmpendence,%
Resistance at 75C of HV Winding in ohms
(at normal & extreme taps)
Resistance at 75C of LV Winding in ohms
Minimum efficiency at 100% load (unity power
factor}, at 75C
Total losses (no-load+ load losses} at 100% load
CLJ.J
-
315kVA
Date: 2015-09-02
cQ ..d:c-
TITLE:
Kenya
KP1/6C.1/13fTSP/10/001-
Issue No.
SPECIFICATION FOR
Power
Clause
Number
Doc. No.
02
DISTRIBUTION TRANSFORMER
Part 2: Pole Mounted
Three Phase Oil Type
Distribution Transformer
Description
Indicate KVA & voltage ratings in columns on the right
Revision No. 1
Date of Issue 2015-09-02
Page46 of 55
BIDDER'S OFFER
50kVA 100kVA 200kVA
Signed:
liit;;J;_.
Signed:
cp
Date::ZOIS-09-0:Z
Date:2015-09-0:Z
TITLE:
4.8.2.2
4.9
4.10
4.10.1
4.10.2
4.10.3
4.10.4
4.10.5
4.10.6
4.10.7
4.10.8
4.11
4.11.1
4.11.2
4.11.3
4.11.4
DISTRIBUTION TRANSFORMER
Part 2:Pole Mounted Three
Phase Oil Type Distribution
Transformer
Description
Indicate KVA & voltage ratings in columns on the right
(cable box)
Phase to earth
Creepage distance
33kV, mm
Phase to phase
(open)
Phase to earth
Creepage distance
Internal clearances
Minimum radial clearance of LV coil and core, mm
Minimum radial clearance of LV coil and earth, mm
Minimum radial clearance between LV and HV, mm
Minimum electrical clearance between the surface of
the tank and tapping leads,mm
Minimum radial clearance between HV and HV
windings, mm
Insulation Levels (internal)
LV: Power frequency withstand voltage
11kV: Lightning impulse & power frequency withstand
voltages
33kV: Lightning impulse & power frequency withstand
voltages
Externalinsulation level and altitude correction
(indicate offered insulation and altitude correction
applied)
Transformer Tank & Tank Cover
Bolted top cover design
Minimum thickness of top cover, bottom and sides of
offered transformer respectively
Inside clearance
Pressure test of tank and test report during delivery
Lifting lugs and factor of safety
Steel radiators
Top cover design, non-accumulation of rain water,
gasket & non-standard bolts and nuts
4 non-standard bolts on top cover
Removable jumper of 25mm x 1.2mm tinned copper
&stainless steel bolt & nut
Paint Work
Method of cleaning before painting
Final colour of exterior surfaces and paint thickness
Cleaning and painting of interior of tank and other oil
filled chambers
Oegreasing & treatment of radiators with anti-rust
inhibitor
KP1/6C.1113fTSPI101001-02
5
Revision No.
Date of Issue
Page47 of 55
2015-09-02
SPECIFICATION FOR
Kenya Power
Clause
Number
Doc.No.
Issue No.
([
BIDDER'S OFFER
50kVA
100kVA
200kVA
315kVA
Date:2015-09-02
GO
==\..._
..
TITLE:
KP1/6C.1/13/TSP/10/001-02
5
Revision No.
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Doc. No.
Issue No.
Clause
Description
BIDDER'S OFFER
Number Indicate KVA & voltage ratings in columns on the right
50kVA 100kVA 200kVA
4.11. 5 Final colour of exterior of radiators & paint thickness
&painting method
4.12.1
Fittings and Accessories
4.12.1(a) Pressure at which pressure relief device operates
i
ii Pressure Relief Device & location
Oil LevelGauge & location
4.12.
1 (b)
Earthing Terminals: location & to have stainel ss
4.12.1
steel
(c)
bolt, nut & washer and t nned copper terminallug for
2
50mm
4.12.1
Separateconductor
Lifting lugs for core, top cover, conservator &
(d)
4.12.1
(e)
4.12.1 {f)
4.12.
1 (g)
4.12.
1 (h)
4.12.1(i
)
4.12.1
(j)
4.12.
1 (k)
4.12.1
(I)
4.12.2
4.12.3
4.12.4
4.13
4.14
4.15
4.15.1
4.15.2
4.15.3
315kVA
complete transformer
Off-circuit tap changer & location
Tinned copper jumper size and materials
Rat ng and diagram plate
Clamp connectors
Jacking Lags
Combined drain plug and sampling device
Mounting Brackets
dimensions
Surge arrester
mounting brackets
Universaltype
Galvanized to ISO 1461
Arcing horns
Features to deter oil vandalism
Detailed drawings
Transformer mounting rails at bottom
Transformer Oil- technical particulars shall be as per
KP1/6C.1/13/TSP/08/001
Surge Arresters technical particulars shall be as per
KP1/6C.1/13/TSP/11/32.
Quality Management System
Quality Assurance Plan to be based on ISO 9001:2008
Declaration of conformity to IEC 60076
Copy of ISO 9001:2008 certificate submitted
Monthly & annual production capacity
List of previous customers
Reference letters from at least four
previous customers
gned:
--
.::J '
Signed:
-=ce
Dnte: ZO15-09-0Z
'IS'
TITLE:
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Kenya Power
Clause
Number
5.
5.1
5.2
5.3
5.3.1
5.3.2
5.3.3
5.3.4
5.4
5.5
5.6
6.
6.1
6.2
6.3
6.4
6.5
7.1
7.2
Other
details
required
with the
tender
Description
Indicate KVA & voltage ratings in columns on the right
Tests and Inspection
Test Standard
Responsibility of testing transformer & manufacturer's
capability to carry out specified tests
Copies of type test reports to IEC 60076
Lightning impulse withstand test
Short circuit withstand test
Temperature rise test
Acceptance tests at manufacturers premises
Routine tests to IEC 60076
Type tests to IEC 60076
Temperature rise test
Lightning impulse withstand test
No-load loss and current at:
I 90% rated voltage
I 110% rated voltage
Additionaltests (sample test)
Sampling as per IEC 60410
Contact details for testing authority
Complete test reports for approvalbefore shipment
Inspection or test by KPLC during delivery before
acceptance to stores
Marking, Labeling & Packing
Packing:mounted & bolted on wooden base blocks
Dispatch fully assembled & oil filled
Assemble & package of items suitably marked
Permanent Rating & Diagram plate indelibly marked
(by
etching,
engraving
or
stamping)
Content of marking
Tender submitted with all technical documents
Doc.No.
KP116C.1/13/TSP/101001-02
Issue No.
Revision No.
Date of Issue
2015-09-02
Page49 of 55
BIDDER'S OFFER
SOkVA 100kVA 200kVA
315kVA
II
Signed:
Signed:
Date:2015-09-02
<:I
Date:2015-09-02
.1
TITLE:
Kenya
Power
SPECIFICATION FOR
DISTRIBUTION TRANSFORMER
Part 2: Pole Mounted Three
Phase Oil Type Distribution
Transformer
Clause
Number
Description
Indicate KVA & voltage ratings in columns on the right
Quantities
List catalogues, brochures and technical
data submitted to support offer
Deviations from tender specifications (indicate
support ng documents submitted)
Doc.No.
KP1/6C.1/13/TSP/10/001-02
Issue No.
Revision No.
Date of Issue
2015-09-02
Page 50 of 55
BIDDER'S OFFER
50kVA 100kVA 200kVA
315kVA
.4, ...