Professional Documents
Culture Documents
Substation Insulation Coordination Studies-Sparacino
Substation Insulation Coordination Studies-Sparacino
Substation Insulation Coordination Studies-Sparacino
TheSelectionofInsulationStrength
March25,2014
AdamSparacino
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
DefinitionofInsulationCoordination1
Insulation Coordination (IEEE)
The selection of insulation strength consistent with expected
overvoltages to obtain an acceptable risk of failure.
The procedure for insulation coordination consists of (a)
determination of the voltage stresses and (b) selection of the
insulation strength to achieve the desired probability of failure.
The voltage stresses can be reduced by the application of surge
protective devices, switching device insertion resistors and controlled
closing, shield wires, improved grounding, etc.
FourBasicConsiderations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
FourBasicConsiderations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
DefinitionofOvervoltages
Overvoltage
Abnormal voltage between two points of a system that is greater than
the highest value appearing between the same two points under
normal service conditions.2
(2) IEEE Std C62.221991 IEEE Guide for the Application of MetalOxide Surge Arresters for AlternatingCurrent
Systems, 1991.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
VocabularyofVoltage
PeaklinegroundVoltage
RMSVoltagelineground=(Vpeak/2)
PeakVoltagelineground=VLL_rms2/3
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
IllustrationofOvervoltages
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
FourBasicConsiderations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
ElectricalInsulation
Insulation can be expressed as a dielectric with a function to
preserve the electrical integrity of the system.
The insulation can be internal (solid, liquid, or gaseous), which is
protected from the effects of atmospheric conditions (e.g.,
transformer windings, cables, gasinsulated substations, oil circuit
breakers, etc.).
The insulation can be external (in air), which is exposed to
atmospheric conditions (e.g., bushings, bus support insulators,
disconnect switches, line insulators, air itself [tower windows, phase
spacing], etc.).
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
InsulationStrength
TypicalVoltTimeCurveforInsulationWithstand
StrengthforLiquidFilledTransformers
Source: IEEE Std 62.22-1997, IEEE Guide for the Application of Metal-Oxide Surge Arresters for AC Systems
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
10
InsulationStrength
Example for Transformers Windings
Normal system operating voltage
345 kVLL_RMS (1.00 p.u.)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
11
FrequencyofDifferentEvents
10-20 minutes
seconds
Power
Frequency
milliseconds
microseconds
Transients
& Surges
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
12
FourBasicConsiderations
Understanding Insulation Stresses
Duty and Magnitude of applied voltage
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
13
PotentialOvervoltageMitigation
1. Surge Arresters
2. PreInsertion Resistors/Inductors
3. SynchronousClose/Open Control
4. Surge Capacitors
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
14
FourBasicConsiderations
Understanding Insulation Stresses
Duty and Magnitude of applied voltage
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
15
InsulationCoordinationProcess
1. Specify the equipment insulation strength, the BIL and BSL of
all equipment.
2. Specify the phaseground and phasephase clearances that
should be considered.
3. Specify the need for, location, rating, and number of surge
arresters.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
16
InsulationCoordinationStudies
1. Very Fast Transients (VFT) Analysis (nanoseconds time frame)
17
InsulationCoordinationStudies(cont.)
4. Temporary Overvoltage Analysis (seconds time frame)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
18
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
LIGHTNINGSURGEANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
19
500 kV LINE
BML00
BLU00
BML01
BLU01
la = 30.70
lb = 25.66
lc = 21.76
la = 23.47
lb = 22.56
lc = 21.64
500 kV LINE
la = 21.19
lb = 20.74
lc = 23.64
la = 23.47
lb = 22.56
lc = 20.64
WEST500kVBUS
GWB06
la,b,c = 8.323
la,b,c = 19.59
G752W
G952W
CB
CB
G752E
la = 26.42
lb = 25.51
lc = 24.59
la = 9.518
lb = 8.603
lc = 7.689
G762W
G962W
CB
CB
G952E
CB
G762E
G772W
la = 12.47
lb = 11.55
lc = 10.64
EAST500kVBUS
CB
CB
G772E
G872E
GML00
la,b,c = 8.323
GEB06
la = 70.62
lb = 76.69
lc = 82.77
G972W
G872W
G4A00
DUMMYBUS(POSITIONFOR
FUTUREBREAKER)
XFMR
la,b,c = 5.634
CB
CB
G962E
la,b,c = 19.59
G3A00
la,b,c = 8.323
la = 26.42
lb = 25.51
lc = 24.59
G972E
GLU00
la,b,c = 8.323
la,b,c = 5.634
la = 70.15
lb = 76.25
lc = 82.30
B3A01
B4A01
B3A00
B4A00
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
XFMR
20
ExampleforLine/XFMRTermination
500 kV Line
Line Trap1
To Transformer
Surge
Arrester
Gas-toAir
Bushing
CCVT
To GIS
Bay #6
Gas-to-Air
Bushing
550 kV GIS
350 MCM
Ground Lead
(38)
Surge
Arrester
Notes
To GIS
Bay
550 kV GIS
350 MCM
Ground
Lead (38)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
21
DetailedAnalysis
ScreeningAnalysis
ApproachforEvaluationtheInsulationCoordinationof
the550kVGasInsulatedSubstation
Step 1:
Step 2:
Step 3:
various
For the detailed analysis, specific details of the transmission lines such as conductor
characteristics, shielding design, ground resistivity, keraunic level, etc. are considered to
determine a reasonable upper bounds to place on the lightning surge impinging on the
substation.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
22
LightningSurgeIncomingFrom500kVLine
PhasetoGroundVoltageofIncomingLightningSurge
MLFULL_halfSRC>MLSRCA(Type 1)
4000
Voltage (kV)
3000
2000
Lightning surge impinges
substation from 500 kV Line.
1000
Lightning surge initiated at
1.0 microseconds.
0
0
10
Time (us)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
15
20
23
LightningSurgeIncomingFrom500kVLine
HighestPhasetoGroundVoltageObservedinGIS
MLFULLB>G752WB(Type 1)
2000
Voltage (kV)
1500
Protective Margin = 40%
([1550/1109 1] x 100%)
Peak overvoltage =
1109 kV.
1000
500
0
0
10
Time (us)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
15
20
24
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
TRANSMISSIONLINESWITCHINGANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
25
TransmissionLineSwitchingAnalysis
PotentialEquipmentConcerns
ExcessiveTransientOvervoltagesand
thePossibilityofaFlashoverDuring
EnergizingorReClosing
OvervoltagesExceedingGuidelines
UsedtoDevelopLineClearances
Transmission line is energized
(normal energizing or re-closing).
Applicable Criteria
BasicSwitchingImpulseLevel(BSL)
ProbabilityofFlashovers
PotentialMitigationTechniques
SynchronousCloseControl
PreInsertionResistors/Inductors
SurgeArresters
ShuntReactors
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
26
StatisticalSwitchingMethodology
Source-Side Voltage
cycle window
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
27
ElectroGeometricLineModel
Example345kVTransmissionLine
14.5
ShieldWire:
Alumoweld7#8
Outsidediameter=0.385
RDC=2.40Ohm/mi
14.5
78
(63atmidpoint)
B
27
27
54
(24atmidpoint)
Center
Line
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
PhaseConductor:
ACSRLapwing
2/cBundle18spacing
Outsidediameter=1.504
RDC=0.059Ohm/mi
Thick/Diam=0.375
LineLength(total)=85mi
Untransposed
Groundresistivity=37Ohmm
28
StatisticalSwitchingOvervoltageStrengthCharacteristics
andSOVdensitiesoftheline
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
29
StatisticalDistr.OfOvervoltagesAlong500kVLinewith
NOSurgeArresters
StatisticalDistributionofOvervoltagesAlongLine
110%
Statistical
distributionbasedon
thecasepeak
methodfromIEEE
Std1313.21999.
ProbabilitytoExceedOvervoltage(%)
100%
Estimatedinsulation
withstandforthe
transmissionline:CFO=3.53
p.u.,f/CFO =5%.
90%
80%
70%
SendingEnd
60%
1/4Point
98%oftheovervoltagesalong
thelineare2.62p.u.(1070
kV).
50%
40%
1/2Point
3/4Point
Highestovervoltageatthe
remoteendoftheline=2.75
p.u.(1123kV).
30%
20%
RemoteEnd
ExampleCFO
E2isthevalueinwhichthe
overvoltagesexceed2%ofthe
switchingoperations.
10%
0%
1.00
1.50
2.00
2.50
3.00
3.50
4.00
PeakOvervoltage(PerUnitona500kVBase)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
30
StatisticalDistr.OfOvervoltagesAlong500kVLinewith
LineEndSurgeArresters
StatisticalDistributionofOvervoltagesAlongLine
110%
ProbabilitytoExceedOvervoltage(%)
100%
Estimatedinsulation
withstandforthe
transmissionline:CFO=3.53
p.u.,f/CFO =5%.
90%
80%
Statistical
distributionbasedon
thecasepeak
methodfromIEEE
Std1313.21999.
70%
SendingEnd
60%
1/4Point
98%oftheovervoltagesalong
thelineare2.16p.u.(882
kV).
50%
1/2Point
3/4Point
40%
RemoteEnd
30%
ExampleCFO
20%
Highestovervoltagealongthe
line=2.21p.u.(902kV).
E2isthevalueinwhichthe
overvoltagesexceed2%ofthe
switchingoperations.
10%
0%
1.00
1.50
2.00
2.50
3.00
3.50
4.00
PeakOvervoltage(PerUnitona500kVBase)
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
31
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
SHUNTCAPACITORSWITCHINGANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
32
ShuntCapacitorSwitchingAnalysis
PotentialEquipmentConcerns
ContactWearfromExcessiveInrush
CurrentDuty
ExcessiveTransientOvervoltages
InducedVoltagesandCurrentsin
ControlCircuits
StepandTouchPotentialsDuring
Switching
ApplicableCriteria
ANSI/IEEEInrushCurrentLimits
BasicSwitchingImpulseLevel(BSL)
BreakerCapabilityBeyondStandards
IEEEStd 80forgrounding
PotentialMitigationTechniques
CurrentLimitingReactors
SynchronousCloseControl
PreInsertionResistors/Inductors
SurgeArresters
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
33
CapacitorBankReStrike
DuringDeEnergization
CurrentThroughSwitchingDevice
Highfrequency
currentis
interrupted
Firstrestrike
occursand
currentisre
established
Secondrestrikeoccursand
currentisreestablished
VoltageonEachSideofSwitchingDevice
Peakovervoltage
from1st restrike
Voltageonsystem
sideofswitching
device
Currentis
interrupted
Voltageoncapacitor
banksideof
switchingdevice(DC
trappedcharge)
Peakovervoltage
from2nd restrike
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
34
VoltageMagnification
When a shunt capacitor bank is energized with a nearby
capacitor at a lower voltage, the potential for voltage
magnification may exist when the following condition is true:
1
Furthermore,whenC1>>C2,andL1<<L2 theconditioncanbe
exaggerated
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
35
VoltageMagnification(Cont.)
Example 4.39 p.u. overvoltage at LV
bus when capacitor bank is switched.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
36
EXAMPLEAPPLICATION
STUDYFORINSULATIONCOORDINATION
SHUNTREACTORSWITCHINGANALYSIS
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
37
ShuntReactorSwitchingAnalysis
PotentialEquipmentConcerns
ExcessiveInrushCurrentsfrom
Energizing
TransientandTemporaryOvervoltages
fromResonanceConditions
GenerationofHarmonics
ResonancefromParallelLines
ApplicableCriteria
EquipmentInsulationLevels
VoltageSag/DipCriteria
HarmonicDistortion
PotentialMitigationTechniques
SynchronousCloseControl
SurgeArresters
AppropriateRelaySettings
OperationalLimitations
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
38
ResonanceOvervoltages
345kVSubstation
345kVSubstation
VoltageMeasuredonEnergizedLine
Lineinservice
(breakersclosed
atbothends)
Lineoutofservice
(breakersopenat
bothends)
345kVSubstation
345kVSubstation
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
39
ResonanceOvervoltages
Peak overvoltage
= 2.94 p.u.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
40
Summary
Insulation Coordination is the selection of insulation strength.
Determine maximum insulation stress.
Determine the minimum insulation strength with margin taking into
account stress reducers (surge arresters, preinsertion resistors,
synchronous close control, etc.) that can withstand the maximum
stress.
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
41
THANKYOUFORYOUATTENTION
MITSUBISHIELECTRICPOWERPRODUCTS,INC.
POWERSYSTEMENGINEERINGSERVICES
42