S.

NO

ALARM DETAILS

ALARM CODE

VERIFICATION

To check the alarm Switch off the


1

Rectifier Mains Failure

7401

mains MCB from PIU.

To remove alarm turn on the


mains MCB.
To check the alarm firstly remove

Rectifier Module Failure

7402

High Room Temperature

7411

the rectifier from the SMPS or switch


off the MCB of rectifier from SMPS.
To remove alarm switch on the
MCB of the rectifier module or insert
the new rectifier module.
To check the alarm rub thermisterin
b/w hands .
To remove alarm switch on the AC &
set AC temp on desired value.

To check the alarm open the door.


6

Shelter Door Open

7410

Smoke Detected in Shelter

7412

Air Condition Failed

7409

Low Fuel

7407

10

DG on Load

7405

12

DG on no Load

7408

To remove alarm close and seal


proper the door.
To check the alarm create a small
fire by paper or jute.
To remove alarm Reset smoke & fire
sensor and clean the smoke from the
sensor.
To check the alarm switch off the
ACs.
To remove alarm switch
on/repair/replace ACs.
To check the alarm see if the desired
fuel level of DG is set on 40% or not.

To remove alarm fill the tank of DG.


To check the alarm switch off the
mains MCB from PIU & switch on the
DG (if it is not in auto mode).
To remove alarm switch on the
mains MCB (if mains is available).
To check the alarm switch off the
mains mcb from PIU and check dg set
is not in auto mode or remove the
connection b/w PIU and Self.
To remove alarm start DG in manual
mode.

STATUS