EE3278 Lab Sheet (Cooling Tower)
EE3278 Lab Sheet (Cooling Tower)
ENGINEERING
Engineering Thermodynamics
Lecturer
Date
Laboratory
LABSHEE
T
COOLING
TOWER
Notes
:
(1) On-the-spot evaluation may be carried out during or at the end of
the experiment. (2) Students are advised to read through this lab
sheet before doing the experiment.
(3) Your performance, teamwork effort, and learning attitude will count towards the
marks.
2.0
OBJECTIVE
1. To observe the processes within a forced draught cooling tower and study
the operation of cooling tower
2. To study the basic principles and characteristics of evaporative water
cooling tower system.
3. To determine all end state properties of the air and H2O from
psychrometric chart and tables, and apply steady flow equations to
the system.
4. To examine the effect of various parameters such as feed flow rate, inlet
water temperature etc. on the performance of the cooling tower.
3.0
APPARATUS
This experiment will give students an appreciation of the construction, design and
operational characteristics of a modern evaporative cooling system. The test unit is
also an excellent example of an
open system through which two streams of fluid flow (water and air) and in
which there is a mass
transfer from one stream to the other. Figure 1 shows a schematic diagram of the
test unit. The Cooling Tower Trainer behaves in a similar manner and has similar
components to a full size cooling tower and may be used to introduce students to
their characteristics and construction.
Water
Circuit:
Warm water is pumped from the load tank through the control valve and water
flow meter to the column cap. After its temperature is measured (TC), the water is
uniformly distributed over the top packing deck and, as it spreads over the plates, a
large thin film of water is exposed to the air stream. During its downward passage
through the packing, the water is cooled, largely by the evaporation of a small
portion of the total flow.
he cooled water falls from the lowest packing deck into the basin, where its
temperature (TD) is again measured and then passes into the load tank where it is
re-heated before re-circulation. Due to evaporation, the level of the water in the
load tank tends to fall. Under steady conditions, the rate of water loss is equal to the
rate of evaporation plus any small airborne droplets in the air discharge.
Nilai
University
Page
2
Nilai
University
Page
3
system. This loss does not contribute to the cooling, but must be made good by
"make-up" water. To minimize this loss, a "droplet arrester", or "eliminator" is fitted
at the tower outlet. This component causes droplets to coalesce, forming drops
which are too large to be entrained and these fall back into the packings.
Under the action of the fan, air is driven upward through the wet packings. It will
be seen that the change of dry bulb temperature is smaller than the change of wet
bulb temperature, and that at air outlet there is little difference between wet and
dry bulb temperatures. This indicates that the air leaving is almost saturated, i.e.
Relative Humidity - 100%. This increase in the moisture content of the air is due to
the conversion of water into steam and the "latent heat" for this accounts for most
of the cooling effect. If the cooling load is now switched off and the unit allowed to
stabilise, it will be found that the water will leave the basin close to the wet bulb
temperature of the air entering. According to the local atmospheric conditions, this
can be several degrees below the incoming air (dry bulb) temperature. With no load,
the water would be cooled to the incoming wet bulb temperature, but this condition
cannot be attained since the pump transfers about 100W to the water. Flow through
the column may be observed through the transparent casing.
Water is heated
electric heater.
using
1kW
Equipment
and
Instruments
Air distribution chamber
Water tank with heater with the load
of 1 kW
A centrifugal fan with intake damper with
maximum airflow
Water
supply
Water
collector
Control
panel
Packed column: 18 cooling plates
per stage
Wet
and
dry
bulb
thermometer
Water
fow
meter
Wet bulb T4
Dry bulb T3
Control panel
packing
Dry bulb T1
Wet bulb
T2
Flow meter
Fan
Heater
Pump
Figure 1 Setup of
experiment
4.0
Theory
4.0.1
Cooling Range: The difference between the water temperature at entry to and exit
from the tower. Cooling Load: The rate at which heat is removed from the water.
This may be expressed in kW, Btu/h or k Cal/h.
Make-Up: The quantity of fresh water which must be supplied to the water circuit
to make good the losses due to evaporation and other causes.
Drift or Carry: Droplets of water which are entrained by the air stream leaving the
tower.
Packing or Fill: The material over which the water flows as it falls through the
tower, so that a large surface area is presented to the air stream.
Approach to Wet Bulb: The difference between the temperature of the water
leaving the tower and
the wet bulb temperature of the air entering.
4.0.2
Basic Principles
Consider the surface of a warm water droplet or film in contact with an air stream
(see Figure 2).
The Approach to Wet Bulb is one of the important parameters in the testing,
specification, design and selection of the cooling tower.
4.0.4
Steady Flow Energy
Equation
Before the equation is applied, the cooling tower system must be defined:
Heat transferred at the load tank, i.e. the process load, and possibly a small
quantity to the surroundings (Q).
Work is transferred at the pump (P).
Low
humidity air enters at the air inlet at A. High humidity air leaves at the air outlet at
B.
Make-up (equal to the increase of moisture in the air stream) enters at the
make-up tank at E. From the steady flow equation, expressing the thermal energy
or heat (H) at exit and entry:
= = ( + ) ( +
)
Note:
pump
power P is ve since it is a work input. Subscript a is for dry air;
v forThe
water
vapour
(or steam). If the enthalpy of air includes the enthalpy of the steam associated with
it, and this quantity is expressed per unit mass of dry air, the equation may be
written as follows:
= ( )
The mass flow rate of dry air ( ) through a cooling tower is a constant, whereas the
mass flow rate of
moist air is not constant due to evaporation of some of the water. In fact, the
term h is usually
E
small compared
with other terms and is often neglected.
4.0.5
Mass Balance
By conservation of mass, under steady state conditions, the mass flow rate of dry
air and of H2O (as liquid or vapour) must be the same at inlet and outlet to any
system.
Thus, for dry air, ( )A = ( )B and for H2O, ( )A + = ( )B
( = ( ()
( ((
)
The specific humidity () is known for the initial and final state points on the
psychrometric chart. Thus,
(( (
)B( = B and (
)A( =
A
( = ( (
)
The system may be re-defined thus. In this case, the process heat and pump work
does not cross the
boundary of the system, but we now have warm water entering the system at C
and cool water leaving at D. Applying the steady flow energy equation,
Assume
P = 0; Q may have a small value due to heat transfer between the unit and
its surroundings.
= + ( + +
= (
)
) + ( )
= (
( ) +
( (
)
As stated earlier, the term h is usually small compared with the other terms. c
E
4.
5.
6.
Let the cooling tower operate for at least 10 minutes before taking readings.
Record water level in the tank and the time.
Wait till the steady state is obtained. The attainment of the steady state
is confirmed by the constancy in the outlet temperature.
7. Measure inlet temperature and outlet temperature of water
8. Measure wet bulb temperature and dry bulb temperature of inlet and outlet
air.
9. Record the orifice difference pressure , the time and the water level in the
tank.
10. Repeat steps 4 to 9 by changing water flow rate.
6.0
Data sheet is provided in the Appendix for recording the measurement data. After
the experiment, the following information should be established to report the
findings:
1. Clear presentation of the measurement data
2. Determination of the state properties of air and H2O from tables or
psychrometric chart
3. Determination of air fow rate, cooling range, approach to wet bulb
temperature, enthalpy change of air and water, evaporation rate and
water loss.
4. Analysis of the relationship between water fow rate and approach to wet bulb
temperature
Discussions
The following issues shall be evaluated and
discussed. Factors affecting the accuracy
of the measurements
Major design factors and issues affecting cooling tower performance
DATA SHEET
Date:
Test No.
Packing
installed
Water fow rate
Air inlet dry
bulb
T
1 inlet wet
Air
bulb
T
2 outlet dry
Air
bulb
T
3 outlet wet
Air
bulb
T
4
Water
inlet
temperature TC
Water outlet
temperature TD
Difference in
water level
Time interval t
Make up
quantity
m
E
Rate
of water
loss
Air
fow rate
Cooling Range
Approach to wet
bulb
temperature
Air
enthalpy
change
Water enthalpy
change
Evaporation
rate
st
1 run
GPM
C
C
C
C
C
C
mm
s
kg
Kg/s
Kg/s
C
C
kW
kW
Kg/s
nd
Atmospheric pressure:
run