Parameters

Fluid properties

Cold plates

Radiator

Chiller (Evaporator)

Density [(kg/m3]
Dynamic Viscosity [kg/m*s]
Specific Heat [J/kg*K]
Thermal conductivity [W/m*K]
Friction factor
Convective coefficient (coolant side) [W/m2*K]
Thermal resistance [C/W]
To [C]
Heat rejected @36m/s (air velocity)
Pressure drop [Pa]
Heat rejected [W]
Pressure drop [Pa]

All the calculations was done using a flow rate of 60 lpm (rather than 32 lpm used for the c
to compensate the inferior thermal properties.

Water

3M NOVAC 7300
997
8.95E-04
4184
0.607

1660
1.18E-03
1140
0.063

Difference
166%
132%
27%
10%

0.022
11584.5
0.00029
48.23

0.028
4151.1
0.00025
50.54

127%
36%
86%
105%

6680.6
10114

8356.8
14116

125%
140%

10825
20000

12848
100000

119%
500%

han 32 lpm used for the calculations with water). This change was necessary