Professional Documents
Culture Documents
Puffer Pak Load Break Switch: Component Identification
Puffer Pak Load Break Switch: Component Identification
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
1
3
1
1
1
2
1
2
4
0
6
1
6
1
16 1/2
COMPONENT IDENTIFICATION
5 3/4
DESCRIPTION
CLOSED-OPEN POSITION INDICATORS WITH PADLOCK PROVISIONS
PHASE IDENTIFICATION TAGS
NAMEPLATE WITH RATINGS AND LINE DIAGRAM
COLOR CODED PRESSURE GAUGE
SF6 FILL VALVE (SWITCH FACTORY FILLED AT 10 PSIG)
2/0 AWG MAXIMUM GROUND LUGS
REMOVABLE OPERATING HANDLES
LIFTING EYES
11
5 3/4
3
11
6
A
2
B
60
5 14
12
1
9
CLOSED
POSITION
OPEN
POSITION
29
7
6 3/4
5
24
47 1/2
23 5/16
SWITCH RATINGS
MAXIMUM DESIGN VOLTAGE
BIL IMPULSE WITHSTAND
AC ONE MINUTE WITHSTAND
DC FIFTEEN MINUTE WITHSTAND
CORONA EXTINCTION AT 3 PC SENSITIVITY
OPEN GAP BIL IMPULSE WITHSTAND **
LOAD INTERRUPTING AND LOOP SWITCHING
MAGNETIZING CURRENT SWITCHING
CAPACITIVE CURRENT SWITCHING
CONTINUOUS CURRENT *
EIGHT HOUR OVERLOAD CURRENT *
ASYMMETRICAL MOMENTARY AND THREE SHOT FAULT CLOSE *
SYMMETRICAL ONE SECOND RATING *
NORMAL OPERATING PRESSURE RANGE (PSIG)
OVERLOAD INTERRUPTING CAPACITY
MECHANICAL LIFE OPERATIONS
CORROSION RESISTANCE PER ASTM-B-117-54 (HOURS)
MAXIMUM GAS LEAKAGE (cc/SECOND)
* WHEN 200 AMP ELBOWS ARE USED, THE CONTINUOUS CURRENT, OVERLOAD,
MOMENTARY AND ONE SECOND RATINGS WILL BE REDUCED. TYPICALLY, 200 AMP
ACCESSORIES ARE RATED 200 AMP CONTINUOUS, 300 AMP EIGHT HOUR OVERLOAD,
15 KA ASYMMETRICAL MOMENTARY AND 10 KA SYMMETRICAL FOR 1/2 SECOND.
** WITH TANK AND ADJACENT PHASES FLOATING
SPECIFICATIONS
15.5 KV
95 KV
35 KV
66 KV
11 KV
200 KV
600 A
25 A
40 A
600 A
900 A
22.5 KA
15 KA
2 - 15
3000 A
2000
2000
10 -7
13 MTG
12
1 3/4
14 1/4
30
28 1/2 MTG
600A.
K76279
APPROVAL
1
ITEM #
DATE
DATE
PRODUCTION X