Manual Motor Starters, Controllers, and Protectors: Type GV2, GV3 and GV7
Manual Motor Starters, Controllers, and Protectors: Type GV2, GV3 and GV7
Class 2520
CONTENTS
Description
Page
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Accessories Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
2
2001 Schneider Electric All Rights Reserved
05/01
3
05/01
Standard Features
The GV family offers such standard features as:
UL Listed, CSA Certified, and CE Marked
UL Listed for Group Motor Applications (for more details see page 7)
Overload relay
Class 10, ambient compensated (GV2, GV3)
Class 10, solid state (GV7)
Single phase sensitivity
Magnetic instantaneous short-circuit protection
Test trip mechanism
Provision for padlocking in the OFF position
Standard for GV2, GV3
Requires attachment of rotary handle for GV7
Fingersafe terminals (meets IP20 standards)
North American and European terminal markings
For manual motor starters designed to meet NEMA standards refer to catalog 2510CT9701.
4
2001 Schneider Electric All Rights Reserved
05/01
GV2P
GV3ME
0.1 to 32 A
Up to 20 hp @ 460 V
10 kA short circuit current @ 480 V
Push Button Operator
0.1 to 25 A
Up to 15 hp @ 460 V
50 kA short circuit current @ 480 V
Rotary Handle Operator
Visible Trip Indication
1 to 63 A
Up to 40 hp @ 460 V
50 kA short circuit current @ 480 V
Push Button Operator
Type of protection
Thermal-magnetic
Mounting
Connection
Use a cross-head screwdriver; captive screws. Same screwdriver used for connections on GV2 starters and their add-on blocks.
Marking
Tripping test
ON or OFF state
ON or OFF state
Tripping by overload, short circuit, undervoltage
or shunt trip.
Padlocking
In the OFF position, with padlock, using the system incorporated in the manual control device.
Accessories
Selection
ON or OFF state
Page 9
Page 9
Page 9
GV7RE / GV7RS
25 to 220 A
Up to 150 hp @ 460 V
25 kA short circuit current @ 480 V
Toggle Operator
Type of protection
Mounting
Connection
Marking
On or Off state
Tripping by overload or short circuit
Padlocking
When used with door mounted rotary handle or with separate locking device
Accessories
Selection
Page 10
5
05/01
Max RMS, kA
Max RMS, kA
GV2
GV2
Max RMS, kA
GV3
Max RMS, kA
GV7
Max RMS, kA
GV7
480 V
600 V
480 V
600 V
480 V
600 V
240/480 V
600 V
0.1 - 0.16
ME01
50
30
P01
50
30
240/480 V 600 V
0.16 - 0.25
ME02
50
30
P02
50
30
0.25 - 0.40
ME03
50
30
P03
50
30
0.40 - 0.63
ME04
50
30
P04
50
30
0.63 - 1.0
ME05
50
30
P05
50
30
1.0 - 1.6
ME06
50
30
P06
50
30
ME06
50
23
1.6 - 2.5
ME07
50
30
P07
50
30
ME07
50
23
2.5 - 4.0
ME08
50
30
P08
50
30
ME08
50
23
4.0 - 6.3
ME10
50
30
P10
50
30
ME10
50
23
6 - 10
ME14
30
30
P14
50
30
ME14
50
23
9 - 14
ME16
25
10
P16
50
18
10 - 16
ME20
50
23
13 - 18
ME20
25
10
P20
50
18
16 - 25
ME25
50
23
17 - 23
ME21
10
10
P21
50
18
20 - 25
ME22
10
10
P22
50
18
24 - 32
ME32
10
10
25 - 40
ME40
50
23
RE40
25
10
RS40
65
10
30 - 50
RE50
25
10
RS50
65
10
40 - 63
ME63
50
23
48 - 80
RE80
25
10
RS80
65
10
60 -100
RE100
25
10
RS100
65
10
90 - 150
RE150
25
10
RS150
65
10
132 - 220
RE220
25
10
RS220
65
10
When used with GV1L3 Current Limiter Max kA RMS at 480 V is 50 kA and at 600 V 30 kA.
For Spring terminals add 3 to the catalog number. Example: GV2ME013.
6
2001 Schneider Electric All Rights Reserved
05/01
Motor
D-Line or K-Line Contactor
Selecting the proper upstream short circuit protection for Group Motor installations can sometimes be
a confusing process. Specific National Electric Code rules must be applied for Group Motor installations.
The examples below illustrate the most common applications of GV manual starters with upstream short
circuit protection in a Group Motor installation. Refer to NEC Section 430-53 C and D for proper
conductor ampacity selection.
NOTE: Examples below show full load currents that may not be typical. Use actual motor nameplate
date for determining actual values.
Example 1:
Eight motors with the sizes shown below are installed on a conveying system. Choose the correct GV
manual starter and the proper size short circuit protection for this application. The user prefers timedelay fuses.
Motor Qty
HP
Voltage
FLA
460
7.6
460
4.8
460
3.4
One GV2M14, two GV2M10, and five GV2M08 manual starters would be selected for this group motor
installation.
Per N.E.C. section 430-52 & -53 and N.E.C. table 430-152, the time-delay fuse must be sized as follows:
175% FLA for largest motor + sum of FLAs for all other motors
==> (1.75 x 7.6) + (2 x 4.8) + (5 x 3.4) = 39.9 A
N.E.C. 430-52 allows use of the next largest standard size fuse which in this case is 40 A. If nuisance
tripping, a problem with this fuse selection, N.E.C. does allow 225% of largest motor FLA to be used in
lieu of 175% when calculating the size. In this case, the calculation would be as follows:
(2.25 x 7.6) + (2 x 4.8) + (5 x 3.4) = 43.7 A
HP
Voltage
10
460
FLA
14
460
7.6
460
4.8
460
3.4
Per N.E.C. section 430-52 & -53 and N.E.C. table 430-152, the circuit breaker must be sized as follows:
250% FLA for largest motor + sum of FLAs for all other motors
==> (2.5 x 14) + 14 +7.6 + (2 x 4.8) + (5 x 3.4) = 83.2 A
The next largest standard size in this case is a 110 A circuit breaker.
7
05/01
Contactor
Max. Available
Fault Current (kA)
at 460 Vac (1)
GV2P02
LC1D09
50
GV2P03
LC1D09
50
GV2P04
LC1D09
50
0.5
GV2P05
LC1D09
50
0.75
GV2P06
LC1D09
50
0.5
0.5
GV2P07
LC1D09
50
200 V
230 V
460 V
0.75
GV2P08
LC1D09
50
1.5
1.5
GV2P10
LC1D09
50
GV2P14
LC1D09
50
10
GV2P16
LC1D25
50
10
GV2P20
LC1D25
50
7.5
15
GV2P21
LC1D25
30
7.5
15
GV2P22
LC1D32
30
10
10
30
GV3M40
LC1D40
20
40
GV3M63
LC1D115
20
(1)
8
2001 Schneider Electric All Rights Reserved
05/01
GV2ME
Pushbutton
GV2P
Rotary Handle
Setting Range of
Thermal Trips (A)
Single Phase
115 V HP
230 V HP
200 V HP
230 V HP
460 V HP
575 V HP
0.11 - 0.16
0.016 - 0.25
0.25 - 0.40
0.40 - 0.63
0.63 - 1
1 - 1.6
1.6 - 2.5
2.5 - 4
4 - 6.3
6 - 10
9 - 14
13 - 18
17 - 23
20 - 25
24 - 32
1/8
1/4
1/2
3/4
1
1-1/2
2
2
1/10
1/6
1/3
1/2
1-1/2
2
3
3
3
5
1/2
3/4
1-1/2
2
3
5
5
5
10
1/2
1
1-1/2
3
3
5
7-1/2
7-1/2
10
1/2
3/4
1
2
3
5
10
10
15
15
20
1/2
1
1-1/2
3
5
7-1/2
10
15
20
20
30
GV2ME01
GV2ME02
GV2ME03
GV2ME04
GV2ME05
GV2ME06
GV2ME07
GV2ME08
GV2ME10
GV2ME14
GV2ME16
GV2ME20
GV2ME21
GV2ME22
GV2ME32
1 - 1.6
1.6 - 2.5
2.5 - 4
4-6
6 - 10
10 - 16
16 - 25
25 - 40
40 - 63
1/8
1/4
1/2
1
2
3
5
1/10
1/16
1/3
1/2
1-1/2
2
3
7-1/2
10
1/2
3/4
1-1/2
2
3
5
10
20
1/2
1
1-1/2
3
5
7-1/2
10
20
3/4
1
2
3
5
10
15
30
40
1
1-1/2
3
7-1/2
10
20
30
60
GV3ME06
GV3ME07
GV3ME08
GV3ME10
GV3ME14
GV3ME20
GV3ME25
GV3ME40
GV3ME63
GV2ME
Three Phase
GV2P01
GV2P02
GV2P03
GV2P04
GV2P05
GV2P06
GV2P07
GV2P08
GV2P10
GV2P14
GV2P16
GV2P20
GV2P21
GV2P22
GV2ME3
GV2P
GV3ME
File E164864
CCN NLRV
File LR 81630
Class 3211 05
9
05/01
IEC
Breaking
Capacity
at 415 V
3 PH
Weight /
kg (lbs)
115 V HP
230 V HP
230 V HP
460 V HP
12 20
10
15
GV7RE20
2.010 (4.43)
15 25
7.5
15
20
GV7RE25
2.010 (4.43)
25 40
7.5
10
30
30
GV7RE40
2.010 (4.43)
10
15
30
40
GV7RE50
2.015 (4.44)
48 80
7.5
15
30
60
75
GV7RE80
2.040 (4.5)
60 100 A
10
15
30
75
100
GV7RE100
2.040 (4.5)
90 150 A
15
30
50
100
150
GV7RE150
2.020 (4.45)
15
50
75
150
200
GV7RE220
2.350 (5.18)
12 20
10
15
GV7RS20
2.010 (4.43)
15 25
7.5
15
20
GV7RS25
2.010 (4.43)
25 40 A
7.5
10
30
30
GV7RS40
2.010 (4.4)
30 50 A
10
15
30
40
GV7RS50
2.015 (4.44)
7.5
15
30
60
75
GV7RS80
2.040 (4.5)
60 100 A
10
15
30
75
100
GV7RS100
2.040 (4.5)
90 150 A
15
30
50
100
150
GV7RS150
2.020 (4.45)
132 220 A
15
50
75
150
200
GV7RS220
2.350 (5.18)
30 50
132 220 A
48 80 A
25 kA
35 kA
65 kA
200 V HP
Catalog
Number
575 V HP
10
2001 Schneider Electric All Rights Reserved
05/01
GV2V02
GV1L3
GV2AK00
GV2ME
GV2AD
GV2AM11
GV2AU
GV2P
GV2AM11
GV2AS
LS1D30
GV2AE11, AE20
GV2AE1
GV2AN
GV2AE1
GV2AN
Mounting Location
Contact Type
Sold in Lots Of
Catalog Number
Weight / kg (lbs)
10
10
10
1
1
1
1
1
1
1
GV2AE1
GV2AE11
GV2AE20
GV2AN11
GV2AN20
0.015 (0.03)
0.020 (0.04)
0.020 (0.04)
0.050 (0.11)
0.050 (0.11)
0.055 (0.12)
0.055 (0.12)
0.055 (0.12)
0.055 (0.12)
0.045 (0.10)
Front (3)
Instantaneous auxiliary contacts
Left Hand Side
1
Left Hand Side
(1)
(2)
(3)
N.O. + N.C.
N.O. + N.O.
N.O. (fault) + N.O.
N.O. (fault) + N.C.
N.C. (fault) + N.O.
N.C. (fault) + N.C.
SPDT
GV2AD1010 GV2AD1001
GV2AD0110 GV2AD0101
GV2AM11
Mounting of a GVAE contact block or a GV2AK00 visible isolation block on GV2P and GV2L.
Choice of N/C or N/O contact operation, depending on which way round the reversible block is mounted.
The GVAD is always mounted next to the circuit-breaker.
For Spring terminals add 3 to the catalog number. Example: GV2ME013.
11
05/01
Electric Trips
Discription
Voltage
Hz
Catalog Number
Weight lb (kg)
50 Hz
GVA/025
0.23 (0.105)
60 Hz
GVA/026
0.23 (0.105)
50 Hz
GVA/055
0.23 (0.105)
60 Hz
GVA/056
0.23 (0.105)
50 Hz
GVA/107
0.23 (0.105)
Side
(1 block on RH side
of GV2)
60 Hz
GVA/107
0.23 (0.105)
50 Hz
GVA/115
0.23 (0.105)
60 Hz
GVA/116
0.23 (0.105)
120127 V
50 Hz
GVA/125
0.23 (0.105)
127 V
60 Hz
GVA/115
0.23 (0.105)
200 V
50 Hz
GVA/207
0.23 (0.105)
200 V220 V
220 V240 V
380 V400 V
60 Hz
GVA/207
0.23 (0.105)
50 Hz
GVA/225
0.23 (0.105)
60 Hz
GVA/226
0.23 (0.105)
50 Hz
GVA/385
0.23 (0.105)
60 Hz
GVA/386
0.23 (0.105)
50 Hz
GVA/415
0.23 (0.105)
415 V
60 Hz
GVA/416
0.23 (0.105)
440 V
60 Hz
GVA/385
0.23 (0.105)
415 V440 V
480 V
60 Hz
GVA/415
0.23 (0.105)
500 V
50 Hz
GVA/505
0.23 (0.105)
600 V
60 Hz
GVA/505
0.23 (0.105)
50 Hz
GVAX115
0.24 (0.110)
60 Hz
GVAX116
0.24 (0.110)
60 Hz
GVAX115
0.24 (0.110)
50 Hz
GVAX225
0.24 (0.110)
60 Hz
GVAX226
0.24 (0.110)
50 Hz
GVAX385
0.24 (0.110)
220240 V
380400 V
60 Hz
GVAX386
0.24 (0.110)
415440 V
50 Hz
GVAX415
0.24 (0.110)
440 V
60 Hz
GVAX385
0.24 (0.110)
Mounting
Maximum number
Catalog Number
Weight lb (kg)
Front (3)
GV2AK00
0.33 (0.150)
GV13
0.29 (0.130)
Independent
LA9LB920
0.70 (0.320)
Limiters
(1) To order an undervoltage trip: replace the dot (/) with a U, example: GVAU025. To order a shunt trip: replace the dot (/) with an S, example: GVAS025.
(2) Visible isolation of the 3 poles upstream of circuit-breaker GV2P and GV2L.
(3) Mounting of a GVAE contact block or a GV2AK00 visible isolation block on GV2P and GV2L.
For Use In
Sold in
Lots of
Catalog Number
Weight
lb (kg)
0.5 (0.23)
US Markets
LS1D30
US Markets
LS1D303
0.5 (0.23)
European Markets
LS1D32
0.5 (0.23)
European Markets
LS1D323
0.5 (0.23)
European Markets
LS1DT32
0.5 (0.23)
12
2001 Schneider Electric All Rights Reserved
05/01
GV2-G454
GV2-G254
LAD-31
GV1-G09
GV2-G454
LAD-31
GV2-G254
GV1-G10
GV2-G05
LA9-E07
GV2-AF01
GV2-AF4
GV2-AF3
GK2-AF01
GV2-GA01
GV2-AF02
GV1-G02
GV2-AP0 2
.
TRIP
T
RESE
GV2-V03
13
05/01
Mounting Accessories
Description
Application
Sold in Lots Of
Catalog Number
Weight / kg (lbs)
10
GK2AF01
0.120 (0.26)
10
GV2AF02
0.021 (0.05)
LAD31
0.040 (0.09)
10
GV1F03
0.003 (0.01)
10
GV2AF01
0.020 (0.04)
10
GV2AF3
0.016 (0.03)
Between GV2/LS1D30
mounted on LAD31 and
contactor LC1D09 to D30
19
GV2AF4
0.016 (0.03)
Adaptor plate
Combination block
Wiring Accessories
Description
Number of GVS
to be Mounted
Number of Side
Mounted-Auxiliary
Blocks on Each
GV Starter
Busbar
Pitch (mm)
Sold in
Lots Of
Catalog
Number
Weight /
kg (lbs)
none
45
GV2G245
0.036 (0.08)
1 GV2AN, AM, AD
54
GV2G254
0.038 (0.84)
72
GV2G272
0.042 (0.09)
None
45
GV2G345
0.052 (0.12)
1 GV2AN, AM, AD
54
GV2G354
0.060 (0.13)
None
45
GV2G445
0.077 (0.17)
1 GV2AN, AM, AD
54
GV2G454
0.085 (0.19)
72
GV2G472
0.094 (0.21)
1 GV2AN, AM, AD
54
GV2G554
0.100 (0.22)
Application
Sold in
Lots Of
Catalog
Number
Weight /
kg (lbs)
GV1G10
0.005 (0.02)
GV1G09
0.040 (0.09)
GV2G05
0.115 (0.25)
10
LA9E07
0.005 (0.01)
Flexible 3-pole
connector
10
GV1G02
0.013 (0.03)
100
LA9D92
0.001 (0.02)
Sets of 3-pole, 63 A
busbars
Description
Catalog Number
Weight / kg (lbs)
GV2AP01
0.200 (0.44)
GV2AP02
0.200 (0.44)
GV2V03
0.130 (0.29)
Padlocking Device
For all GV2 devices
14
2001 Schneider Electric All Rights Reserved
05/01
GV2V01
GV2MC
GV2K
GV2MP
GV2E01
GV2SN
15
05/01
GV2ME Enclosures
Application
Type
Surface mounting,
double insulated with
protective (sealable) cover.
Degree of Protection
of Enclosure
Catalog Number
Weight / kg (lbs)
IP 41
GV2MC01
0.290 (0.64)
IP 55
GV2MC02
0.300 (0.66)
IP 55 for
temperature < + 5 C
GV2MC03
0.300 (0.66)
GV2MP01
0.115 (0.25)
IP 41 (reduced size)
GV2MP03
0.115 (0.25)
IP 55 (full size)
GV2MP02
0.130 (0.29)
IP 55 (reduced size)
GV2MP04
0.130 (0.29)
Front Plate
Degree of Protection
of Enclosure
Application
Padlocking device (1)
for GV2M operator
(padlocking is only
possible in the O
position)
Spring return
Mushroom head stop
pushbutton (1) 40
mm, red
Weight / kg (lbs)
GV2V01
0.075 (0.17)
GV2K011
0.052 (0.11)
GV2K021
0.100 (0.22)
Turn to release
GV2K031
0.052 (0.11)
Turn to release
GV2K04
0.120 (0.26)
IP 55
10
GV2E01
For enclosures
and front plate
0.120 (0.26)
10
GV2E02
0.120 (0.26)
10
GV2N01
0.030 (0.06)
Sold in Lots Of
Catalog
Number
Weight / kg (lbs)
Green
10
GV2SN13
0.019 (0.06)
Red
10
GV2SN14
0.019 (0.06)
Orange
10
GV2SN15
0.019 (0.06)
Clear
10
GV2SN17
0.019 (0.06)
Green
10
GV2SN23
0.019 (0.06)
Red
10
GV2SN24
0.019 (0.06)
Orange
10
GV2SN25
0.019 (0.06)
Clear
10
GV2SN27
0.019 (0.06)
Green
10
GV2SN33
0.019 (0.06)
Red
10
GV2SN34
0.019 (0.06)
Orange
10
GV2SN35
0.019 (0.06)
Clear
10
GV2SN37
0.019 (0.06)
Neutral link
Description
Catalog
Number
Latching
Latching/Padlockable
Sealing kit
Sold in Lots Of
Voltage
Color
110 V
220/240 V
380/440 V
16
2001 Schneider Electric All Rights Reserved
05/01
Characteristics
Voltage
Sold in Lots Of
Catalog
Number
Weight /
kg (lbs)
GV3B11
0.070 (0.15)
220, 240 V 50 Hz
240, 277 V 60 Hz
GV3B22
0.070 (0.15)
380, 415 V 50 Hz
480 V 60 Hz
GV3B38
0.070 (0.15)
GV3D11
0.070 (0.15)
220, 240 V 50 Hz
240, 277 V 60 Hz
GV3D22
0.070 (0.15)
380, 415 V 50 Hz
480 V 60 Hz
GV3D38
0.070 (0.15)
GV3B
Shunt trips
GV1A01
Instantaneous auxiliary
contact blocks
GV1A01
0.060 (0.13)
(1 per breaker)
(side-mounted)
N.O. + N.O.
GV1A02
0.060 (0.13)
GV1A03
0.070 (0.15)
GV1A05
0.070 (0.15)
GV1A06
0.070 (0.15)
GV1A07
0.070 (0.15)
N.C.
GV3A08
0.030 (0.70)
(internal mount)
N.O.
GV3A09
0.030 (0.70)
GV1V02
0.010 (0.01)
Metal Enclosure
GV3CE01
Application
Type
Degree of Protection
of Enclosure
Catalog Number
Weight / kg (lbs)
Surface mounting
IP 55
GV3CE01
2.000 (4.41)
Reference
Characteristics
Sold in Lots Of
Catalog
Number
LA9D40959
Weight /
kg (lbs)
0.001 (0.01)
IP 55 padlocking device for operators (when padlocked, the motor circuit is automatically in the Open (OFF) position) GV1V01
0.044 (0.10)
Mushroom head
stop pushbutton (2)
40 mm, red
Spring return
Latching
Latching/Padlockable
GV1K01
0.052 (0.11)
0.095 (0.21)
GV1K02
Turn to release
GV1K03
0.052 (0.11)
Turn to release
GV2K04
0.095 (0.22)
DE1DS4091
0.001 (0.01)
GV3CE01
17
05/01
GV7AC02
GV7AC04
GV7RE, RS
GV7AC01
GV7AC04
Standard manual controllers and protectors include terminal and device mounting hardware. Cable
clamps and accessories should be selected from the table below.
Cabling Accessories
Application
Sold in
Lots Of
Catalog Number
Weight / kg (lbs)
GV7AC021
0.300 (0.66)
For GV7R220
1.5185 mm2 (#14 to 350 mcm).
GV7AC022
0.350 (0.77)
GV7AC03
0.180 (0.40)
GV7AC01
0.125 (0.28)
Phase Barriers
GV7AC04
0.075 (0.17)
Insulating Screens
GV7AC05
0.075 (0.17)
GV7AC06
0.550 (1.21)
Description
Clip-On Connectors
Spreaders
18
2001 Schneider Electric All Rights Reserved
05/01
2
1
GV7AE11, AB11
GV7RE, RS
GV7AU, AS
GV7AD
Function
N.O./N.C. contact
Application
Indicates the position of the starter poles.
Trip indication
Indicates that the starter has tripped due to an overload, short-circuit, differential fault, operation of a voltage
release (under voltage or shunt release), or by the push to trip button. It resets when the starter is reset.
Electrical fault
indication
Indicates that the starter has tripped due to an overload, short-circuit, or differential fault. It resets when the starter
is reset.
N.O./N.C. Contact
Type
Voltage
Catalog Number
Weight / kg (lbs)
Standard
GV7AE11
0.015 (0.03)
Low level
GV7AB11
0.015 (0.03)
19
05/01
Catalog Number
Weight / kg (lbs)
GV7AD111
0.100 (0.22)
110240 VAC/DC
GV7AD112
0.100 (0.22)
Type
Undervoltage Trip
Shunt Trip
Voltage
Catalog Number
Weight / kg (lbs)
48V, 50 Hz
GV7AU055
0.105 (0.23)
110130 V, 50/60 Hz
GV7AU107
0.110 (0.24)
200240 V, 50/60 Hz
GV7AU207
0.110 (0.24)
380440 V, 50/60 Hz
GV7AU387
0.105 (0.23)
525 V, 50 Hz
GV7AU525
0.100 (0.22)
48V, 50 Hz
GV7AS055
0.105 (0.23)
110130 V, 50/60 Hz
GV7AS107
0.110 (0.24)
200240 V, 50/60 Hz
GV7AS207
0.110 (0.24)
380440 V, 50/60 Hz
GV7AS387
0.105 (0.23)
525 V, 50 Hz
GV7AS525
0.100 (0.22)
20
2001 Schneider Electric All Rights Reserved
05/01
GV7AP03
ON
GV7RE, RS
GV7AP04
OFF
ON
ON
OFF
OFF
ON
GV7AP05
OFF
GV7AP01, AP02
ON
OFF
ON
GV7V01
OFF
21
05/01
Description
Type
Catalog Number
Weight / kg (lbs)
GV7AP03
0.205 (0.45)
GV7AP04
0.205 (0.45)
GV7AP05
0.100 (0.22)
Conversion Accessory
This conversion accessory makes it impossible to open the door if the device is closed and prevents the device from being closed if the door is open.
Description
Type
Catalog Number
Weight / kg (lbs)
GV7AP01
0.775 (1.71)
GV7AP02
0.775 (1.71)
Locking Device
The locking device allows controllers without a rotary handle installed, to be locked in the O (Off) position
by a padlock. As many as 3 padlocks with a shank diameter of 5 to 8 mm (0.2 to 0.3 in) can be used.
The padlocks are not supplied. Refer to the diagram on page 21.
Description
Application
Catalog Number
Weight / kg (lbs)
Locking Device
GV7V01
0.100 (0.22)
22
2001 Schneider Electric All Rights Reserved
05/01
LS1D30, LS1D303
LS1D32, LS1DT32,
LS1D323
Type
GV2ME
Conforming to standards
IEC 60947-1, 60947-2, 60947-4-1, EN 60204, BS 4752, BS 4941, UL 508, CSA C22.2 No. 14, NF C 63-650, NFC63-120, 79-130, VDE 0113, 0660.
Product approvals
UL File Number
Protective treatment
Degree of protection
conforming to IEC 60529
In enclosure GV2ME01:
IP 41 In enclosure GV2ME02: IP 55
Shock resistance
conforming to IEC 60068-2-27
BV
TH
TH
30 g
30 g
Vibration resistance
conforming to IEC 60068-2-6
5 g (5 to 150 Hz)
5 g (5 to 150 Hz)
- operation
-4 to +140 F (-20 to + 60 C)
-58 to +158 F
(-50 to +70 C)
-58 to +158 F
(-50 to +70 C)
Temperature compensation
-4 to +140 F (-20 to + 60 C)
Flame resistance
conforming to IEC 60695-2-1
1760 F (960 C)
6562 ft (2000 m)
6562 ft (2000 m)
23
Max
Min
90
90
90
30 30
90
90
90
UL, CSA
Operating positions
in relation to normal
vertical mounting position
Wiring
Number of conductors and
cross
Max
Min
Max
Min
Yes
Tightening torque
Resistance to
mechanical impact
0.5 J
Yes
No
No
No
No
0.5 J
23
05/01
GV2ME
GV2P
Utilization category
conforming to IEC 60947-2
AC-3
AC-3
LS1D30, LS1D303
LS1D32, LS1DT32,
LS1D323
AC 20B#
690
690
690
600 (B600)
Hz
50/60
50/60
50/60
50/60
kV
2.5
2.5
3.2
3.2
Mechanical life
(ops: closing, opening)
ops
100 000
100 000
Electrical life
for AC-3 duty
ops
100 000
100 000
Duty class
(maximum operating rate)
ops/h
25
25
Continuous
duty
Rated duty
conforming to IEC 60947-4-1
24
2001 Schneider Electric All Rights Reserved
05/01
GV2AU
GV2AS
690
690
Operational voltage
conforming to IEC 60947-1
0.85-1.1 Ue
0.7-1.1 Ue
Drop-out voltage
0.35-0.7 Ue
0.2-0.75 Ue
Inrush consumption
VA
12
14
10.5
VA
3.5
1.1
1.6
msec
From the moment the voltage reaches its operational value until opening of the GV210-15
Sealed consumption
Operating time
conforming to IEC 60947-1
On-load factor
100%
Wiring
Number of conductors and cross
Min
Max
Tightening torque
Mechanical life
(ops: closing-opening)
ops
100 000
25
05/01
690
690
600
300
2.5
Mechanical life
(ops: closing-opening)
ops
100 000
1000
AC-14/1000 ops
48
110
127
230
240
380
415
440
500
690
24
48
110
127
230
240
300
500
720
850
650
500
400
36
48
72
72
VA
3000
7000
13 000
15 000
13 000
12 000
9000
220
300
450
450
4.5
3.3
2.2
1.5
0.6
1.5
0.5
0.3
DC-13/1000 ops
24
48
60
110
240 (1)
24
48
60
140
240
180
140
120
24
15
240
360
240
210
180
100
50
50
1.3
0.5
0.3
0.15
17
mA
Min
Max
Tightening torque
(1) Add an RC circuit type LA4 D to the load terminals, see Square D Digest.
26
2001 Schneider Electric All Rights Reserved
05/01
300
2.5
Mechanical life
ops
100 000
24
48
110
127
230
240
VA
48
60
120
120
VA
480
600
1270
2400
1.25
0.5
24
48
60
24
15
100
50
50
0.3
0.15
Number of faults for n million operating cycles (17 V-5 mA): = 10-6
Min
Max
Max
Tightening torque
mm2)
Power Pole
Contact operation
instantaneous auxiliary contacts
Contact open
GV2AN20
N.O.
N.O.
Contact closed
GV2AN11
N.O.
N.C.
Operation of fault
signalling contacts
GV2AE1
N.O.
N.C.
GV2AE20
N.O.
N.O.
GV2AM11
Change of state
following tripping on
short circuit.
GV2AE11
N.O.
N.C.
GV2AD10
N.O.
GV2AD01
N.C.
27
05/01
690
63
kA
11
kA2s
104
Degree of protection
IP 20
690
63
Degree of protection
IP 20
Wiring
Solid cable
Tightening torque
Connector
Screw clamp
690
63
Operating threshold
rms current
Wiring
Solid cable
Tightening torque
28
2001 Schneider Electric All Rights Reserved
05/01
Time (s)
10 000
1000
100
1
10
2
3
0,1
0,01
0,001
1
1,5
10
100
x setting current (Ir)
1
2
3
29
05/01
0.
0 .2
2
0.
3
=
10 000
0.
0.
0.
co
0.
95
1000
10
100
100
1
2
3
4
5
I peak max.
20-25 A
17-23 A
13-18 A
9-14 A
1000
6
7
8
9
10
11
100 000
Prospective Isc (A)
6-10 A
4-6.3 A
2.5-4 A
1.6-2.5 A
1-1.6 A
Limit of rated ultimate breaking capacity on short circuit of GV2M
(14, 18, 23 and 25 Amp ratings)
30
2001 Schneider Electric All Rights Reserved
05/01
1
2
3
4
5
6
10
0,1
0,01
0,1
1
2
3
4
5
20-25 A
17-23 A
13-18 A
9-14 A
6-10 A
10
6
7
8
9
100
Prospective Isc (kA)
4-6.3 A
2.5-4 A
1.6-2.5 A
1-1.6 A
31
05/01
1
2
3
4
5
6
10
0,1
0,01
0,1
1
2
3
4
5
20-25 A
17-23 A
13-18 A
9-14 A
6-10 A
10
6
7
8
9
100
Prospective Isc (kA)
4-6.3 A
2.5-4 A
1.6-2.5 A
1-1.6 A
32
2001 Schneider Electric All Rights Reserved
05/01
Rating
230/
240 V
Icu
400/
415 V
Icu
440 V
Icu
Icu
Icu
Associated fuses
(if required)
if Isc > breaking
capacity Icu
conforms to
IEC 60947-2
400/
415 V
440 V
500 V
690 V
P16
P20
P21
P22
6.3
10
14
18
23
25
0.1
to
1.6
2.5
6.3
10
14
18
23
25
kA
50
50
100
100
15
15
15
15
50
50
50
50
50
40
40
50
50
50
50
15
50
20
20
20
100
100
50
50
50
50
75
75
75
75
50
10
50
42
10
10
10
100
100
75
75
75
75
100
75
75
75
75
75
75
75
75
75
75
75
75
100
100
100
100
100
100
100
100
kA
kA
kA
kA
Ics
% (1)
230/
240 V
P14
Ics
% (1)
690 V
P10
2.5
Ics
% (1)
500 V
P08
0.1 to
1.6
Ics
% (1)
Breaking capacity
conforms to
IEC 60947-2
P07
Ics
% (1)
f
(1)
GV2
ME01
P01
to
ME07 ME08 ME10 ME14 ME16 ME20 ME21 ME22 to
ME06
P06
Type
aM
80
80
gl
100
100
aM
63
63
80
80
100
100
100
gl
80
80
100
100
125
125
125
aM
50
50
50
50
63
63
50
63
80
80
gl
63
63
63
63
80
80
63
80
100
100
aM
50
50
50
50
50
50
50
50
50
50
50
gl
63
63
63
63
63
63
63
63
63
63
63
aM
16
25
32
32
40
40
40
40
20
25
40
40
50
50
50
50
gl
20
32
40
40
50
50
50
50
25
32
50
50
63
63
63
63
33
05/01
GV2
ME01
to
ME06
Rating
230/240 V
Icu
Breaking capacity
conforms
to IEC 60947-2
Icu
Icu
Icu
ME14
ME16
ME20
ME21
ME22
0.1 to 1.6
2.5
6.3
10
14
18
23
25
100
100
100
100
50
50
40
40
kA
50
20
20
20
75
75
75
75
kA
50
42
10
10
10
100
100
75
75
75
P07
P08
P10
P14
P16
P20
P21
P22
kA
Ics
% (1)
500 V
ME10
Ics
% (1)
440 V
ME08
kA
Ics
% (1)
400/415 V
ME07
Ics
% (1)
GV2
P01
to
P06
Type
Rating
0.1 to 1.6
2.5
6.3
10
14
18
23
25
kA
kA
100
100
100
100
50
50
50
50
kA
100
100
100
100
100
50
50
50
50
50
ME01
to
ME06
ME07
ME08
ME10
ME14
ME16
ME20
ME21
ME22
0.1 to 1.6
2.5
6.3
10
14
18
23
25
0.04 in2
1 mm2
(3)
(3)
(3)
10kA
6 kA
(2)
(2)
(2)
(2)
(c.s.a.) protected to 40 C at
0.06 in2
1.5 mm2
(3)
(3)
(3)
20kA
10 kA
(2)
(2)
(2)
(2)
Isc max
0.10-0.24 in
2.5-6 mm
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
230/240 V
Icu
Ics
% (1)
400/415 V
Breaking capacity
conforms
to IEC 60947-2
Icu
kA
Ics
% (1)
440 V
Icu
Ics
% (1)
500 V
Icu
Ics
% (1)
GV2
Type
Rating
Cable protection against thermal stress
in the event of short circuit
(PVC insulated copper cables)
Minimum cross sectional area
34
2001 Schneider Electric All Rights Reserved
05/01
Approvals
UL File Number
Protective treatment
TC
GV3ME open-mounted: IP 20
22 g for 20 ms duration
Operation
Open
Enclosed
-4 to +140 F (-20 to + 60 C)
-4 to +104 F (-20 to + 40 C)
Open
Enclosed
-4 to +140 F (-20 to + 60 C)
-4 to +104 F (-20 to + 40 C)
Temperature compensation
Without derating
90
90
90
90
Flame resistance
Operating position
Type
Wiring
Number of conductors and cross
sectional area (c.s.a.)
Solid cable
Min
Max
Min
mm2)
Tightening Torque
mm2)
mm2)
Max
44 lb-in (5 Nm)
Technical Characteristics
Type
690
Conforming to
CSA C 22.2 No. 14 and UL 508
600 (B600)
63
ops
100 000
50 000
ops
100 000
50 000
ops/h
25
Mechanical life
Electrical life
ops: Closing-opening
Maximum operating rate
Sensitivity to phase failure
AC-3 duty
35
05/01
690
600 (B600)
Pick-up voltage
0.8-1.1 Un
Drop-out voltage
0.7-0.35 Un
Inrush consumption
12 VA (7 W)
Sealed consumption
7 VA (2.5 W)
ms
On-load factor
Wiring
Number of conductors and cross
sectional (c.s.a.)
Solid cable
Min
Max
(1) From the disappearance of Ue at the trip terminals to opening of the GV3.
36
2001 Schneider Electric All Rights Reserved
05/01
690
690
conforming to
CSA C22.2 No. 14 and UL 508
600 (B600)
600 (B600)
conforming to
CSA C22.2 No.14 and UL 508
5 (B600)
5 (B600)
Mechanical life
ops
100 000
1000
110
127
48
220
240
380
415
440
500
690
48
110
127
220
240
380
415
440
500
690
Operational power
VA
350
500
800
850
700
700
400
240
460
800
850
450
450
200
VA
4000
12 000
20 000
20 000
15 000
15 000
10 000
2400
8000
12 000
15 000
12 000
12 000
8000
4.5
3.5
2.2
1.5
1.5
0.6
3.6
3.5
2.2
0.3
24
48
60
110
220
24
48
60
110
220
Operational power
180
240
180
140
120
120
120
90
70
60
240
360
240
210
180
180
180
135
105
90
1.3
0.5
2.5
1.5
0.7
0.3
Power poles:
0
GV1A01, A07
O
F
Contact operation
GV1A02
F
F
O = N.C.
F = N.O.
GV1A03
F
F
O
F
F
F
GV1A05
GV1A06
Contact:
F
F
Open
Closed
Type
Wiring
Number of conductors
Min
Max
Min
Max
37
05/01
10 000
1000
100
1
2
10
0,1
0,01
0,001
1
10
100
X setting current (Ir)
1
2
3
4
38
2001 Schneider Electric All Rights Reserved
05/01
100
0 .2
0.
0.
4
5
0.
10
0.
0.
co
0.
95
10
0,1
0,1
10
15
100
Prospective Iso (kA)
1
2
3
4
5
I peak max
40-63 A
25-40 A
16-25 A
10-16 A
6
7
8
9
10
6-10 A
4-6 A
2.5-4 A
1.6-2.5 A
1-1.6 A
39
05/01
100
1
2
3
4
10
0,1
0,1
10
15
100
Prospective Isc (kA)
1
2
3
4
40-63 A
25-40 A
16-25 A
10-16 A
5
6
7
8
6-10 A
4-6 A
2.5-4 A
1.6-2.5 A
40
2001 Schneider Electric All Rights Reserved
05/01
GV3
Type
ME08
ME10
ME14
ME20
ME25
ME40
ME63
100
230 V
kA
100
100
100
100
100
100
100
400/415 V
kA
100
100
100
100
100
100
35
35
440 V
kA
100
100
100
25
25
25
25
25
500 V
kA
100
100
100
690 V
kA
100
aM
gl
aM
250
315
gl
315
400
aM
125
160
200
250
315
gl
160
200
250
315
400
aM
80
100
125
160
200
gl
100
125
160
200
250
aM
40
50
80
100
125
160
200
gl
50
63
100
125
160
200
250
230 V
400/415 V
440 V
500 V
690 V
ME06
and
ME07
41
05/01
Approvals
Protective Treatment
TC
Degree of Protection
conforming to IEC 60529
Temperature Compensation
90
90
90
90
Operating Position
Yes
Vibration Resistance
2.5 gn at 25 Hz
Cabling Characteristics
Connection to Bars, and Cables with Lugs or Bare Cables
GV7R 220
Type
without spreaders
35 mm (1.4 in)
35 mm (1.4 in)
35 mm (1.4 in)
with spreaders
45 mm (1.8 in)
45 mm (1.8 in)
45 mm (1.8 in)
6 (0.24 in)
6 mm (0.24 in)
6 mm (0.24 in)
25 (1 in)
25 mm (1 in)
25 mm (1 in)
10 (0.39 in)
10 mm (0.39 in)
10 mm (0.39 in)
size
M6
M8
M8
tightening torque
10 Nm (7.5 lb.-ft.)
15 Nm (11.3 lb.-ft.)
15 Nm (11.3 lb.-ft.)
height
20 mm (0.78 in)
Pitch
Screws
Bare Cables
(Copper or Aluminum)
with Connectors
mm2
cross-sectional area
1.5
(#16 AWG)
tightening torque
15 Nm (11.3 lb.-ft.)
20 mm (0.78 in)
20 mm (0.78 in)
1.595 mm2
(#16-#3/0 AWG)
1.5185 mm2
(#16-350 mcm AWG)
15 Nm (11.3 lb.-ft.)
15 Nm (11.3 lb.-ft.))
42
2001 Schneider Electric All Rights Reserved
05/01
Technical Characteristics
GV7
Type
RE40RE100
RS40RS100
RE150
RS150
RE220
RS220
Utilization Category
AC-3
AC-3
AC-3
690 V
690 V
690 V
750 V
750 V
750 V
50/60 Hz
50/60 Hz
50/60 Hz
8 kV
8 kV
8 kV
5W
8.7 W
14.5 W
50,000 C.O.
40,000 C.O.
20,000 C.O.
440 V
In/2
50,000 C.O.
40,000 C.O.
20,000 C.O.
440 V
In
30,000 C.O.
20,000 C.O.
10,000 C.O.
Continuous duty
Continuous duty
Continuous duty
Electrical Durability
Rated Duty Conforming to IEC 60947-4-1
GV7
Type
RE40RE100
RE150
RS150
RE220
RS220
2540 A to 60100 A
90150 A
90150 A
132220 A
132220 A
Icu
85 kA
100 kA
85 kA
100 kA
85 kA
100 kA
Ics%
100%
100%
100%
100%
100%
100%
Icu
25 kA
70 kA
35 kA
70 kA
35 kA
70 kA
Ics%
100%
100%
100%
100%
100%
100%
Icu
25 kA
65 kA
35 kA
65 kA
35 kA
65 kA
Ics%
100%
100%
100%
100%
100%
100%
Icu
18 kA
50 kA
30 kA
50 kA
30 kA
50 kA
Ics%
100%
100%
100%
100%
100%
100%
Icu
8 kA
10 kA
8 kA
10 kA
8 kA
10 kA
Ics%
100%
100%
100%
100%
100%
100%
Rating
230/240 V
400/415 V
Breaking Capacity
Conforming to
IEC 60947-2
440 V
500 V
690 V
RS40RS100
GV7R motor controllers and protectors are not recommended for use with variable speed controllers or soft start units for applications under 40 Hz.
Icu - interrupting capacity at full voltage.
Ics - short-circuit interrupting capacity as a percentage of Icu.
Range
240 V (+)
480 V (+)
600 V (+)
GV7 - RE40
25 to 40 A
25
25
10
GV7 - RE50
30 to 50 A
25
25
10
GV7 - RE80
48 to 80 A
25
25
10
GV7 - RE100
60 to 100 A
25
25
10
GV7 - RE150
90 to 150 A
25
25
10
GV7 - RE220
132 to 220 A
25
25
10
GV7 - RS40
25 to 40 A
65
65
10
GV7 - RS50
30 to 50 A
65
65
10
GV7 - RS80
48 to 80 A
65
65
10
GV7 - RS100
60 to 100 A
65
65
10
GV7 - RS150
90 to 150 A
65
65
10
GV7 - RS220
132 to 220 A
65
65
10
Group Installation: Maximum NTD fuse size: 1200 A / Maximum circuit breaker rating: 1200 A. Suitable for use on a circuit with an available short circuit
current level no greater than the short circuit current rating of the manual motor controller, or circuit breaker, whichever is less.
43
05/01
GV7AE11
GV7AB11
690
690
600
300
6A
6A
5A
1A
Mechanical Durability
(C.O.: Close-Open)
50,000 C.O.
50,000 C.O.
Operational Current
Conforming to IEC 60947-5-1
AC Operation
24
48
110
230/240
380/415
440
690
24
48
110
230/240
380/415
440
690
AC-12
AC-15
0.1
2.5
2.5
0.1
24
48
110
250
24
48
110
250
DC-12
2.5
2.5
0.8
0.3
0.5
DC-14
0.2
0.5
0.03
0.5
0.1
0.25
17 V
12 V
DC Operation
5 mA
5 mA
Short-circuit Protection
By GB2CB circuit breaker (rated according to operational current for Ue 415 V) or by gl fuse, 10 A max.
Cabling
Solid Cable
1 x 1.5
mm2
(1 x #16 AWG)
GV7AU
GV7AS
690 V
690 V
Operational Voltage
Conforming to IEC 60947-1
0.851.1 Ue (V)
0.71.1 Ue (V)
Drop-Out Voltage
0.350.7 Ue (V)
0.20.75 Ue (V)
<10 VA
<10 VA
<5 W
<5 W
Inrush Consumption
<5 VA
<5 VA
<5 W
<5 W
<50 ms
<50 ms
Sealed Consumption
Operating Time
Conforming to IEC 60947-1
On-load Factor
100%
100%
Cabling
Solid or Flexible Cable
44
2001 Schneider Electric All Rights Reserved
05/01
1.5
2.5
10
16
25
35
AWG
#16
#14
#12
#10
#8
#6
#4
#2
#1
2.97 x 104
8.26 x 104
2.12 x 105
4.76 x 105
1.32 x 106
3.4 x 106
8.26 x 106
1.62 x 107
3.31 x 107
Al
5.41 x 105
1.39 x 106
3.38 x 106
6.64 x 106
1.35 x 107
Cu
4.10 x 104
1.39 x 105
2.92 x 105
6.56 x 105
1.82 x 106
4.69 x 106
1.39 x 107
2.23 x 107
4.56 x 107
Al
7.52 x 105
1.93 x 106
4.70 x 106
9.23 x 106
1.88 x 107
PVC
Insulation
Cu
PRC
50
Example 1: For a GV7RS220, the peak value is limited to 20 kA for a prospective Isc of 40 kA.
Example 2: For a GV7RS220, and with a prospective Isc of 40 kA, an I2t of 7.5 x 105 A2s is obtained,
which requires the use of a PVC insulated copper cable with a cross-sectional area of 10
mm2 (# 8 AWG).
45
05/01
10 000
5000
2000
1000
500
200
100
50
20
10
5
1
2
2
1
0.5
3
0.2
0.1
0.05
0.02
0.01
0.005
0.002
x setting current (Ir)
1
2
3
46
2001 Schneider Electric All Rights Reserved
05/01
100
80
70
60
50
40
30
20
1
2
3
10
8
7
6
5
1
2
3
4
2
20
10
30
40 50 60 70
100
GV7RE220
GV7RE150
GV7RE100
100
80
70
60
50
40
30
20
1
2
3
10
8
7
6
5
4
2
10
20
30
40 50 60 70
100
1
2
3
GV7RS220
GV7RS150
GV7RS100
47
05/01
10 7
5x10 6
3x10 6
2x10 6
10 6
1
5x10 5
3x10
2
3
2x10 5
10 5
5x10 4
3x10 4
2x10 4
2
10
20
30
40 50 60 70
100
1
2
3
GV7RE220
GV7RE150
GV7RE100
10 7
5x10 6
3x10 6
2x10 6
10 6
1
5x10 5
3x10 5
2x10
10 5
5x10 4
3x10 4
2x10 4
2
10
20
30
40 50 60 70
100
1
2
3
GV7RS220
GV7RS150
GV7RS100
48
2001 Schneider Electric All Rights Reserved
05/01
50
40
30
20
1
2
10
8
7
6
5
4
2
9 10
20
1
2
GV7RE220
GV7RE150 and GV7RE100
50
40
30
20
1
2
10
8
7
6
5
1
2
4
2
10
GV7RS220
GV7RS150 and GV7RS100
20
49
05/01
3x106
2x106
106
5x105
3x10 5
2x105
10 5
2
10
20
1
2
GV7RE220
GV7RE150 and GV7RE100
3x106
2x10 6
10 6
5x10 5
3x10 5
2x10 5
10 5
2
1
2
10
GV7RE220
GV7RE150 and GV7RE100
20
50
2001 Schneider Electric All Rights Reserved
05/01
GV2AE
.59
15
LS1D7323:
3.92
101
.39
10
X1
LS1D30
X1
GV2ME
X1
.37
9.3
.37
9.3
3.2
81(1)
63
16
.71
18
1.8
45
=
1.8
44.5
46
1.8
44.5
X1
3.92
101
1.7
44
2.6
66
' GV2ME3:
.43 .63
11 16
3.5
89
1.8
45
3.5
89
'
67.2
GV2P
.55
14
3.9
98
1.3
32
1.8
45
2.4
61
3.5
89
X1
GV2AK00
X2
1.1
50
3.2
82
1.0
26
.59
15
.37
9.3
1.8
44.5
.37
9.3
3.2
81(1)
.71
18
1.8
44.5
Mounting of GV2M
GV2AF02
DZ5MB201
AF1EA4
DZ5ME8
1.4
35
1.4
35
1.1
50
2.4
60
1.1/2.4
50/60
1.8
44.5
3.1
80
Mounting of GV2P
1.1/2.4
50/60
1.8
44.5
1.7
4.2
.59
15
1.4
35
On Panel
On Pre-slotted Mounting
Plate AM1PA
.20
5
1.4
35
AF1EA4
1.8
44.5
1.4
35
1.8
45
4.1 .20
105 5
5.3
135
3.3
84
3.3
84
1.8
44.5
2.2
55
.22
5.5
1.8
45
.53
13.5
.53
13.5
.94
24
.37
9.5
2.1
54
GV2M + GV1L3
GV1F03
(current limiter)
3.1
79
1.8
45
3.0
77
X1
3.5
89
1.8
45
5.1
129
6.0
152
1.5
39
1.6
40 X1
GV2AF01
GV2M + K contactor combination
1.8
44.5
.51
13
1.4
35
51
05/01
c1
45
c1
45
d1
d
GV2-ME +
LC2-D09 to D18
GV2-P +
LC2-D09 to D18
7.4 (188.6)
7.8 (199)
6.61 (169.1)
7.9 (199.5)
c1
3.6 (92.7)
3.9 (99)
c1
4.6 (116.8)
4.6 (116.8)
3.9 (98.2)
4.11 (104.5)
4.8 (122.3)
4.8 (122.3)
d1
3.9 (98.3)
3.9 (98.3)
4.1 (103.8)
1.4 (103.8)
Door Cut-out
=
2.1
54
1.7
43
2.6
65
.28
7
4x0.14
4x3.5
2.1
53
.06-20
1.5-5
.20
5.2
.24
6
(1)
=
2.1
54
(1) 135 mm min., 284 mm max. with operating rod uncut, 88 with operating rod cut.
2x0.13
2x3.3
0.70
17
2.4
62
4.6
118
5.2
133
5.1
130
5.8
147
.83
21
2x0.21x0.25
(1) 2x5.3x6.3
.45
11.5
.04-16
1-4
=
3.3
84
3.7
93
3.0
76
3.7
93
.47
12
0 .30
7.5
.04-.24
1-6
.47
12
a1
GV2
a1
MP01, MP02
MP03, MP04
5.5
140
5
127
3.7
93.5
4.2
106.5
.37
9.5
GV2MP01, MP02
a
4.6
117
5.2
133
GV2MP0
2.8
71
3.7
93
.26
6.5
52
2001 Schneider Electric All Rights Reserved
05/01
2.5
63
.71
18
.12
3
1.8
45
a
No. of Taps
GV2G454
GV2G445
GV2G472
1.2
30
53
05/01
.79
20
X1
.68
17.3
(1)
.87
22
3.0
75
4.4
113
.22
5.5
X1
1.8
45
2.8
70
100110
4.7
120
.18
4.5
2.4
61.2
X1 = Electrical clearance
(breaking at Isc max.)
.83
21.2
4.8
122.5
2.8
70.4
Mounting on Panel
100110
100110
AF1EA4
4.4
113
4.4
113
.79
20
12.2
312
7.7
195
12.2
312
(1)
4x0.30
4x 7.7
(2)
5.9
150
6.1
154.4
4.1
105
7.1
181
(1) 0.04 x 0.83 " / 1 x 21 mm and 0.04 x 1.5 " / 1 x 37.5 mm blanking plugs for cable entries
(2) 0.04 x 0.83 " / 1 x 21 mm and 0.08 x 1.5 " / 1 x 37.5 mm blanking plugs for cable entries
54
2001 Schneider Electric All Rights Reserved
05/01
440-480 Vac
550-600 Vac
75 Hp (FLC=192 A)
150 Hp (FLC=180 A)
200 Hp (FLC=192 A)
FLC = Full load current. The values listed are for three-phase AC induction motors.
Motor Controllers
GV7R
=
=
4.13
105
4.37 86
111 (1)
(1)
3.19
81
(2)
(3)
x1
x2
Safety Clearance
Painted or insulated metal plate, insulation or insulated bar
Bare metal plate
x1
x1
14.06
357
4.92
125
=
12.64
321
6.34
= 161 =
=
6.34
161
=
3.19
81 3.39
= =
1.38
35
x2
Inches (mm)
Inches (mm)
0 (0)
1.18 (30)
U 440 V
0.20 (5)
1.38 (35)
0.39 (10)
1.38 (35)
U 600 V
0.79 (20)
1.38 (35)
x2
Inch (mm)
a
GV7R + LC1F115 or
F150 + GV7AC06
4.69 (119)
13.15 (334)
7.13 (181)
4.69 (119)
13.31 (338)
7.40 (188)
5.16 (131)
14.09 (358)
7.40 (188)
5.12 (130)
14.33 (364)
8.46 (215)
55
05/01
4.92
125
5.31
135
4.92
125
DZ5-ME5
1.38
35
0.59
15
4.25
108
=
4.25
108
1.85
3.0 47
76
n Controllers GV7R
Side by Side
1 Starter
GV7R
Flush Mounting
1.14
29
3.46
88
3.27
83
= =
1.14
29
4.25
108
Inch (mm)
GV7R + LC1F115 + GV7AC06
1.73 (44)
3.35 (85)
4.72 (120)
1.81 (46)
3.35 (85)
4.72 (120)
1.89 (48)
3.35 (85)
4.72 (120)
2.24 (57)
3.35 (85)
4.72 (120)
2.36 (60)
3.35 (85)
4.72 (120)
56
2001 Schneider Electric All Rights Reserved
05/01
Smooth Terminals
1.77
45
Connectors
1.61
41
1.77
45
Cabling
2.76
70
2.76
70
0.75
19
0.41
10.5
1.18
30
a (in/mm)
1.85
3.0 47
76
1.77
DD
60
0.85/21.5
Flush Mounting
60
0.77/19.5
GV7R 220
2.87 45
73
GV7R
1.10
28
6.10
155
4.76
121
3.58
91
1.14
29
2.17 1.42
55
36
3.5
89
3.82
97
0.35
9
3.94
100
4.72
120
2.32
59
0.36
9.25
1.61
41
4.92
125
4.72
120
2.72
69
2.0
51
=
3.94
100
2.95
75
0.35
9
60
60
l
2.95
75
57
05/01
5/L3
5/L3
3/L2
3/L2
6/T3
1/L1
1/L1
5/L3
4/T2
3/L2
6/T3
2/T1
1/L1
4/T2
GV2P
2/T1
GV2ME
GV2AE11
GV2AE20
13
23
24
21
22
14
13
11
12
14
13
14
or
53
97
51
54
98
52
GV2AD1001
97
51
52
GV2AD1010
98
95
53
GV2AD0101
96
95
96
54
GV2AD0110
08
06
43
(73)
44
(74)
GV2AM11
05
(63)
33
43
(73)
44
(74)
GV2AN20
(64)
34
(61)
31
(62)
32
GV2AN11
Voltage Trips
D1
D2
E1
E2
GVAX
C2
D2
C1
GV2AS
D1
GV2AU
GV2AD10
Short-circuit
signalling
Trip
signalling
N/C or N/O
Start-Stop Contact
58
2001 Schneider Electric All Rights Reserved
05/01
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
GV3M
31
13
23
33
13
23
33
13
23
31
32
14
24
34
14
24
34
14
24
32
GV1A07
23
GV1A06
13
GV1A05
24
23
24
GV1A03
14
13
21
22
GV1A02
14
13
14
GV1A01
98
96
97
95
GV3A08
Voltage Trips
GV3D
C1
D1
GV3B
C2
D2
59
05/01
GV7AS
97
C1
24
22
21
GV7AD111, AD112
98
97
50 ms
50 ms
13
97
84
82
94
92
91
A self-adhesive label, supplied with the contact, can be affixed to the front face of the starter to allow personalized
marking according to the function of the contact or contacts.
C2
D1
D4
81
14
12
5/L3
6/T3
11
3/L2
4/T2
2/T1
1/L1
50 ms
21
23
98
14
KA1
A2
KA1
KM1
A1 22
B1
A1
24
KA1
A2
98
KA1
60
2001 Schneider Electric All Rights Reserved
05/01
61
05/01
62
2001 Schneider Electric All Rights Reserved
05/01
63
05/01
Square D Company
8001 Highway 64 East
Knightdale, NC 27545
USA
1-888-SquareD
(1-888-778-2733)
www.squared.com
Catalog No. 2520CT0001 May 2001 2001 Schneider Electric All Rights Reserved
Replaces 2520CT9501R6/97 dated 12/97 and 2520CT9801 dated 01/99.