URD Voltage Drop Cal RF
URD Voltage Drop Cal RF
URD Voltage Drop Cal RF
xls
Date:
General Information
Type of Service
Normal feed
Voltage Drop Limit
3.0%
Number of Lots:
12
Diversity Factor
1.95
Segment to:
Ped 245595
Ped 245596
Xmer S49729
Conductor
Size
#2
300 MCM
300 MCM
Length
(m)
65
55
13
Number of 200 A
Lots Served
Total kVA
3.1
18.5
36.9
Towards Xmer
Towards House
Segment from:
Lot 18 (inludes cable to meter)
Ped 245595
Ped 245596
2.07%
Total
THIS CALCULATOR IS THE PROPERTY OF ATCO ELECTRIC AND CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSED WITHOUT PRIOR WRITTEN CONSENT OF ATCO
ELECTRIC
328492508.xls
7.5%
5.0%
Diversity Factors
Loading Assumptions
# of Lots Diversity Factor
0
1
1
1
2
1.1
6 kVA per 100A service
3
1.18
12 kVA per 200A service
4
1.3
5
1.45
6
1.5
7
1.56
8
1.63
9
1.7
10
1.78
>10
1.95
Reference: Willis, H. Lee, Power Distribution Planning Reference Book,
CRC Press, 2004, p. 812, figure 22.10
Streetlights
Sizes
43
100
150
Assumptions
Street lights use 120V
Each sequential light in a string alternates the 120V leg it is fed from
All non streetlight load is divided equally between both legs
Neutral currents cancel
Ignoring current contribution of uncalculated 120V leg in cable, assume negligible
THIS CALCULATOR IS THE PROPERTY OF ATCO ELECTRIC AND CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR
DISCLOSED WITHOUT PRIOR WRITTEN CONSENT OF ATCO ELECTRIC
328492508.xls
Calculation Method:
Voltage Drop = Vs-Vr
Vs = Square Root of ((Vr*sine(phi) + I*Xloop)^2+(V r*cos(phi)+I*Rloop)^2) - Vr
Vr =Receiving End Voltage = 120 V (Assume balanced loading on each 120V leg)
where cos(phi) = power factor
phi=arccos(pf)
I = Load Current = (1000*Lots Served*Demand per Service)/(V r*Diversity Factor)
THIS CALCULATOR IS THE PROPERTY OF ATCO ELECTRIC AND CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR
DISCLOSED WITHOUT PRIOR WRITTEN CONSENT OF ATCO ELECTRIC
328492508.xls
Lights 2:
Ignore voltage drop between
xmer and ped combo. Voltage
drop calculations are still
needed if a service drop from
this ped is >100m.
Lights 1:
Also include voltage drop above
steetlights due to services. (Not
applicable in this example as the ped is
attached to the xmer).
245669
245595
Services 3:
Total 12 lots are being
served dodwnstream of
this cable
245671
Services 2:
Total 6 lots are
being served
downstream of
this cable
245594
245596
Services 1:
Begin at the furthest point from the
transformer:
One service on this #2 cable for lot 18.
A voltage drop calculation is required on the
longest service drop from each pedestal. (ie
one calc per pedestal).
See "Voltage Drop Calc" Tap for an example
245670
Lights 3:
Alternate lights on streetlight
cable. Only include lights on
longest leg of streetlights. In
this case only include 245670
in the calculation.
Also include voltage drop
above steetlights due to
services. (Not applicable in this
example as the ped is attached
to the xmer). See "Streetlights
+120 leg" tab for an example
calculation.
The voltage drop limit for each run must be specified in the
calculation tab by the consultant.
The default values are:
3.3% for normal service feed
5% for alternate service feed
5% for streetlights
ATCO Electric may specify larger or smaller allowable
voltage drops for any subdivision. These other values will be
based on ATCO Electric's voltage at the primary side of the
transformer. They will be calculated to deliver minimum
voltage levels at the customer's meter.
THIS CALCULATOR IS THE PROPERTY OF ATCO ELECTRIC AND CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR DISCLOSED WITHOUT PRIOR WRITTEN CONSENT OF ATCO ELECTRIC
328492508.xls
Revision Name
Date
RC
Comments
1st release
RD
RE
RF
RG
RH
Added 200A services, changed current summing to avoid double counting load, added column for "3 of
lots served on this cable", updated assumptions, updated example tab
Added "0" lots to diversity look-up table to allow for cable sections where no extra load is added.
Combined residential lots and street lights into one sheet. Fixed calculation errors.
Updated the voltage drop limit as per the URD specification clause 3.4.2.
Updated the voltage drop limist to 3% Normal Feed and 7.5% Alternate Feed
THIS CALCULATOR IS THE PROPERTY OF ATCO ELECTRIC AND CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION WHICH MUST NOT BE DUPLICATED, USED, OR
DISCLOSED WITHOUT PRIOR WRITTEN CONSENT OF ATCO ELECTRIC