Main data sheet for Transformer

Client

M/s NTDC

Offer No.

Type of transformer

#REF!

Applicable standard & tolerances

IEC 60076

Service area
General data

Outdoor
Altitude: 1000 m max. above sea level
Max. Ambient Temperature: 50 C

Service condition
Insulating oil

IEC 60296

Rated power (ONAN/ONAF)


Phases / Rated frequency
Rated voltage
Ratings

(MVA)

10 / 13

( / Hz)

3 / 50

HV side

(kV)

66

LV side

(kV)

11.5

(%)

-10% to +10% in 23 steps

Tapping range of HV side

Vacuum type On-load tap-changer


(make: MR-Germany)

Tap changing method


Connection symbol

Dyn11

Cooling method

ONAN / ONAF

Insulation level (HV / LV)

LI 325 AC 140 / LI 110 AC 38

Top Oil

Characteristics

Masses
Dimensions

Accessories

Rev. No.

50

Temperature Rise
Winding Average
(K)
Hotspot
Guarantees at

55
68

10.0 MVA, at 75 C main tapping, rated voltage are:

No-load loss

(kW)

9.0

Load loss

(kW)

43.5

Impedance voltage

(%)

9.00

Oil

(kg)

8,700

Total

(kg)

33,000

Length x Width x Height

(mm)

4000 x 2900 x 4500

Oil drain / fill valves

Handholes

Oil sampling valves

Earthing terminals

Oil dehydration valves

Name Plate

Radiators

Double float buchholz relay

Butterfly valves

Oil level indicator with contacts

Conservator

Pressure relief device with contacts

Silicagel breather

Winding temperature indicator with contacts

Lifting lugs

Oil temperature indicator with contacts

Jacking pad

Outdoor & auxiliary panels

Roller wheels

LV bushings in cable box

Q16-XXX

Date

11-Jul-16

Signature