I. INTRODUCTION
proposed in references [6, 7]. Taha et al. [8] and Apostolov [9]
presented the object modeling of DERs with IEC 61850-7-420
and its extensions from the control and communication point
of view. Kanabar et al. [10] presented the study of different
communication systems between DERs and IEC 61850 based
distribution system.
This paper presents the modeling of DER IEDs according to
IEC 61850-7-420 and its extensions. Performance evaluation
of the communication architecture for integrating DER in
distribution system with different wired and wireless
communication technologies using Optimized Network
Engineering Tool (OPNET) [11] modeler is presented.
The organization of paper is as follows: Section II
summarizes IEC 61850 communication standards, Section III
explains the modeling of different distributed energy resources
system according to IEC 61850-7-420, and Section IV
presents the simulation study of communication between
different DERs and distribution system using different
communication technologies. Finally, Section V presents
future work and conclusion.
II. IEC 61850 COMMUNICATION STANDARD
IEC 61850 provides a comprehensive model for power
system devices to organize data, configure objects and map
them on to protocols, so that they are consistent and
interoperable.
The IEC 61850 standard consists of many parts. Part 3, 4
and 5 describes the general and specific functional
requirements for communication in substation. The part 7-2
and 7-4 describe the abstract services and the abstraction of
data objects. The data objects consists of building blocks
Common Data Classes (CDC) elements which are defined in
part 7-3. The mapping of these abstract services and data
objects on to manufacturing Messaging Specification (MMS)
SV
(Type
4)
GOOSE
(Type 1,
1A)
IEEE
1588
(Type
6)
MMS Protocol
Suite
(Type 2,3,5)
TCP/IP
T-Profile
Application
Presentation
Session
Transport
Network
Link
Physical
Fig. 2. Organization of DER logical nodes and Logical devices at ECP [1]
PV Plant
Utility
Grid
AC
Diesel
Generator
AC
132 kV
11 kV
Wind plant
Fig. 5 (b). Customized Node model for wireless Breaker and control IEDs
Fig. 5 (a). Customized Node model for wired Breaker and control IEDs
Source IED
Trip commands
Destination
IED
Size (bytes)
98
DER Breaker
IED
Station PC
Sample Values
MU IED
DER Control
IED
102
Status Update
Server
200
DER Control
IED
150
Server
TABLE III
PERFORMANCE EVALUATION OF 100 AND 1000 MBPS WIRED
LAN
Type
of
Message
100 Mbps
1000 Mbps
Delay (ms)
Throughput
(kbps)
Delay
(ms)
Throughput
(kbps)
GOOSE
0.11
80
0.08
80
Sampled
Values
0.14
3500
0.106
Other MMS
type traffic
0.22
1000
0.203
TABLE IV
PERFORMANCE EVALUATION OF 100 AND 1000 MBPS WIRED
LAN
Type
of
Message
54Mbps
24 Mbps
Delay (ms)
Throughput
(kbps)
Delay
(ms)
Throughput
(kbps)
GOOSE
0.84
80
0.88
80
3500
Sampled
Values
1.02
3500
1.03
3500
1000
Other MMS
type traffic
0.92
1000
0.92
1000
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
Fig. 9. OPNET Simulation of communication network architecture with
wireless technologies.
[13]
Ingram, D.M.E.; Schaub, P.; Taylor, R.R.; Campbell, D.A., "SystemLevel Tests of Transformer Differential Protection Using an IEC 61850
Process Bus," Power Delivery, IEEE Transactions on , vol.29, no.3,
pp.1382,1389, June 2014
M. Adamiak, R. Hunt, A. King, and S. McCreery," Application of
digital radio for distribution pilot protection and other applications, in
Proc. 2008 IEEE Protective Relay Conf., pp. 310-333.
B. Hadzi-Kostova, Z.Styczynski, and R. Krebs, "New protection
conceptsfor distribution systems with dispersed generation, in Proc.
IEEE Power Tech. Conf., pp. 1-6, June 2005.
Ustun, T.S.; Ozansoy, C.; Zayegh, A., "Distributed Energy Resources
(DER) object modeling with IEC 618507420," Universities Power
Engineering Conference (AUPEC), 2011 21st Australasian , pp.1,6, 2528 Sept. 2011
Apostolov, A.P., "Modeling systems with distributed generators in IEC
61850," Power Systems Conference, 2009. PSC '09. , vol., no., pp.1,6,
10-13 March 2009
Kanabar, P.M.; Kanabar, M.G.; El-Khattam, W.; Sidhu, T.S.; Shami, A.,
"Evaluation of communication technologies for IEC 61850 based
distribution automation system with distributed energy resources,"
Power & Energy Society General Meeting, 2009. PES '09. IEEE,
pp.1,8, 26-30 July 2009.
OPNET Modeler OPNET Technologies, [Online], Available:
http://www.opnet.com.
IEEE Standard Communication Delivery Time Performance
Requirements for Electric Power Substation Automation," IEEE Std
1646-2004.
IEC, Wind TurbinesPart 25: Communications for Monitoring and
Control of Wind Power Plants, IEC Std. 61400-25, 2006.
References
[1]
[2]
[3]
[4]