Electrical tacing calculation for

Basis :

1. Cabel selction is based on Chromalox Cabel, http://www.chrom


2. Elec Supply : 220 v
3. Calc will is for one filter, both are identical filter, dimenssions are
Tank Dia
Tank Height
Cone Hight
Area
Operating Temp
Ambient Temp
Wind Speed
Installation
Surface Area
Insulation thickness
dt
Qt
Heat Loss
Manways Loss
Other Loss
Total Heat Loss
Cable Selction
Area Classification
Pipe Moc
Max Temp to maintain
Selected Family
Construction Option
Selected cabel
Out put
Length of cable

g calculation for Tanker unloading Filter

hromalox Cabel, http://www.chromalox.com

are identical filter, dimenssions are assumed, as approved GA are not available.
Client cal
Units
D
M
0.9
H
M
1.3
h
M
0
A
M2
4.9
T1
55
T2
25
Ws
32
Outdoor
A
4.9
thi
100
30
w/m2/c
0.388
Qt
W
57.6
Qty
1
Qs
540.0
Q
W
597.6
Class I, Div 2 Gr D, T3.
CS
55 deg C
SRM
CT
SRM/E-20 2CT
20.0

w/ft

29.9

Ft

g Filter

ot available.
Reference

Basis 3

table 4

As per Guide line


0.9
1.3
0
4.9
55
25
32
Outdoor
4.9
100
30
0.388
57.6
1
540.0
597.6

CS
55 deg C
Table 5

SRM
CT
SRM/E-20 2CT

Table 10

20
29.9

M
M
M
M2

w/m2/c
W

w/ft
ft