1 ABOUT NTPC Indias largest power company, NTPC was set up in 1975 to
accelerate power development in India. NTPC is emerging as a diversified power major
with presence in the entire value chain of the power generation business. Apart from
power generation, which is the mainstay of the company, NTPC has already ventured into
consultancy, power trading, ash utilization and coal mining. NTPC ranked 341st in the
2010, Forbes Global 2000 ranking of the Worlds biggest companies. NTPC became a
Maharatna company in May, 2010, one of the only four companies to be awarded this
status. The total installed capacity of the company is 39,174 MW (including JVs) with 16
coal based and 7 gas based stations, located across the country. In addition under JVs, 7
stations are coal based & another station uses naptha/LNG as fuel. The company has set a
target to have an installed power generating capacity of 1,28,000 MW by the year 2032.
The capacity will have a diversified fuel mix comprising 56% coal, 16% Gas, 11%
Nuclear and 17% Renewable Energy Sources(RES) including hydro. By 2032, non-fossil
fuel based generation capacity shall make up nearly 28% of NTPCs portfolio. NTPC has
been operating its plants at high efficiency levels. Although the company has 17.75% of
the total national capacity, it contributes 27.40% of total power generation due to its focus
on high efficiency.
2. 2 In October 2004, NTPC launched its Initial Public Offering (IPO) consisting of
5.25% as fresh issue and 5.25% as offer for sale by Government of India. NTPC thus
became a listed company in November 2004 with the Government holding 89.5% of the
equity share capital. In February 2010, the Shareholding of Government of India was
reduced from 89.5% to 84.5% through Further Public Offer. The rest is held by
Institutional Investors and the Public.
3. 3 Strategies of NTPC Technological Initiatives Introduction of steam generators
(boilers) of the size of 800 MW. Integrated Gasification Combined Cycle (IGCC)
Technology. Launch of Energy Technology Centre -A new initiative for development
of technologies with focus on fundamental R&D. The company sets aside up to 0.5%
of the profits for R&D. Roadmap developed for adopting Clean Development.
Mechanism to help get / earn Certified Emission Reduction.
4. 4 Corporate Social Responsibility As a responsible corporate citizen NTPC has
taken up number of CSR initiatives. NTPC Foundation formed to address Social issues
at national level NTPC has framed Corporate Social Responsibility Guidelines
committing up to0.5% of net profit annually for Community Welfare. The welfare of
project affected persons and the local population around NTPC projects are taken care of
through well drawn Rehabilitation and Resettlement policies.
Thecompanyhasalsotakenupdistributedgenerationforremoteruralareas Partnering
government in various initiatives Consultantroletomodernizeandimprovise
severalplantsacrossthecountry. Disseminate technologies to other players in the sector.
Consultant role Partnership in Excellence Programme for improvement of PLF of 15
Power Stations of SEBs. Rural Electrification work under Rajiv Gandhi Garmin
Vidyutikaran. Environment management AllstationsofNTPCareISO14001certified.
Variousgroupstocareofenvironmental issues. TheEnvironment ManagementGroup.
AshtilizationDivision. AfforestationGroup. Centre for Power Efficiency &
13. 13 Given below are the details of unit with the year theyre installed.
14. 14 StationLocation Badarpurissituatedonly20kmaway
fromDelhi.TheplantislocatedontheleftsideoftheNational Highway(DelhiMathuraRoad)anditcomprisesof430hectares(678acres) borderedby the Agra Canal from
East and by Mathura-Delhi Road from West. However, the area for ash
disposalisdoneintheDelhiMunicipallimitandismaintained
withthehelpofDelhiDevelopment
Authority.Theplantisalsoclosetotheprojectof220kvDoubleCircuitTransmissionlinebetween
the I.P.stationandBallabgarhCoolingWaterisobtainedfromAgraCanal for the cooling
system. Additional 60 cusecs channel has also been constructed parallel to the Agra Canal
so as to obtain uninterrupted water supply during the slit removing operation in
AgraCanal.
15. 15 OPERATION OF A POWER PLANT Basic Principle As per FARADAYs
Law-Whenever the amount of magnetic flux linked with a circuit changes, an EMF is
produced in the circuit. Generator works on the principle of producing electricity. To
change the flux in the generator turbine is moved in a great speed with steam. To
produce steam, water is heated in the boilers by burning the coal. In a Badarpur Thermal
PowerStation, steam is produced and used to spin a turbine that operates a generator.
Water is heated, turns into steam and spins a steam turbine which drives an electrical
generator. After it passes through the turbine, the steam is condensed in a condenser; this
is known as a Rankine cycle. The electricity generated at the plant is sent to consumers
through high-voltage power lines The Badarpur Thermal Power Plant has Steam TurbineDriven Generators which has a collective capacity of 705MW. The fuel being used is
Coal which is supplied from the Jharia Coal Field in Jharkhand. Water supply is given
from the Agra Canal.
16. 16 Basic Steps of Electricity Generation
Thebasicstepsinthegenerationofelectricityfromcoalinvolvesfollowingsteps: Coal to
steam Steam to mechanical power Mechanical power to electrical power
17. 17 Coal to Electricity : Basics
18. 18
19. 19
20. 20 PARTS OF A POWER PLANT The various parts are listed below:- 1. Cooling
tower 2. Cooling water pump 3. Transmission line (3-phase) 4. Unit transformer (3phase) 5. Electric generator (3-phase) 6. Low pressure turbine 7. Condensate extraction
pump 8. Condenser 9. Intermediate pressure turbine 10. Steam governor valve 11. High
pressure turbine
21. 21 12. Deaerator 13. Feed heater 14. Coal conveyor 15. Coal hopper 16. Pulverised
fuel mill 17. Boiler drum 18. Ash hopper 19. Super heater 20. Forced draught fan 21.
Reheater 22. Air intake 23. Economiser 24. Air preheater 25. Precipitator 26. Induced
draught fan 27. Flue Gas 1. Cooling Tower Cooling towers are heat removal devices used
to transfer process waste heat to the atmosphere. Cooling towers may either use the
evaporation of water to remove process heat and cool the working fluid to near the wetbulb air temperature or in the case of closed circuit dry cooling towers rely solely on air
to cool the working fluid to near the dry-bulb air temperature. Common applications
include cooling the circulating water used in oil refineries, chemical plants, power
stations and building cooling. The towers vary in size from small roof-top units to very
large hyperboloid structures that can be up to 200 meters tall and 100 meters in diameter,
or rectangular structures that can be over 40 meters tall and 80 meters long. Smaller
towers are normally factory-built, while larger ones are constructed on site. The absorbed
heat is rejected to the atmosphere by the evaporation of some of the cooling water in
mechanical forced-draft or induced
22. 22 Draft towers or in natural draft hyperbolic shaped cooling towers as seen at most
nuclear power plants. 2. Cooling Water Pump it pumps the water from the cooling tower
which goes to the condenser. 3. Three phase transmission line Three phase electric power
is a common method of electric power transmission. It is a type of polyphase system
mainly used to power motors and many other devices. A three phase system uses less
conductive material to transmit electric power than equivalent single phase, two phase, or
direct current system at the same voltage. In a three phase system, three circuits reach
their instantaneous peak values at different times. Taking current in one conductor as the
reference, the currents in the other two are delayed in time by one-third and two-third of
one cycle .This delay between phases has the effect of giving constant power transfer
over each cycle of the current and also makes it possible to produce a rotating magnetic
field in an electric motor. At the power station, an electric generator converts mechanical
power into a set of electric currents, one from each electromagnetic coil or winding of the
generator. The current are sinusoidal functions of time, all at the same frequency but
offset in time to give different phases. In a three phase system the phases are spaced
equally, giving a phase separation of one-third of one cycle. Generators output at a
voltage that ranges from hundreds of volts to 30,000 volts. 4. Unit transformer (3-phase)
At the power station, transformers step-up this voltage to one more suitable for
transmission. After numerous further conversions in the transmission and distribution
network the power is finally transformed to the standard mains voltage (i.e. the
household voltage). The power may already have been split into single phase at this
point or it may still be three phase. Where the step-down is 3 phase, the output of this
transformer is usually star connected with the standard mains voltage being the phase23. 23 neutral voltage. Another system commonly seen in North America is to have a
delta connected secondary with a center tap on one of the windings supplying the ground
and neutral. This allows for 240 V three phase as well as three different single phase
voltages( 120 V between two of the phases and neutral , 208 V between the third phase
( or wild leg) and neutral and 240 V between any two phase) to be available from the
same supply. 5. Electrical generator An Electrical generator is a device that converts
kinetic energy to electrical energy, generally using electromagnetic induction. The task of
converting the electrical energy into mechanical energy is accomplished by using a
motor. The source of mechanical energy maybe water falling through the turbine or steam
turning a turbine (as is the case with thermal power plants). There are several
classifications for modern steam turbines. Steam turbines are used in our entire major
coal fired power stations to drive the generators or alternators, which produce electricity.
The turbines themselves are driven by steam generated in "boilers or "steam generators"
as they are sometimes called. Electrical power stations use large steam turbines driving
electric generators to produce most (about 86%) of the worlds electricity. These
centralized stations are of two types: fossil fuel power plants and nuclear power plants.
The turbines used for electric power generation are most often directly coupled to theirgenerators .As the generators must rotate at constant synchronous speeds according to the
frequency of the electric power system, the most common speeds are 3000 r/min for 50
Hz systems, and 3600 r/min for 60 Hz systems. Most large nuclear sets rotate at half
those speeds, and have a 4-pole generator rather than the more common 2-pole one. 6.
Low Pressure Turbine Energy in the steam after it leaves the boiler is converted into
rotational energy as it passes through the turbine. The turbine normally consists of several
stages with each stages consisting of a stationary blade (or nozzle) and a rotating blade.
Stationary blades convert the potential energy of the steam into kinetic energy and direct
the flow onto the
24. 24 rotating blades. The rotating blades convert the kinetic energy into impulse and
reaction forces, caused by pressure drop, which results in the rotation of the turbine shaft.
The turbine shaft is connected to a generator, which produces the electrical energy. Low
Pressure Turbine (LPT) consists of 4x2 stages. After passing through Intermediate
Pressure Turbine steam is passed through LPT which is made up of two parts- LPC
REAR & LPC FRONT. As water gets cooler here it gathers into a HOTWELL placed in
lower parts of turbine. 7. Condensation Extraction Pump A Boiler feed water pump is a
specific type of pump used to pump water into a steam boiler. The water may be freshly
supplied or returning condensation of the steam produced by the boiler. These pumps are
normally high pressure units that use suction from a condensate return system and can be
of the centrifugal pump type or positive displacement type. Construction and operation:
Feed water pumps range in size up to many horsepower and the electric motor is usually
separated from the pump body by some form of mechanical coupling. Large industrial
condensate pumps may also serve as the feed water pump. In either case, to force the
water into the boiler, the pump must generate sufficient pressure to overcome the steam
pressure developed by the boiler. This is usually accomplished through the use of a
centrifugal pump. Feed water pumps usually run intermittently and are controlled by a
float switch or other similar level-sensing device energizing the pump when it detects a
lowered liquid level in the boiler. Some pumps contain a two-stage switch. As liquid
lowers to the trigger point of the first stage, the pump is activated. If the liquid continues
to drop, (perhaps because the pump has failed, its supply has been cut off or exhausted, or
its discharge is blocked) the second stage will be triggered. This stage may switch off the
boiler equipment (preventing the boiler from running dry and overheating), trigger an
alarm, or both.
25. 25 8. Condenser The steam coming out from the Low Pressure Turbine (a little above
its boiling pump) is brought into thermal contact with cold water (pumped in from the
cooling tower) in the condenser, where it condenses rapidly back into water, creating near
Vacuum-like conditions inside the condenser chest. 9. Intermediate Pressure Turbine
Intermediate Pressure Turbine (IPT) consists of 11 stages. When the steam has been
passed through HPT it enters into IPT. IPT has two ends named as FRONT & REAR.
Steam enters through front end and leaves from Rear end. 10. Steam Governor Valve
Steam locomotives and the steam engines used on ships and stationary applications such
as power plants also required feed water pumps. In this situation, though, the pump was
often powered using a small steam engine that ran using the steam produced by the boiler
a means had to be provided, of course, to put the initial charge of water into the boiler
(before steam power was available to operate the steam-powered feed water pump).The
pump was often a positive displacement pump that had steam valves and cylinders at one
end and feed water cylinders at the other end; no crankshaft was required. In thermal
plants, the primary purpose of surface condenser is to condense the exhaust steam from a
steam turbine to obtain maximum efficiency and also to convert the turbine exhaust steam
into pure water so that it may be reused in the steam generator or boiler as boiler feed
water. By condensing the exhaust steam of a turbine at a pressure below atmospheric
pressure, the steam pressure drop between the inlet and exhaust of the turbine is
increased, which increases the amount heat available for conversion to mechanical power.
Most of the heat liberated due to condensation of the exhaust steam is carried away by the
cooling medium (water or air) used by the surface condenser. Control valves are valves
used within industrial plants and elsewhere to control operating conditions such as
temperature, pressure, flow and liquid level by fully or partially opening or closing in
response to signals received from controllers that compares a set point to a
26. 26 process variable whose value is provided by sensors that monitor changes in
such conditions. The opening or closing of control valves is done by means of electrical,
hydraulic or pneumatic systems. 11.High Pressure Turbine Steam coming from Boiler
directly feeds into HPT at a temperature of 540C and at a pressure of 136 kg/cm2. Here
it passes through 12 different stages due to which its temperature goes down to 329C
and pressure as 27 kg/cm2. This line is also called as CRH COLD REHEAT LINE. It is
now passed to a REHEATER where its temperature rises to 540C and called as HRHHOT REHEATED LINE. 12. Deaerator A Deaerator is a device for air removal and used
to remove dissolved gases (an alternate would be the use of water treatment chemicals)
from boiler feed water to make it non- corrosive. A dearator typically includes a vertical
domed deaeration section as the deaeration boiler feed water tank. A Steam generating
boiler requires that the circulating steam, condensate, and feed water should be devoid of
dissolved gases, particularly corrosive ones and dissolved or suspended solids. The gases
will give rise to corrosion of the metal. The solids will deposit on the heating surfaces
giving rise to localized heating and tube ruptures due to overheating. Under some
conditions it may give rise to stress corrosion cracking. Deaerator level and pressure must
be controlled by adjusting control valves the level by regulating condensate flow and the
pressure by regulating steam flow. If operated properly, most deaerator vendors will
guarantee that oxygen in the deaerated water will not exceed 7 ppb by weight (0.005
cm3/L) 13. Feed water heater A Feed water heater is a power plant component used to
pre-heat water delivered to a steam generating boiler. Preheating the feed water reduces
the irreversibility involved in steam generation and therefore improves the
thermodynamic efficiency of the system. This reduces plant operating costs and also
helps to avoid thermal shock to the boiler
27. 27 metal when the feed water is introduced back into the steam cycle. In a steam
power (usually modelled as a modified Rankine cycle), feed water heaters allow the feed
water to be brought up to the saturation temperature very gradually. This minimizes the
inevitable irreversibility associated with heat transfer to the working fluid (water). 14.
Coal conveyor Coal conveyors are belts which are used to transfer coal from its storage
place to Coal Hopper. A belt conveyor consists of two pulleys, with a continuous loop of
material- the conveyor Belt that rotates about them. The pulleys are powered, moving
the belt and the material on the belt forward. Conveyor belts are extensively used to
transport industrial and agricultural material, such as grain, coal, ores etc. 15. Coal
Hopper Coal Hoppers are the places which are used to feed coal to Fuel Mill. It also has
the arrangement of entering Hot Air at 200C inside it which solves our two purposes:- 1.
If our Coal has moisture content then it dries it so that a proper combustion takes place. 2.
It raises the temperature of coal so that its temperature is more near to its Ignite
Temperature so that combustion is easy. 16. Pulverized Fuel Mill A pulveriser is a device
for grinding coal for combustion in a furnace in a fossil fuel power plant. 17. Boiler drum
Steam Drums are a regular feature of water tube boilers. It is reservoir of water/steam at
the top end of the water tubes in the water-tube boiler. They store the steam generated in
the water tubes and act as a phase separator for the steam/water mixture. The difference
in densities between hot and cold water helps in the accumulation of the hotterwater/and saturated steam into steam drum. Made from high-grade steel (probably
28. 28 stainless) and its working involve temperature of 390C and pressure well above
350psi (2.4MPa). The separated steam is drawn out from the top section of the drum.
Saturated steam is drawn off the top of the drum. The steam will re-enter the furnace in
through a super heater, while the saturated water at the bottom of steam drum flows down
to the mud-drum /feed water drum by down comer tubes accessories include a safety
valve, water level indicator and fuse plug. 18. Ash Hopper A steam drum is used in the
company of a mud-drum/feed water drum which is located at a lower level. So that it acts
as a sump for the sludge or sediments which have a tendency to accumulate at the
bottom. 19. Super Heater A Super heater is a device in a steam engine that heats the
steam generated by the boiler again increasing its thermal energy. Super heaters increase
the efficiency of the steam engine, and were widely adopted. Steam which has been
superheated is logically known as superheated steam; non- superheated steam is called
saturated steam or wet steam. Super heaters were applied to steam locomotives in
quantity from the early 20th century, to most steam vehicles, and also stationary steam
engines including power stations. 20. Force Draught Fan External fans are provided to
give sufficient air for combustion. The forced draught fan takes air from the atmosphere
and, warms it in the air preheater for better combustion, injects it via the air nozzles on
the furnace wall. 21. Reheater Reheater is a heater which is used to raise the temperature
of steam which has fallen from the intermediate pressure turbine.
29. 29 22. Air Intake Air is taken from the environment by an air intake tower which is
fed to the fuel. 23. Economizers Economizer, or in the UK economizer, are mechanical
devices intended to reduce energy consumption, or to perform another useful function
like preheating a fluid. The term economizer is used for other purposes as well-Boiler,
power plant, heating, ventilating and air-conditioning. In boilers, economizer are heat
exchange devices that heat fluids , usually water, up to but not normally beyond the
boiling point of the fluid. Economizers are so named because they can make use of the
enthalpy and improving the boilers efficiency. They are devices fitted to a boiler which
save energy by using the exhaust gases from the boiler to preheat the cold water used to
fill it (the feed water). Modern day boilers, such as those in cold fired power stations, are
still fitted with economizer which is decedents of Greens original design. In this context
there are turbines before it is pumped to the boilers. A common application of economizer
in steam power plants is to capture the waste heat from boiler stack gases (flue gas) and
transfer thus it to the boiler feed water thus lowering the needed energy input , in turn
reducing the firing rates to accomplish the rated boiler output . Economizer lower stack
temperatures which may cause condensation of acidic combustion gases and serious
equipment corrosion damage if care is not taken in their design and material selection. 24.
Air Preheater Air preheater is a general term to describe any device designed to heat air
before another process (for example, combustion in a boiler). The purpose of the air
preheater is to recover the heat from the boiler flue gas which increases the thermal
efficiency of the boiler by reducing the useful heat lost in the flue gas. As a consequence,
the flue gases are also sent to the flue gas stack (or chimney) at a lower temperature
allowing simplified design of the ducting and the flue gas stack. It also allows control
over the temperature of gases leaving the stack.
30. 30 25. Precipitator An Electrostatic precipitator (ESP) or electrostatic air cleaner is a
particulate device that removes particles from a flowing gas (such as air) using the force
of an induced electrostatic charge. Electrostatic precipitators are highly efficient filtration
devices, and can easily remove fine particulate matter such as dust and smoke from the
air steam. ESPs continue to be excellent devices for control of many industrial particulate
emissions, including smoke from electricity-generating utilities (coal and oil fired), salt
cake collection from black liquor boilers in pump mills, and catalyst collection from
fluidized bed catalytic crackers from several hundred thousand ACFM in the largest coalfired boiler applications. The original parallel plate-Weighted wire design (described
above) has evolved as more efficient (and robust) discharge electrode designs, today
focus is on rigid discharge electrodes to which many sharpened spikes are attached ,
maximizing corona production. Transformer rectifier systems apply voltages of 50-100
Kilovolts at relatively high current densities. Modern controls minimize sparking and
prevent arcing, avoiding damage to the components. Automatic rapping systems and
hopper evacuation systems remove the collected particulate matter while on line allowing
ESPs to stay in operation for years at a time. 26. Induced Draught Fan The induced draft
fan assists the FD fan by drawing out combustible gases from the furnace, maintaining a
slightly negative pressure in the furnace to avoid backfiring through any opening. At the
furnace outlet and before the furnace gases are handled by the ID fan, fine dust carried by
the outlet gases is removed to avoid atmospheric pollution. This is an environmental
limitation prescribed by law, which additionally minimizes erosion of the ID fan. 27. Flue
gas stack A Flue gas stack is a type of chimney, a vertical pipe, channel or similar
structure through which combustion product gases called flue gases are exhausted to the
outside air. Flue gases are produced when coal, oil, natural gas, wood or any other large
combustion
31. 31 device. Flue gas is usually composed of carbon dioxide (CO2) and water vapour as
well as nitrogen and excess oxygen remaining from the intake combustion air. It also
contains a small percentage of pollutants such as particulates matter, carbon mono oxide,
nitrogen oxides and sulphur oxides. The flue gas stacks are often quite tall, up to 400
meters (1300 feet) or more, so as to disperse the exhaust pollutants over a greater area
and thereby reduce the concentration of the pollutants to the levels required by
government's environmental policies and regulations. The flue gases are exhausted from
stoves, ovens, fireplaces or other small sources within residential abodes, restaurants,
hotels through other stacks which are referred to as chimneys.
32. 32 VARIOUS CYCLES AT POWER STATION PRIMARY AIR CYCLE
SECONDARY AIR CYCLE COAL CYLCE ELECTRICITY CYCLE FLUE
GAS CYCLE CONDENSATE CYCLE FEED WATER CYCLE STEAM CYCLE
33. 33 PRIMARY AIR CYCLE P A FAN COLD AIR DUCT SEAL AIR FAN APH HOT
AIR DUCT PULVERISER
34. 34 SECONDARY AIR CYCLE W I N D B O X IGNITER FAN SCANNER AIR
FAN SCANNER COOLING FD FAN SCAPH APH WIND BOX BOILER
35. 35 ELECTRICITY CYCLE GENERATOR UAT UAT MAIN TRANSFORMER
SWITCH YARD OUTGOING FEEDER To Auxiliaries To Auxiliaries
36. 36 CONDENSATE CYCLE HOT WELL CONDENSATE PUMPS MAIN EJECTOR
GLAND STEAM COOLER WITH EJECTOR LP HEATER 2 LP HEATER 3 LP
HEATER 4 DEAERATOR BOILER FEED PUMP
37. 37 FEED WATER CYCLE BOILER FEED PUMP HP HEATOR 5 HP HEATOR 6
HP HEATOR 7 FEED REGULATING STN ECONOMISER BOILER DRUM DOWN
COMERS UPRISERS BOILER DRUM
38. 38 STEAM CYCLE BOILER DRUM L.T.S.H. FLATEN S.H. FINAL S.H. H P
TURBINE C.R.H. H.R.H I P TURBINE L P TURBINE CONDENSER
39. 39 Coal Cycle
40. 40 Flue Gas Cycle
41. 41 ELECTRICAL MAINTENANCE DEPARTMENT I (EMD-I) Electrical
maintenance division 1 It includes: Motors High Tension/Low Tension
Switchgear Coal handling plant I was assigned to do training in this division from 11th
June to29th June.
42. 42 MOTORS Motorscanbeclassifiedas ACandDC . ACMOTORS 1.
Squirrelcagemotor 2. Woundmotor 3. Slipringinductionmotor In modern thermal power
plant three phase squirrel cage induction motors are used but sometimedouble
woundmotor isusedwhenweneedhighstartingtorquee.g.inballmill.
THREEPHASEINDUCTIONMOTOR Ns(speed)=120f/p Stator canhandleconcentrated
singlelayer winding, witheachcoiloccupyingonestator slot
Themostcommontypeofwindingare: 1. DISTRIBUTEDWINDING: This type of winding
is distributed over a number of slots. 2. DOUBLELAYERWINDING: Eachstator
slotcontainssidesoftwodifferentcoils. SQUIRRELCAGEINDUCTIONMOTOR Squirrel
cage and wound cage have same mode of operation. Rotor conductors cut the rotating
stator magnetic field. an emf is induced across the rotor winding, current flows, a rotor
magnetic field is produced which interacts with the stator field causing a turning
43. 43 motion. The rotor does not rotate at synchronous speed, its speed varies with
applied load. The slip speed beingjustenoughtoenablesufficientinducedrotor
currenttoproducethepower dissipatedby the motor load and motor losses. BEARINGS
ANDLUBRICATIONS Agoodbearingisneededfor troublefreeoperationof
motor.Sinceitisverycostlypartofthe motor, due care has to be taken by checking it at
regular intervals. So lubricating plays an important role. Two types of lubricating are
widely used 1. Oil lubrication 2. Grease lubrication 3. Insulation INSULATION
Windingisanessentialpartsoitshouldbeinsulated.Followingtypesofinsulationarewidelyused
TYPESOFINSULATION CLASS TEMP UPTO WHICH THEY ARE EFFECTIVE
(DEGREE CENTIGRADE) Y 90 A 105 E 120 B 130 F 155 H 180 C more than 180
Fclassinsulationisgenerallypreferred.
44. 44 MAIN MOTOR USED INBOILERAND OFFSIDE AREA 1. IDFAN(2PER
UNIT) ItislocatedbetweenEPandchimneyusedfor creatinginduceddraftinthefurnace. 2.
PAFAN(2 PER UNIT) It is used for handling atmospheric air up to temperature 50 degree
centigrade 3. FDFAN(2 PER UNIT) Itisusedfor handlingsecondaryair for theboiler. 4.
SCANNER FAN(2 PER UNIT) Itisrequiredforrequisiteair for scanner cooling. 5.
IGNITORFAN Itsuppliesair for coolingofigniters. INSTRUMENTSSEEN 1.
MICROMETER Thisinstrumentisusedfor measuringinsideaswellasoutsidediameter
ofbearing. 2. MEGGAR Thisinstrumentisusedfor measuringinsulationresistance. 3.
VIBRATIONTESTER Itmeasuresthevibrationofthemotor.Itismeasuredinthreedimensionsaxial,verticaland horizontal.
45. 45 SWITCHGEAR INTRODUCTION Switchgear isonethatmakesor
breakstheelectricalcircuit.Itisa switchingdevicethatopens& closes a circuit that defined as
apparatus used for switching, Lon rolling & protecting the electrical
circuit&equipments.Theswitchgear
equipmentisessentiallyconcernedwithswitching&interrupting currentseither under
normalorabnormaloperatingconditions.Thetubular switch with ordinary fuse is simplest
form of switchgear & is used to control & protect&other equipmentsin
homes,officesetc.For circuitsofhigherratings,aHighRupturingCapacity (H.R.C) fuse in
condition with a switch may serve the purpose of controlling
&protectingthecircuit.However
suchswitchgearcannotbeusedprofitablyonhighvoltagesystem(3.3 KV)
for2reasons.Firstly,whena fuseblows,ittakessometimetoreplaceit&consequently there is
interruption of service to customer. Secondly, the fuse cannot successfully interrupt large
currents that result from the High Voltage System. In order to interrupt heavy fault
currents, automatic circuit breakers are used. There are very
fewtypesofcircuitbreakersinB.P.T.StheyareVCB,OCB,and
SF6gascircuitbreaker.Themostexpensive circuit breaker is the SF6 type due to gas. There
are various companies which manufacturethesecircuitbreakers: VOLTAS,JYOTI,and
KIRLOSKAR.Switchgearincludesswitches,fuses,circuitbreakers,relays&other
equipments
46. 46 THEEQUIPMENTSTHATNORMALLYFALLINTHISCATEGORYARE:- 1.
ISOLATOR Anisolator
isonethatcanbreaktheelectricalcircuitwhenthecircuitistobeswitchedonnoload. These are
used in various circuits for isolating the certain portion when required for
maintenanceetc.Anoperatingmechanismboxnormallyinstalledatgroundleveldrivestheisolat
or. Theboxhasanoperatingmechanisminadditiontoitscontactor
circuitandauxiliarycontactsmaybe solenoidoperatedpneumaticthreephasemotoror DC
motor transmittingthrough a spur gear to the torsion shaft of the isolator. Certain
interlocks are also provided with theisolator Theseare 1. Isolator
cannotoperateunlessbreaker isopen 2. Bus 1 and bus 2 isolators cannot be closed
simultaneously 3. Theinterlockcanbebypassintheeventofclosingofbuscoupler breaker. 4.
Noisolator canoperatewhenthecorrespondingearthswitchison 2. SWITCHINGISOLATOR
Switching isolator is capable of: 1. Interruptingchargingcurrent 2. Interrupting
transformer magnetizing current 3. Load transformer switching. Its main application is in
connection with the transformer feeder as the unit makes it possible to
switchgearonetransformer whiletheotherisstillonload. 3. CIRCUITBREAKER One
whichcanmakeor breakthecircuitonloadandevenonfaultsisreferredtoascircuit
breakers.Thisequipmentisthemostimportantandisheavydutyequipmentmainlyutilized for
protection of various circuits and operations on load. Normallycircuitbreakers
installedareaccompaniedbyisolators.
47. 47 4. LOADBREAK SWITCHES Thesearethoseinterruptingdeviceswhichcanmakeor
break circuits.Thesearenormallyon same circuit,whicharebackedbycircuitbreakers 5.
EARTH SWITCHES Devices which are used normally to earth a particular system, to
avoid any accident happening
duetoinductiononaccountofliveadjoiningcircuits.Theseequipmentsdonothandle
anyappreciable current at all. Apart from this equipment there are a number of relays etc.
which areusedinswitchgear. LT SWITCHGEAR In LT switchgear there is no
interlocking. It is classified in following ways:- 1. MAINSWITCH Main switch is control
equipment which controls or disconnects the main supply. The main switch for 3 phase
supply is available for the range 32A, 63A, 100A, 200Q, 300A at 500V grade. 2. FUSES
With Avery high generating capacity of the modern power stations extremely heavy
carnets would flow in the fault and the fuse clearing the fault would be required to
withstand extremely heavy stress in process. It is used for supplying power to auxiliaries
with backup fuse protection. With fuses, quick break, quick make and double break
switch fuses for 63A and 100A, switch fuses for 200A,400A, 600A, 800A and 1000A are
supplies coal to Unit- I, II, III & NCHP supplies coal to Unit- IV and V.
COALSUPPLIEDATBTPS Coal is supplied to BTPS by Jharia coal mines. It is noncooking coal and has following specifications:- Moisture- less than 8% Volatile
matter-17%to19% Ash- 35% - 40% Calorific Value- 4500 to5300 Kcal/kg Coal is
received in railway box racks containing 20 - 42 wagons in each rack. Capacity of each
box wagon is about 55 ton. These wagons are placed on 2 wagon tippler in OCHP &
one wagon tippler in NCHP, in total 3, capacity 80 toneach.
54. 54 COAL CYCLE
55. 55 OLD COAL HANDLING PLANT (OCHP) KEY DIAGRAM
56. 56 The main constituents of OCHP plant are:- WAGONTIPPLER Wagon from coal
yard come to the tippler and emptied here. There are 2 wagon tipplers in the OCHP. The
tippler is tilted to about 137- 141 so that coal from the wagon is emptied into the
hopper. Elliptics feeder is used in OCHP. Total 8 feeders are used, 4 in each hopper. Slip
Ring Induction Motor is used to operate a wagon tippler. This type of IM is used in the
tippler because of its high resistance, low speed & high torque characteristics. The rating
of the motor used is: o Power 55 Kw o Voltage 415V o Current 102A o Speed 1480rpm o
Phase 3 o Frequency 50Hz Three types of wagon tipplers are used:- a) ROTASIDE: - It is
used for open type wagons in which each wagon carries around 50- 56 tons of coal. The
wagon is tilted by 150 to put the coal in the unloading hopper. b) ROTARY: - In this
case the unloading hopper is placed directly under the tippler table. This is also used to
tilt the wagon tippler to 180. c) ROCKING TYPE: - It is used for close type wagons. In
this hoppers is placed by the side of end rocking is provided to facilitate unloading of
coal at corners of the wagon.
57. 57 CONVEYER Conveyer belts are used in the OCHP to transfer coal from one place
to other as required in a convenient&safe way.Allthebeltsarenumberedaccordingly
sothattheir functioncanbeeasily demarcated. These belts are made of rubber & move with
a speed of 250-300 m/min. Motor employedfortheconveyer hasa
capacityof150HP.Theseconveyershavea capacityof carrying the coal at the rate of 400
ton/hr. ZEROSPEED SWITCH It is used as a safety device for the motor i.e. if the belt is
not moving & the motor is ON, then
itburnstosavethemotor.Thisswitchchecksthespeedofthebelt&switchesoffthemotor when
speediszero. METALDETECTOR As the conveyer belt take coal from wagon to crusher
house, no metal piece should go along with coal. To achieve this objective, metal
detectors & separators are used. In the OCHP, these MDs are installed in the conveyer
belts 2A & 2B. CRUSHERHOUSE Both the plants i.e. OCHP & NCHP use TATA
crusher powered by BHEL motor. Crusher is of ring typeandthemotorisaHT motor
ofrating400HP&6.6 KV.Crusherisdesignedto crushthepieces to 20 mm size i.e. practically
considered as the optimum size for transfer via conveyer. ROTARYBREAKER
Ifanylargepieceofmetalofanyhardsubstanceslikemetalimpuritiescomesintheconveyer
beltwhich
causeloadonthemetalseparator,thentherotarybreakerrejectsthemreducingtheloadonthemeta
l detector.
58. 58 STACKER-CUM-RECLAIMER It is used for stacking & reclaiming the coal from
the stockyard in case of unavailability of wagons from coal mines. PLOUGHFEEDER
Theseplough feedersaregenerallyinstalledunder slotbunkersor hoppers.Theseareusedtop
lough the coal to the belt from the coal fed from stockyard. These feeders used in this
power station are generally of rotary type. TRIPPERS Trippersareprovidedintheconveyer
tocollectthematerialatdesiredlocationoneither sideoralongthe conveyer
withthehelpofchute/ductsfittedwithtripper itself.Themotor inthetrippercanmakeit move
bothinforwardandreversedirection. PULL GUARDSWITCH
Thesearetheswitcheswhichareinstalledatevery10mgapina conveyer belttoensurethesafety
of motors running the conveyer belts. If at any time some accident happens or coal jumps
from belt and starts collecting at a place, this switch can be moved to NO(normally open)
position from NC (normally closed) position to stop conveyor belt from moving. At this
timetheproblemcanbecorrected&thenagaintheswitchcanbemovedtoNC(normallyclosed)
position for normal working again. INTERLOCKS: - The CHP is normally spread over a
wide area with centralized control room. Elaborate scheme is
thereforeprovided.Ifduetoanyemergencyeither theconveyor beltorthemotor hastobe
stopped, due to this interlocking all the other motors connected to it will automatically
stop &will not work till signal is given from the control room.
59. 59 The control & protection scheme normally includes: - A hooter system to warn
that the plant is going to be started. The plant can be started only after a definite time
after the hooter is energized. Sequential starting of conveyor system and tripping of all
proceeding system if any equipmentinthechainistripped. Tripping of conveyor from
speed switch for protection against belt slippage.
SEQUENTIALOPERATIONOFOCHP:- I. Unloadingthecoal II. Crushing & storage. III.
Conveyingtoboiler bunkers. a) Coal arrives to plant via road, rail, sea, and river or canal
route from collieries. Most of it
arrivesbyrailrouteonlyinrailwaywagons.Coalrequirementbythisplantis approximately
10,500 metric ton/day. b) This coal is tippled into hoppers. If the coal is oversized (400
mm sq), then it is broken manuallysothatitpassesthehopper meshwherethroughelliptic
feeder itisputinto vibrators&thentoconveyor belt1A &1B. c) The coal through conveyor
belts 1A & 1B goes to the crusher house. Also the extra coal is sent to stockyard through
these belts. d) Inthecrusher housethe smallsizecoalpiecesgoesdirectlytothebelt2A &2B
whereasthe bigsizecoalpiecesarecrushedinthecrusher &thengiventothebelts2A&2B. e)
Thecrushedcoalistakentothebunker housevia theconveyor belts3A&3B whereitcanbe
usedfor further operations.
60. 60 NEW COAL HNDLINGPLANT (NCHP) KEYDIAGRAM
61. 61 The main constituents of NCHP plant are:- Most of the constituents of the NCHP
are the same as that of OCHP. WAGONTIPPLER InNCHPthereisonlyone
wagontippler.Inthisittakes52sectoraisea wagon,10secto emptythe
wagoncompletely&thenagain52sectobringthetippler down.AsemicircularhugeWTgear is
used to run the tippler. Protocol cameras have been installed for safety to ensure that
nomoving creatureor objectisnearthewagonwhichisonthetippler.
65. 65 2. RCFEEDER It transports pre-crust coal from raw coal bunker to mill. The
quantity of raw coal fed in mill can be controlled by speed control of aviator drive
controlling damper and aviator change 3. BALLMILL: The ball mill crushes the raw coal
to a certain height and then allows it to fall down. Due to impact of ball on coal and
attraction as per the particles move over each other as well as over the Armor lines, the
coal gets crushed. Large particles are broken by impact and full grinding is done by
attraction. The Drying and grinding option takes place simultaneously inside the mill. In
ball mill coal is converted to powdered form and due to pneumatic action the powdered
form of coal is transferred upwards. 4. CLASSIFIER: It is equipment which serves
separation of fine pulverized coal particles medium from coarse medium. The pulverized
coal along with the carrying medium strikes the impact plate through the lower part.
Large particles are then transferred to the ball mill. 5. MILLFAN From ball mill the
powdered coal is sucked through mill fan. 6. CYCLONESEPARATORS It separates the
pulverized coal from carrying medium. The mixture of pulverized coal vapour caters the
cyclone separators tangentially in the upper part of the separator. Due to decrease in the
velocity the centrifugal action, the pulverized coal separated from the vapour
&fallsdowntothelower epicalpart.
66. 66 7. THETURNIGATE It serves to transport pulverized coal from cyclone separators
to pulverized coal bunker or to worm conveyors. There are 4 turnigates per boiler. 8.
WORMCONVEYOR It is equipment used to distribute the pulverized coal from bunker
of one system to bunker of other system. It can be operated in both directions
67. 67 ELECTRICAL MAINTENANCE DEPARTMENT II (EMD-II) Electrical
maintenance division 2 It includes: Generators Transformers Switch yard I was
assigned to do training in this division from 2nd July to13th July.
68. 68 GENERATORS The generator works on the principle of electromagnetic
induction. There are two components stator and rotor. The rotor is the moving part and
the stator is the stationary part. The rotor, which has a field winding, is given a excitation
through a set of 3000rpm to give
therequiredfrequencyofHZ.TherotoriscooledbyHydrogengas,whichislocally manufactured
by the plant and has high heat carrying capacity of low density. If oxygen and
hydrogengetmixedthentheywillformveryhighexplosiveandtopreventtheir combininginany
waythereissealoilsystem.Thestator coolingisdonebyde-mineralized(DM)
waterthroughhollow conductors.WaterisfedbyoneendbyTeflontube.Aboilerandaturbineare
coupled to electric generators. Steam from the boiler is fed to the turbine through the
connecting pipe. Steam drives the turbine rotor. The turbine rotor drives the generator
rotor which turns the electromagnet within the coil of wire conductors. Carbon dioxide is
provided from the top and oil is provided from bottom to the generator. With
thehelpofcarbondioxidetheoilisdrainedouttotheoiltank. Hydrogen gas is used to cool
down the rotor. Lube oil is used to cool the bearings.
69. 69 DM water is used to cool the stator. Seal oil is used to prevent hydrogen
leakage Seal oil coolers are present to cool the seal oil Hydrogen dryer are used
which removes the moisture from hydrogen gas and then is supplied to the generator.
Clarified water in cooling tower is used to cool down the hydrogen gas.
RATINGSOFTHEGENERATORSUSED Turbo generator 100MW
TURBOGENERATOR210MW The 100 MW generator generates 10.75 KV and 210 MW
generates 15.75 KV. The voltage is steppedupto220KVwiththehelpofgenerator
transformerandisconnectedtothegrid. Thevoltageissteppeddownto6.6
KVwiththehelpofUNIT AUXILLARY TRANSFORMER (UAT)and this voltage is used
to drive the HT motors. The voltage is further stepped down to 415 V and then to 220 V
and this voltage is used to drive Lt Motors.
70. 70 TURBOGENERATOR100MW MAKE BHEL, Haridwar CAPACITY 117,500
KVA POWER 100,000 KW STATOR VOLTAGE 10,500 V STATOR CURRENT 6475 A
SPEED 5000rpm POWER FACTOR 0.85 FREQUENCY 50 HZ EXCITATION 280 V
TURBOGENERATOR210MW MAKE BHEL, Haridwar CAPACITY 247,000 KVA
POWER 210,000 KW STATOR VOLTAGE 15,750 V STATOR CURRENT 9050 A
SPEED 5000 rpm POWER FACTOR 0.85 FREQUENCY 50 HZ EXCITATION 310 V
GAS PRESSURE 3.5 kg/cm
71. 71 TRANSFORMERS INTRODUCTION It is a static machine which increases or
decreases the AC voltage without changing the frequency of the supply. It is a device
that: Transfer electric power from one circuit to another. It accomplishes this by
electromagnetic induction. In this the two electric circuits are in mutual inductive
influence of each other. WORKINGPRINCIPLE: It works on FARADAYS LAW OF
ELECTROMAGNETIC INDUCTION (self or mutual induction depending on the type of
transformer).
72. 72 MAINPARTS CONSERVATOR It is used generally to conserve the insulating
property of the oil from deterioration& protect the transformer against failure on account
of bad quality of oil. SILICAGEL DEHYDRATINGBREATHER It is used to prevent
entry of moisture inside the transformer tank. The breather consists of silica gel.
GASOPERATEDRELAY(BUCHHOLZRELAY) It is a gas actuated relay used for
protecting oil immersed transformer against all types of faults. It indicates presence of
gases in case of some minor fault & take out the transformer out of circuit in case of
serious fault. BUSHINGS It is made from highly insulating material to insulate & to
bring out the terminals of the transformer from the container. The bushings are of 3 types:
a. Porcelain bushings used for low voltage transformer b. Oil filled bushings used for
voltage up to 33KV. c. Condensed type bushings used for voltage above 33KV.
OILGUAGE Every transformer with an oil guage to indicate the oil level. The oil guage
may be provided with the alarm contacts which gave an alarm the oil level has dropped
beyond permissible height due to oil leak etc. TAPPINGS The transformer are usually
provided with few tappings on secondary side so that output voltage can be varied for
constant input voltage. RADIATORS It increases the surface area of the tank & more
heat is thus radiated in less time. WINDINGSTEMPERATUREINDICATOR(OIL
GUAGE) Device which indicates the temperature of winding of transformer & possible
damage to the transformer due too overload can be prevented.
Itprovidesadequateinsulationbetweenthecontactsandfromeachcontacttoearth.
CAPACITATIVE VOLTAGETRANSFORMER A capacitor voltage transformer (CVT) is
a transformer used in power systems to step-down extra high voltage signals
andprovidelow voltage signals either for measurement or to operatea
protectiverelay.Itislocatedinthelastintheswitchyardasit increasestheground resistance.
Finally the voltage from CVT in the switchyard is sent out from the station through
transmissionlines. EARTHINGROD Normallyun-galvanizedmildsteelflatsareusedfor
earthling.Separateearthingelectrodesare provided to earth the lightening arrestor whereas
the other equipments are earthed by connectingtheir earthleadstotherid/ser
ofthegroundmar. CURRENTTRANSFORMER It is essentially a step up transformer
which step down the current to a known ratio. It is a type of instrument transformer
designed to provide a current in its secondary winding proportional to the alternating
current flowing in its primary.
81. 81 POTENTIALTRANSFORMER Itisessentiallya
stepdowntransformeranditstepdownsthevoltagetoaknownratio. RELAYS Relay is a
sensing device that makes your circuit ON or OFF. They detect the abnormal
conditionsintheelectricalcircuitsbycontinuouslymeasuringtheelectricalquantities,
whicharedifferentundernormalandfaultyconditions,likecurrent,voltagefrequency.Having
detectedthefaulttherelayoperatestocompletethetripcircuit, whichresultsintheopening of the
circuit breakers and disconnect the faulty circuit. Therearedifferenttypesofrelays: i.
Currentrelay ii. Potentialrelay iii. Electromagneticrelay iv. Numericalrelayetc.
AIRBREAK EARTHINGSWITCH Thework
ofthisequipmentcomesintopicturewhenwewanttoshutdownthesupplyfor maintenance
purpose. This help to neutralize the system from induced voltage from extra high voltage.
This induced power is up to 2KV in case of 400 KV lines. ELECTROSTATIC
PRECIPITATOR An electrostatic precipitator ( ESP) or electrostatic air cleaner is a
particulate collection device that removes particles from a flowing gas (such as air) using
the force of an induced electrostatic charge. Electrostatic precipitators are highly efficient
filtration devices that minimally impede the flow of gases through the device, and can
easily remove fine particulate matter such as dust and smoke from the air stream.
82. 82 In contrast to wet scrubbers which apply energy directly to the flowing fluid
medium, an ESP applies energy only to the particulate matter being collected and
therefore is very efficient in its consumption of energy (in the form of electricity).The
most basic precipitator contains a row of thin vertical wires, and followed by a stack of
large flat metal plates oriented vertically, with the plates typically spaced about 1 cm to18
cm apart, depending on the application. The air or gas stream flows horizontally through
the spaces between the wires, and then passes through the stack of plates. A negative
voltage of several thousand volts is applied between wire and plate. If the applied voltage
is high enough an electric (corona) discharge ionizes the gas around the electrodes.
Negative ions flow to the plates and charge the gas-flow particles. The ionized particles,
following the negative electric field created by the power supply, move to the grounded
plates. Particles build up on the collection plates and form a layer. The layer does not
collapse, thanks to electrostatic pressure (given from layer resistivity, electric field, and
current flowing in the collected layer).
instrument uses for protection are: RELAY It is a protective device. It can detect wrong
condition in electrical circuits by constantly measuring the electrical quantities flowing
under normal and faulty conditions. Some of the electrical quantities are voltage, current,
phase angle and velocity. 2. FUSES it is a short piece of metal inserted in the circuit,
which melts when heavy current flows through it and thus breaks the circuit. Usually
silver is used as a fuse material because: a. The coefficient of expansion of silver is very
small. As a result no critical fatigue occurs and thus the continuous full capacity normal
current ratings are assured for the long time.
87. 87 b. The conductivity of the silver is unimpaired by the surges of the current that
produces temperatures just near the melting point c. Silver fusible elements can be raised
from normal operating temperature to vaporization quicker than any other material
because of its comparatively low specific heat. Miniature Circuit Breaker They are used
with combination of the control circuits to. a) Enable the staring of plant and distributors.
b) Protect the circuit in case of a fault. In consists of current carrying contacts, one
movable and other fixed. When a fault occurs the contacts separate and are is stuck
between them. There are three types of trips. I. MANUAL TRIP II. THERMAL TRIP III.
SHORT CIRCUIT TRIP Protection and Interlock System- 1) HIGH TENSION
CONTROL CIRCUIT for high tension system the control system is excited by separate
D.C supply. For starting the circuit conditions should be in series with the starting coil of
the equipment to energize it. Because if even a single condition is not true then system
will not start. 2) LOW TENSION CONTROL CIRCUIT For low tension system the
control circuits are directly excited from the 0.415 KV A.C supply. The same circuit
achieves both excitation and tripping. Hence the tripping coil is provided for emergency
tripping if the interconnection fails.
88. 88 3. AUTOMATION LAB This lab deals in automating the existing equipment and
feeding routes. Earlier, the old technology dealt with only (DAS) Data Acquisition
System and came to be known as primary systems. The modern technology or the
secondary systems are coupled with (MIS) Management Information System. But this lab
universally applies the pressure measuring instruments as the controlling force. However,
the relays are also provided but they are used only for protection and interlocks. 4.
PYROMETRY LAB LIQUID IN GLASS THERMOMETER Mercury in the glass
thermometer boils at 340 C which limits the range of temperature that can be measured.
It is L shaped thermometer which is designed to reach all inaccessible places. ULTRA
VIOLET CENSOR- This device is used in furnace and it measures the intensity of ultra
violet rays there and according to the wave generated which directly indicates the
temperature in the furnace. THERMOCOUPLES This device is based on SEEBACK and
PELTIER effect. It comprises of two junctions at different temperature. Then the emf is
induced in the circuit due to the flow of electrons. This is an important part in the plant.
RTD (RESISTANCE TEMPERATURE DETECTOR) It performs the function of
thermocouple basically but the difference is of a resistance. In this due to the change in
the resistance the temperature difference is measured. In this lab, also the measuring
devices can be calibrated in the oil bath or just boiling water (for low range devices) and
in small furnace (for high range devices) .
89. 89 5. FURNACE SAFETY AND SUPERVISORY SYSTEM LAB This lab has the
responsibility of starting fire in the furnace to enable the burning of coal. For first stage
coal burners are in the front and rear of the furnace and for the second and third stage
corner firing is employed. Unburnt coal is removed using forced draft or induced draft
fan. The temperature inside the boiler is 1100C and its heights 18 to 40 m. It is made up
of mild steel. An ultra violet sensor is employed in furnace to measure the intensity of
ultra violet rays inside the furnace and according to it a signal in the same order of same
mV is generated which directly indicates the temperature of the furnace. For firing the
furnace a 10 KV spark plug is operated for ten seconds over a spray of diesel fuel and
pre-heater air along each of the feeder-mills. The furnace has six feeder mills each
separated by warm air pipes fed from forced draft fans. In first stage indirect firing is
employed that is feeder mills are not fed directly from coal but are fed from three feeders
but are fed from pulverized coalbunkers. The furnace can operate on the minimum feed
from three feeders but under no circumstances should anyone be left out under operation,
to Prevent creation of pressure different with in the furnace, which threatens to blast it. 6.
ELECTRONICS LAB This lab undertakes the calibration and testing of various cards. It
houses various types of analytical instruments like oscilloscopes, integrated circuits,
cards auto analyzers etc. Various processes undertaken in this lab are: 1. Transmitter
converts mV to mA. 2. Auto analyzer purifies the sample before it is sent to electrodes. It
extracts the magnetic portion. ANNUNCIATIN CARDS They are used to keep any
parameter like temperature etc. within limits. It gets a signal if parameter goes beyond
limit. It has a switching transistor connected to relay that helps in alerting the UCB.
90. 90 CONTROL & MONITORING MECHANISMS There are basically two types of
Problems faced in a Power Plant 1. Metallurgical 2. Mechanical Mechanical Problem can
be related to Turbines that is the max speed permissible for a turbine is3000 rpm so speed
should be monitored and maintained at that level. Metallurgical Problem can be view as
the max Inlet Temperature for Turbine is 1060 C so temperature should be below the
limit. Monitoring of all the parameters is necessary for the safety of both: 1. Employees
2. Machines So the Parameters to be monitored are: 1. Speed 2. Temperature 3. Current 4.
Voltage 5. Pressure 6. Eccentricity 7. Flow of Gases 8. Vacuum Pressure 9. Valves 10.
Level 11. Vibration
91. 91 PRESSURE MONITORING Pressure can be monitored by three types of basic
mechanisms 1. Switches 2. Gauges 3. Transmitter type For gauges we use Bourdon tubes.
The Bourdon Tube is a non-liquid pressure measurement device. It is widely used in
applications where inexpensive static pressure measurements are needed. A typical
Bourdon tube contains a curved tube that is open to external pressure input on one end
and is coupled mechanically to an indicating needle on the other end, as shows
schematically below. Typical Bourdon Tube Pressure Gages For Switches pressure
switches are used and they can be used for digital means of monitoring as switch being
ON is referred as high and being OFF is as low. All the monitored data is converted to
either Current or Voltage parameter.
92. 92 The Plant standard for current and voltage are as under Voltage : 0 10 Volts
range Current : 4 20milli-Amperes We use 4mA as the lower value so as to check for
disturbances and wire breaks. Accuracy of such systems is very high. ACCURACY:
0.1% Programmable Logic Circuits (PLCs) are used in the process as they are the heart
of Instrumentation.
93. 93 TEMPERATURE MONITORING We can use Thermocouples or RTDs for
temperature monitoring. Normally RTDs are used for low temperatures. Thermocouple
selection depends upon two factors: 1. TemperatureRange 2. Accuracy Required
Normally used Thermocouple is KTypeThermocouple: In this we use Chromel (NickelChromium Alloy) / Alumel (Nickel-Aluminium Alloy) as two metals. This is the most
commonly used general purpose thermocouple. It is inexpensive and, owing to its
popularity, available in a wide variety of probes. They are available in the200C to
+1200C range. Sensitivity is approximately 41 V/C. RTDs are also used but not in
protection systems due to vibrational errors. We pass a constant current through the RTD.
So that if R changes then the Voltage also changes RTDs used in Industries are Pt100 And
Pt1000 Pt100: 0C 100 ( 1 = 2.5 0C ) Pt1000: 0C - 1000 Pt1000 is used for
higher accuracy. The gauges used for Temperature measurements are mercury filled
Temperature gauges. For Analog medium thermocouples are used and for Digital medium
Switches are used which are basically mercury switches.
94. 94 FLOWMEASUREMENT Flow measurement does not signify much and is
measured just for metering purposes and for monitoring the processes ROTAMETERS: A
Rotameter is a device that measures the flow rate of liquid or gas in a closed tube. It is
occasionally misspelled as 'Rotometer'. It belongs to a class of meters called variable area
meters, which measure flow rate by allowing the cross sectional area the fluid travels
through to vary, causing some measurable effect. A rotameter consists of a tapered tube,
typically made of glass, with a float inside that is pushed up by flow and pulled down by
gravity. At a higher flow rate more area (between the float and the tube) is needed to
accommodate the flow, so the float rises. Floats are made in many different shapes, with
spheres and spherical ellipses being the most common. The float is shaped so that it
rotates axially as the fluid passes. This allows you to tell if the float is stuck since it will
only rotate if it is not. For Digital measurements Flap system is used. For Analog
measurements we can use the following methods : 1. Flow meters 2. Venturimeters /
Orifice meters 3. Turbines 4. Massflowmeters(oil level) 5. UltrasonicFlowmeters 6.
Magnetic Flow meter (water level ) Selection of flow meter depends upon the purpose,
accuracy and liquid to be measured so different types of meters used.
95. 95 TURBINE TYPE: They are simplest of all. They work on the principle that on
each rotation of the turbine a pulse is generated and that pulse is counted to get the flow
rate. VENTURIMETERS : Referring to the diagram, using Bernoulli's equation in the
special case of incompressible fluids (such as the approximation of a water jet), and the
theoretical pressure drop at the constriction would be given by (/2)(v2 2 - v1 2 ). And we
know that rate of flow is given by: Flow= k(D.P) Where DP is Differential Pressure or
the Pressure Drop.
96. 96 CONTROL VALVES A valve is a device that regulates the flow of substances
(either gases, fluidized solids, slurries, or liquids) by opening, closing, or partially
obstructing various passageways. Valves are technically pipe fittings, but usually are
discussed separately. Valves are used in a variety of applications including industrial,
military, commercial, residential, transportation. Plumbing valves are the most obvious in
everyday life, but many more are used. Some valves are driven by pressure only, they are
mainly used for safety purposes in steam engines and domestic heating or cooking
appliances. Others are used in a controlled way, like in Otto cycle engines driven by a
camshaft, where they play a major role in engine cycle control. Many valves are
controlled manually with a handle attached to the valve stem. If the handle is turned a
quarter of a full turn (90) between operating positions, the valve is called a quarter-turn
valve. Butterfly valves, ball valves, and plug valves are often quarter-turn valves. Valves
can also be controlled by devices called actuators attached to the stem. They can be
electromechanical actuators such as an electric motor or solenoid, pneumatic actuators
which are controlled by air pressure, or hydraulic actuators which are controlled by the
pressure of a liquid such as oil or water. So there are basically three types of valves that
are used in power industries besides the handle valves. They are : PNEUMATIC
VALVES They are air or gas controlled which is compressed to turn or move them
HYDRAULIC VALVES They utilize oil in place of Air as oil has better compression
MOTORISED VALVES These valves are controlled by electric motors
97. 97 FURNACE SAFEGUARD SUPERVISORY SYSTEM FSSS is also called as
Burner Management System (BMS). It is a microprocessor Based programmable logic
controller of proven design incorporating all protection facilities required for such
system. Main objective of FSSS is to ensure safety of the boiler. The 95 MW boilers are
indirect type boilers. Fire takes place in front and in rear side. Thats why its called front
and rear type boiler. The 210 MW boilers are direct type boilers (which means that HSD
is in direct contact with coal) firing takes place from the corner. Thus it is also known as
corner type boiler. IGNITER SYSTEM Igniter system is an automatic system, it takes the
charge from 110kv and this spark is brought in front of the oil guns, which spray aerated
HSD on the coal for coal combustion. There is a 5 minute delay cycle before igniting, this
is to evacuate or burn the HSD. This method is known as PURGING. PRESSURE
SWITCH Pressure switches are the devices that make or break a circuit. When pressure is
applied, the switch under the switch gets pressed which is attached to a relay that makes
or break the circuit. Time delay can also be included in sensing the pressure with the help
of pressure valves. Examples of pressure valves: 1. Manual valves (tap) 2. Motorized
valves (actuator) works on motor action 3. Pneumatic valve (actuator) - works due to
pressure of compressed air 4. Hydraulic valve