16-SAMSS-510
28 April 2013
Scope.............................................................. 2
References..................................................... 2
Vendor Experience......................................... 3
Service Conditions.......................................... 4
General Requirements.................................... 4
Data Schedule..................................................... 10
Appendix A......................................................... 11
Page 1 of 11
Scope
1.1
1.2
1.3
This specification defines switchgear that utilizes fully rated equipment. SF6 gas
is used as the insulating medium. SF6 gas or vacuum is used for interruption.
The bus maybe contained within an SF6 insulted compartment or be insulated
with a solid insulating material. Tape insulation of bus and or bus joints is
unacceptable. The switchgear cable terminations are designed for use with
fully-shielded, dead-front, separable cable connectors.
1.4
This specification defines the basic features of the equipment required and shall
take precedence over all standards and codes as referenced. The equipment
manufacturer shall ensure that the applicable standards are adhered to in
addition to this specification.
If there are any conflicts between this Specification and associated purchasing,
project or engineering documents, this specification shall take precedence.
2.2
Direct all requests to deviate from this Specification in writing to the Company
or Buyer Representative, who shall follow internal company waiver procedure.
2.3
References
The following is a summary of all the documents which have been mentioned within
this Specification. The specific part(s) of these documents which are applicable have
been identified throughout this Specification.
Page 2 of 11
3.1
IEC 62271
IEC 60529
IEC 60227
Vendor Experience
Designs and materials used shall have a minimum of two (2) years of verifiable, proven
field experience.
Page 3 of 11
5.1
5.2
Service Conditions
6.1
6.2
6.3
Unless otherwise specified this equipment shall be suitable for use in locations that
are subject to sand and dust storms, fog, and airborne contaminants, including NaCl
(Sodium Chloride) to 300 ppm and MgCl (Magnesium Chloride) to 50 ppm.
6.4
Unless otherwise specified, equipment shall be suitable for use in locations with
the following ambient temperatures: Average monthly normal maximum
(hottest month), 45C; Average daily temperature (hottest month), 40C;
Maximum daily peak 50C.
General Requirements
7.1
This specification shall take precedence over any referenced third party
document(s).
7.2
7.3
7.4
7.5
The Buyer's inspection requirements are presented within Saudi Aramco Form
175-162600. This form is included with the Quotation Request or the Purchase
Order documents.
Page 4 of 11
7.6
The Buyer's nonmaterial requirements are presented within Saudi Aramco Form
NMR-7920. This form is included with the Quotation Request or the Purchase
Order documents.
7.7
7.8
7.8.2
7.8.3
7.9
7.10
7.11
7.12
The circuit breaker, load-break and ground switch functions shall be storedenergy, spring-operated, to provide fast and reliable operation. The speed of
operation of the switch shall be independent of the operator. When a separate
selector is provided the switching device must be mechanically interlocked so
that it can only be operated (Closed) when the selector is in a determinate
position (ON/OFF/Ready to Earth).
7.13
Springs and moving parts of the switch operating mechanism(s) shall be located
inside the weatherproof enclosure protected from environmental conditions.
7.14
7.15
7.16
7.17
The enclosures for outdoor use shall be NEMA ICS 6 Type 3 or IEC 60529
Type IP54, fabricated from a minimum of 2 mm (14 gage) 316 stainless steel
sheet. The enclosure door(s) shall be provided with pad-lockable handles.
Commentary Note:
This enclosure shall be used for the protection of switchgear not inherently
designed for use outdoor which includes equipment intended for subsurface use.
8.2
The base frame of the enclosure shall be made of hot-dipped galvanized steel.
The switchgear shall be fixed to this base. The assembly shall be adequately
braced to provide strength and rigidity under normal operating conditions and
during transportation.
Page 6 of 11
8.3
Bolts, hinges, and associated hardware shall be Type 316 stainless steel.
Gasketing materials and adhesives shall be suitable for the environmental
conditions specified in Section 5.
8.4
8.5
8.6
All exterior and interior surfaces of the equipment shall be painted and shall meet
the requirements of ANSI/IEEE C57.12.28 -Pad Mounted Equipment-Enclosure
Integrity, Section 5 -Enclosure Coating System, except the paint color shall be
white, or light gray unless otherwise specified. A wet paint process is described in
the paint system requirements of ANSI/IEEE C57.12.28. However, an equivalent
coating system utilizing an electrostatic powder coating process is acceptable.
8.7
8.8
Outdoor onshore locations within one kilometer from the shoreline of the
Arabian Gulf
Outdoor onshore locations within three kilometers from the shoreline of the
Red Sea.
The nameplates shall be stainless steel and attached with stainless steel
hardware. Entries shall be marked by etching, engraving or other
permanent marking method.
8.8.2
8.8.3
Danger and warning labels shall be written in both Arabic and English,
utilizing white characters on a red background. If specifically noted
Page 7 of 11
b)
Manufacturer's location
c)
d)
e)
Date of Manufacture
9.2
Load-break Switches
Load-break switches shall comply with the requirements of this specification as
described in Sections 6 and 7.
9.3
Circuit Breakers
9.3.1
9.3.2
9.3.3
Page 8 of 11
9.4
16 May 2007
14 October 2008
22 May 2012
28 April 2013
Revision Summary
Major revision.
Editorial revision to replace Electrical Substations Equipment Standards Committee
Chairman and Vice Chairman.
Editorial revision to update the next planned update and change primary contact.
Minor revision. Due to its compactness, this type of gear has been over deployed in Saudi
Aramco facilities and we have recently been experiencing failures due to corrosion.
This revision is necessary to define the correct application for this equipment.
Page 9 of 11
Data Schedule
Attachment to Specification 16-SAMSS-510
Manually-Operated Pad Mounted SF6 Switchgear: 1 kV to 36 kV
Minimum Ratings
(Select Value)
Description
Rated Voltage
15 kV
600 A
600 A
25 kA
Vendor's
Proposed Values
52.5 kA
25 kA
95 kV
35 kV
Manufacturer
--------
--------
--------
--------
Model/Type
--------
--------
--------
--------
Manufacturing Location
--------
--------
--------
--------
Switchgear Location
X _ Standard Environment
Severe Corrosive environment
Yes _ X_____
No ______
____________________________________________________________________________________________
Load-Break
Switch
Circuit
Breaker
Cable Fault
Detectors
___YES__
___YES__
___YES__
___YES__
___YES__
_________
___NO___
___YES__
___YES__
___YES__
___YES__
_________
__YES___
__YES___
__YES___
__YES___
__YES___
_________
Page 10 of 11
Appendix A
Acceptable Protective Devices
Packaged Switchgear Relays
Type Protection
Manufacturer
Manufacturer's
Number
ANSI Function #
Siemens
Siemens
50/51N
Merlin Gerin
VIP300
50/51/50N/51N
50/51
Page 11 of 11