Easun Reyrolle Limited, India: INPUT DATA For CSC 101 / CSC 162 Relays

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 10

Easun Reyrolle Limited, India

INPUT DATA for CSC 101 / CSC 162 Relays:


1 Voltage Level (KV)
2 PT Ratio
3 CT Ratio
4 Positive seq. Resistance(R1) / Km
5 Positive seq. Reactance(X1) / Km
6 Zero seq. Resistance(R0) / Km
7 Zero seq. Resistance(X0) / Km
8 Line Length (Km)
9 Maximum Load Current (Primary in A)
10 Operating Power Factor
11 Zone 1 Settings required in %
12 Zone 2 Settings required in %
13 Zone 3 Settings required in %
14 Zone 4 Settings required in %
15 Zero Seq. Mutual Reactance (Xm0)

Fill the following Data


132.0000
1200
400.0000
0.1540
0.3870
0.3030
1.4096
7.1000
400.0000
0.8500
80.0000
150.0000
400.0000
25.0000
0.0000

SETTINGS TO BE ADOPTED
(CT Secondary Rated : 1A, PT Secondary : 110V P-P)
1 KV, CTR, LL

( As It Is)

2 Kr

0.323

3 Kx

0.881

4 Km

0.000

5 R_Line

0.364

6 X_Line

0.916

7 R1_PE

0.733

8 X1_PE

0.733

9 R2_PE

1.921

10 X2_PE

1.374

11 R3_PE

5.121

12 X3_PE

3.664

13 R4_PE

0.320

14 X4_PE

0.229

15 R1_PP

0.733

16 X1_PP

0.733

17 R2_PP

1.921

18 X2_PP

1.374

19 R3_PP

5.121

20 X3_PP

3.664

21 R4_PP

0.320

22 X4_PP

0.229

23 Max Load Resistance Observed on Ohms

31.807

Note : Select the Resitance Value of the Z3 or Z4 such


that it should be less than the Max. Load Resistance
Calculated
Created By:
G.Mahendiran
Deputy Manager - Product Management
Easun Reyrolle Limited
Hosur, India - 635 126
Moile : +91 99524 25301.
Email : mahendiran@easunreyrolle.com
All Rights Reserved to M/s. Eaun Reyrolle Limited., Any
form of Reproduction of this copy is prohibited.

EASUN REYROLLE LIMITED, INDIA

INPUT DATA for CSC 101 / CSC 162 Relays:

INPUT

Voltage Level (KV)

132

PT Ratio

1200

CT Ratio

400

Positive seq. Resistance(R1) / Km

0.154

Positive seq. Reactance(X1) / Km

0.387

Zero seq. Resistance(R0) / Km

0.303

Zero seq. Resistance(X0) / Km

1.4096

Line Length (Km)

7.1

Maximum Load Current (Primary in A)

400

10

Power Factor

0.85

11

Zone 1 Settings required in %

80

12

Zone 2 Settings required in %

150

13

Zone 3 Settings required in %

400

14

Zone 4 Settings required in %

25

15

Zero Seq. Mutual Reactance (Xm0)

Zone 2 Ph-E Fault:


R2_pe

0.5467

X2_pe

1.37385

max(x2_pe/2,25/LZ+R_line)

8.6978

R2_pe derived (as per Manual)

0.5467

X2_pe Rect

0.686925

Min(8*X2_Rect, R2_pe/4)

0.136675

R2_pe Rect

1.37385

R2_pe to be Set

1.92055

Zone 2 Ph-Ph Fault:


R2_pp

0.5467

X2_pp

1.37385

max(x2_pp/2,15/LZ+R_line)
R2_pp derived (as per Manual)

5.3644666667
0.5467

X2_pp Rect

0.686925

Min(8*X2_Rect, R2_pp/4)

0.136675

R2_pp Rect

1.37385

R2_pp to be Set

1.92055

Zone 4 Ph-E Fault:


R4_pe

0.0911166667

X4_pe

0.228975

max(x4_pe/2,25/LZ+R_line)
R4_pe derived (as per Manual)
X4_pe Rect
Min(8*X4_Rect, R4_pe/4)
R4_pe Rect
R4_pe to be Set

8.6978
0.0911166667
0.1144875
0.0227791667
0.228975
0.3200916667

Zone 4 Ph-Ph Fault:


R4_pp

0.0911166667

X4_pp

0.228975

max(x4_pp/2,15/LZ+R_line)

5.3644666667

R4_pp derived (as per Manual)

0.0911166667

X4_pp Rect
Min(8*X4_Rect, R4_pp/4)
R4_pp Rect
R4_pp to beSet

0.1144875
0.0227791667
0.228975
0.3200916667

ED, INDIA

COMMON PARAMETERS:
CTR / PTR

0.3333333333

Kr

0.3225108225

Kx

0.8807924203

km
R_Line
X_line

0.3644666667
0.9159

Zone 1 Ph-E Fault:


R1_pe

0.2915733333

X1_pe

0.73272

max(x1_pe/2,25/LZ+R_line)
R1_pe derived (as per Manual)
X1_pe Rect
Min(8*X1_Rect, R1_pe/4)

8.6978
0.2915733333
0.36636
0.0728933333

R1_pe Rect

0.73272

R1_pe to be Set

0.73272

Zone 1 Ph-Ph Fault:


R1_pp

0.2915733333

X1_pp

0.73272

max(x1_pp/2,15/LZ+R_line)

5.3644666667

R1_pp derived (as per Manual)

0.2915733333

X1_pp Rect

0.36636

Min(8*X1_Rect, R1_pp/4)

0.0728933333

R1_pp Rect

0.73272

R1_pp to be Set

0.73272

Zone 3 Ph-E Fault:


R3_pe

1.4578666667

X3_pe

3.6636

max(x3_pe/2,25/LZ+R_line)

8.6978

R3_pe derived (as per Manual)


X3_pe Rect
Min(8*X3_Rect, R3_pe/4)
R3_pe Rect
R3_pe to be Set

1.4578666667
1.8318
0.3644666667
3.6636
5.1214666667

Zone 3 Ph-Ph Fault:


R3_pp

1.4578666667

X3_pp

3.6636

max(x3_pp/2,15/LZ+R_line)

5.3644666667

R3_pp derived (as per Manual)

1.4578666667

X3_pp Rect
Min(8*X3_Rect, R3_pp/4)
R3_pp Rect
R3_pp to be Set

1.8318
0.3644666667
3.6636
5.1214666667

Maximum Load Resistance:


Theta (DEGREES(ACOS(PF)))

31.7883306171

Factor = (K re * 0.9) / (K rel * K ss* IL max)

0.0013701923

Factor * KV

180.8653846154

63.4 - Theta

31.6116693829

Sin(63.4 - Theta) / Sin 63.4


Load Resistance Primary

0.5862068802
106.0245328536

Load Resistance Secondary

35.3415109512

90% of Load Resistance

31.8073598561