PREVENTIVE MAINTENANCE ROUTINE - EQUIPMENT TEST LIST

Site ID:
Region:
#

Z34012
East

Equipment
District:

Network
Element

NOC
Center

Maintenance Task

BTS3900L

MNOC

Record the temperature


read on the thermometer.

BTS3900L

MNOC

Record the humidity read on


the humidiometer.

MNOC

Check whether the daily


lighting and emergency
lighting systems are
operational.

MNOC

Check whether the air


conditioner works properly.

3
BTS3900L

4
BTS3900L

BTS3900L

MNOC

Check whether the disaster


prevention devices,
equipment protection
devices, and fire fighting
devices are in good
condition.

BTS3900L
Jubail

Engineer
Start Time

Muhammad Ali
10:35

Date
End Time

Frequency
Vendor's
Recommend.

Frequency
STC

Required Result

On Site or
Remote Test

Time
(minutes)

PMR StatusPass/Fail

Quarterly

Quarterly

5C to 45C

OnSite

23C

Quarterly

Quarterly

5% RH to 85% RH

OnSite

48%

Quarterly

Quarterly

make sure it is OK

OnSite

OK

Quarterly

Quarterly

OnSite

OK

Quarterly

Quarterly

OnSite

NOK

make sure its working


normally.

The carbon dioxide


extinguisher or dry
powder fire
extinguisheris installed
in the
equipment room. In
addition, the pressure
and period of validity of
the extinguisher meet
the requirement. No rat,
ant, or insect exists in
the equipment room.

5/11/2016
12:39
Comments

Fire Control Penal not


active

BTS3900L

MNOC

Check whether the disaster


prevention devices,
equipment protection
devices, and fire fighting
devices are in good
condition.

Quarterly

BTS3900L

MNOC

BTS3900L

MNOC

Check the connections of


power cables.

BTS3900L

MNOC

Measure the voltage of the


power supply by using a
multimeter.

BTS3900L

MNOC

Quarterly

Check whether the cabinet,


device case, inside of the
device, desktop, floor, door,
and window are clean.

The carbon dioxide


extinguisher or dry
powder fire
extinguisheris installed
in the
equipment room. In
addition, the pressure
and period of validity of
the extinguisher meet
the requirement. No rat,
ant, or insect exists in
the equipment room.

Check whether the PGND


cables and grounding bars
are connected properly.

OnSite

10

OK

OnSite

10

OnSite

10

-53.7

OnSite

10

NOK

All the devices in the


equipment room are
neat and clean.

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

The power cables are


not aging, and there is
no corrosion on
theconnection points.

The voltage of the


power supply is within
the specified voltage
range.

The connection points


of PGND are safe and
secure, with no
corrosion on them. The
grounding bards are
not corroded, with anticorrosive materials
properly applied.

Grounding Busbar & Cables


missing

10

BTS3900L

MNOC

Check whether the PGND


cables and grounding bars
are connected properly.

BTS3900L

MNOC

Measure the earth


resistance by using an
electric earth resistance
tester and keep a record.

11

12

BTS3900L

MNOC

Check the fans.

BTS3900L

MNOC

If the air filter is dusty, clean


it

MNOC

Check whether the


appearance of the cabinet is
impaired and the mark of
the cabinet is legible.

MNOC

Check whether the lock


works properly and the door
can be opened and
closed freely.

13
BTS3900L

14
BTS3900L

The connection points


of PGND are safe and
secure, with no
corrosion on them. The
grounding bards are
not corroded, with anticorrosive materials
properly applied.

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

Quarterly

The grounding
resistance of the
cabinet is smaller than
10 ohms.

The fans work properly


without making
abnormal sounds such
as the sound of blades
bumping the cabinet.

make sure it is clean

OnSite

10

OnSite

OK

OnSite

Cleaned

OnSite

OnSite

make sure it is
complete

Quarterly

Quarterly
make sure the door is
OK and safe

NOK

Shelter lock missing

15

Quarterly

Quarterly

The appearance of the


cabinet is clean and the
inside of the cabinet is
not dusty.

OnSite

10

OnSite

10

clean

MNOC

Check whether the cabinet


is clean

Quarterly

Quarterly

BTS3900L

MNOC

Use one of the following


methods:
Use the ESD wrist strap
tester.
Measure the
earthresistance by using the
multimeter.

17

BTS3900L

MNOC

Check antennas support

Quarterly

Quarterly

Antenna Support must


be Tight

OnSite

10

OK

18

BTS3900L

MNOC

Check Connector Earthing

Quarterly

Quarterly

All connectors must be


Earthed

OnSite

10

GND missind

19

BTS3900L

MNOC

Check Feeders Tighting

Quarterly

Quarterly

Feeders clamps must


be tight

OnSite

10

OK

20

BTS3900L

MNOC

Check Connectors Sealing

Quarterly

Quarterly

All Connectors must be


sealed

OnSite

10

OK

21

BTS3900L

MNOC

Check Labels

Quarterly

Quarterly

All labels must be


pasted

OnSite

10

OK

22

BTS3900L

MNOC

Check Cable Tray

Quarterly

Quarterly

Check cable tray

OnSite

10

OK

23

BTS3900L

MNOC

Check Cable Ladders

Quarterly

Quarterly

Cable ladders must be


ok.

OnSite

OK

BTS3900L

16

l If you use the ESD


wrist strap tester, it
indicates GOOD. l If
you use the multimeter,
the earth resistance of
the ESD wrist strap
ranges within 0.75
megaohms and 10
megaohms.

TT

TT Status