Professional Documents
Culture Documents
Six Week Industrial Training at 66 KV Sub
Six Week Industrial Training at 66 KV Sub
TRAINING
REPORT
AT
66 KV SUB-STATION TANDA
BADHA
SUBMITED TO:
ELECTRICAL DEPARTMENT
FATEHGARH SAHIB
66 KV SUBSTATION
NAME OF 66KV SUB STATION = TANDA
BADHA
NAME OF S/D = SSE 66KV S/S BHADSON
NAME OF DIVISION = P&M KHANNA
NAME OF CIRCLE = P&M LUDHIANA
NO OF POWER T/F = 2
CAPACITY OF POWER T/F = T1
20
MVA
CAPACITY OF POWER T/F = T1
20
MVA
NO OF 66 KV LINE (IN & OUT CKT) =
1No. IN CKT, 1 No. OUTGOING CKT.
INCOMING LINE(MOTHER S/S) = 220KV
S/S AMLOH
OUTGOING LINE= 66KV S/S MALLEHWAL
INTRODUCTION
Normally large power generating stations are built far away from
the load centres. There are a number of transformations and
switching stations built between generating stations and the
ultimate consumers. These are generally known as substations. A
typical substation may include the following equipments:
transformer, circuit breaker, disconnecting switches, station buses
and insulators, reactors, capacitors, current and potential
transformers, grounding system, lightning arrestors and spark
gaps, wave traps protective relays, station batteries, etc.
Types of substations
A substation or switching functions as a connection and switching
points for transmission lines, sub transmission feeders, generating
units, and transformers. Depending upon the purpose, the
substations may be classified into five categories:
1. Generating or step-up substations: Normally the generating
voltages are limited and need to be stepped up to the
transmission voltage so that large amount of power can be
transmitted economically over long. Each generating unit is
connected to generating transformers to increase the
secondary voltage up to transmission voltages levels.
the other can still have the current and the supply will not stop.
The two lines in the bus are separated by a little distance by a
conductor having a connector between them. This is so that one
can work at a time and the other works only if the first is having
any fault.
A bus bar in electrical power distribution refers to thick strips of
copper or aluminum that conduct electricity within a
switchboard, distribution board, substation, or other electrical
apparatus. The size of the bus bar is important in determining the
maximum amount of current that can be safely carried. Bus bars
are typically either flat strips or hollow tubes as these shapes
allow heat to dissipate more efficiently due to their high surface
area to cross sectional area ratio. The skin effect makes 50-60 Hz
AC bus bars more than about 8 mm (1/3 in) thick inefficient, so
hollow or flat shapes are prevalent in higher current applications.
A hollow section has higher stiffness than a solid rod of equivalent
current carrying capacity, which allows a greater span between
bus bar supports in outdoor switchyards. A bus bar may either be
supported on insulators or else insulation may completely
surround it. Bus bars are protected from accidental contact either
by a metal enclosure or by elevation out of normal reach.
Neutral bus bars may also be insulated. Earth bus bars are
typically bolted directly onto any metal chassis of their enclosure.
Bus bars may be enclosed in a metal housing, in the form of bus
duct or bus way, segregated-phase bus, or isolated-phase bus.
ISOLATER
It is device which works as controlling switch which can operate
whenever fault is occurred b/w mother. Station and receiving end.
It also behaves as a safety device .When we isolate the main line.
We earth the line to make it safe for working
The use of this isolator is to protect the transformer and the other
instrument in the line. The isolator isolates the extra voltage to the
ground and thus any extra voltage cannot enter the line. Thus an
isolator is used after the bus also for protection.
Lightening Arrester
Lightening arrestors are the instrument that are used in the
incoming feeders so that to prevent the high voltage entering the
main station. This high voltage is very dangerous to the
instruments used in the substation. Even the instruments are very
costly, so to prevent any damage lightening arrestors are used.
The lightening arrestors do not let the lightening to fall on the
station. If some lightening occurs the arrestors pull the lightening
and ground it to the earth. In any substation the main important
is of protection which is firstly done by these lightening arrestors.
The lightening arrestors are grounded to the earth so that it can
pull the lightening to the ground. The lightening arrestor works
with an angle of 30 to 45 making a cone.
Instrument Transformer
Instrument transformers are used to step-down the current or
voltage to measurable values. They provide standardized, useable
levels of current or voltage in a variety of power monitoring and
measurement applications. Both current and voltage instrument
transformers are designed to have predictable characteristics on
overloads. Proper operation of over-current protection relays
requires that current transformers provide a predictable
transformation ratio even during a short circuit.
These are further classified into two types which are discussed
below.
Current Transformer
Potential Transformer
SF6 Breaker
Transformer
Circuit Breaker
The circuit breakers are used to break the circuit if any fault
occurs in any of the instrument. These circuit breaker breaks for
a fault which can damage other instrument in the station. For any
unwanted fault over the station we need to break the line current.
This is only done automatically by the circuit breaker.
Types: Oil circuit breaker :- A high voltage circuit breaker in which
the arc is drawn in oil to dissipate the heat and extinguish
the arc; the intense heat of the arc decomposes the oil,
generating a gas whose high pressure produce a flow of fresh
fluid through the arc that furnishes the necessary insulation
to prevent a re-strike the arc.
Vacuum circuit breaker: - A vacuum circuit breaker is such
kind of circuit breaker where the arc quenching takes place
in vacuum. The technology is suitable for mainly medium
voltage application. For higher voltage vacuum technology
has been developed but not commercially viable. The
Protective Relaying
Protective relays are used to detect defective lines or apparatus
and to initiate the operation of circuit interrupting devices to
CAPACITOR BANK
DC BATTERIES
THANKS
BY
GURINDERDEEP SINGH
BHANDOHAL
Roll No. 1302277