Cabos Automotivos FORD

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

Engineering Specification

PART NAME

LET
FR
LET
FR

A
1
A
20

PART NUMBER

FORD GLOBAL WIRE SPECIFICATION


A
B
D
A
A
B
A
2
3
4
5
6
7
8
A
C
D
D
D
B
D
21
22
23
24
25
26
27
LET

10-24-07
10-24-07

6-13-08

FR

A
9
D
28

A
10
D
29

A
11

A
12

REVISIONS

ALL Released ES-AU5T-1A348-AA


Notice # AELE-E-11789584-040

ES-AU5T-1A348-AA
A
C
B
B
13
14
15
16

A
17

A
18

DR

CK

REFERENCE

RP
RP

MW
MW

PREPARED/APPROVED BY

RP

MW

A
19

Rakesh Patel

1-22-09

11-17-09

Revised to add temp class 9, and 1.25 & 8 mm2 sizes.


-Revised frames identified with Rev level B.
-Notice # AELE-E-11789584-131
Revised to add 0.35 mm2 Standard wall dimensions.
- Added wire sizes in Table 2 & 3. Added requirements
for Loss of Mass test. Added wire codes.
Notice # AELE-E-11789584-191
Revised to add temp class 5 & 6. Added 0.5 mm2 std
wall. Revised Table 1, 2, 3, 7.
Notice # AELE-E-11789584-259

CHECKED BY

DETAILED BY

Ulrich Schwarz
RP

US

CONCURRENCE/APPROVAL
SIGNATURES
Design Engineering Supervisor

Paul Nicastri
Design Engineering Management

RP

RP Paul Nicastri
Manufacturing Engrg.

Quality Control

Purchasing

Supplier Quality Assistance

FRAME 1
PD
May 1988

OF

3947a1e

29

REV D
(Previous editions may NOT be used)

Engineering Specification
Ford Global Wire specification

FRAME

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

TABLE OF CONTENT
ENGINEERING SPECIFICATION
1
SCOPE
2
APPLICATION
3
REQUIREMENTS
3.1
QUALITY SYSTEM REQUIREMENTS
3.2
INFRARED SPECTROPHOTOMETRY AND/OR THERMAL ANALYSIS
3.3
TESTING, CONDITIONING AND TEST CONDITIONS
3.3.1
OVEN
3.4
CABLE TEMPERATURE CLASS
3.5
CABLE OUTSIDE DIAMETER
3.6
CONDUCTOR
3.7
CONDUCTOR DIAMETER
3.8
INSULATION COLOUR
3.9
INSULATION THICKNESS
3.10
ELECTRICAL CHARACTERISTICS
3.10.1
CONDUCTOR RESISTANCE
3.10.2
WITHSTAND VOLTAGE, 30 MINUTES
3.10.3
1 MINUTE WITHSTAND VOLTAGE
3.10.4
INSULATION FAULTS
3.10.5
INSULATION VOLUME RESISTIVITY
3.11
MECHANICAL CHARACTERISTICS
3.11.1
PRESSURE TEST AT HIGH TEMPERATURES
3.11.2
LOW TEMPERATURE WINDING
3.11.3
LOW TEMPERATURE IMPACT
3.11.4
ABRASION RESISTANCE
3.11.5
SHORT TERM HEAT AGING
3.11.6
LONG TERM HEAT AGING (For Initial Qualification Only)
3.11.7
THERMAL OVERLOAD
3.11.8
SHRINKAGE BY HEAT
3.11.9
LOSS OF MASS (For Initial Qualification Only)
3.11.10
FLEXIBILITY TESTS
3.11.11
NOTCHING RESISTANCE
3.11.12
RESISTANCE TO FLAME PROPAGATION
3.11.13
COLUMN STRENGTH
3.11.14
HOT WATER TEST (For Initial Qualification Only)
3.12
RESISTANCE TO CHEMICLALS (initial qualification only)
3.13
ENVIRONMENTAL CYCLING
3.14
RESISTANCE TO OZONE
4
SUPPLIER'S RESPONSIBILITY
5
TABLES
5.1
Table 1 - CONDUCTOR STRANDING AND DIMENSIONS
5.2
Table 2 WIRE DIMENSIONS
5.3
Table 3 - CONDUCTOR RESISTANCE ( / km, max)
5.4
Table 4.1 - SCRAPE ABRASION
Table 4.2 - SANDPAPER ABRASION
5.5
Table 5 - MANDREL DIAMETERS
5.6
Table 6 - FLUID COMPATIBILITY
5.7
Table 7 - FLEXIBILITY TEST: WIRES 3.0 mm.
5.8
Table 8 - IMPACT
5.9
Table 9 - INSULATION COLORS
6
Draft Code
APPENDIX A
WIRE SIZE COMPARISON CHART

PD
May 92

3947a2e

(Previous editions may be used)

3
3
3
3
3
3
3
4
4
4
4
4
4
5
5
5
6
6
7
7
7
8
9
10
12
13
13
14
14
14
15
16
17
18
19
20
21
22
23
23
24
25
25
26
26
27
27
27
28
28
29

Engineering Specification
Ford Global Wire specification

FRAME

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

SCOPE

The products defined by these specifications are low tension stranded and insulated cables.
PRIMARY LOW TENSION CABLE 85C
PRIMARY LOW TENSION CABLE 100C
PRIMARY LOW TENSION CABLE 115C
PRIMARY LOW TENSION CABLE 125C
PRIMARY LOW TENSION CABLE 150C
PRIMARY LOW TENSION CABLE 175C
PRIMARY LOW TENSION CABLE 200C
The specification has been agreed by the following FORD Business Units:
Ford NA
Ford of Europe
Volvo Cars

APPLICATION

These cable specifications were originally released for use at a nominal system voltage of 60 V rms or less in
automotive electrical harnesses.

REQUIREMENTS

3.1

QUALITY SYSTEM REQUIREMENTS

Material suppliers and part producers must conform to Quality System Requirements, ISO-9000. Material
specification requirements are to be used for initial qualification of materials. A Control Plan for ongoing
production verification is required. This plan must be reviewed and approved by the relevant Ford Materials
activity and/or Ford Supplier Technical Assistance (STA) prior to production parts submission. Appropriate
statistical tools must be used to analyze process/product data and assure consistent processing of the
materials. Part producers using this material in their products, must use Ford approved materials and must
conform to a process control plan, which has been approved by STA and/or the relevant Materials Activity.

3.2

INFRARED SPECTROPHOTOMETRY AND/OR THERMAL ANALYSIS

Ford Motor Company, at its option, may conduct infrared and/or thermal analysis of material/parts supplied to
this specification. The IR spectra and thermograms established for initial approval shall constitute the reference
standard and shall be kept on file at the designated material laboratory. All samples shall produce IR spectra
and thermograms that correspond to the reference standard when tested under the same conditions.

3.3

TESTING, CONDITIONING AND TEST CONDITIONS

Initial qualification tests shall be performed by a certified, independent test laboratory unless otherwise agreed
with the appropriate Ford business unit.
All test values indicated herein are based on material conditioned in a controlled atmosphere of 23 +/- 2 C and
50 +/- 5 % relative humidity for not less than 24 h prior to testing and tested under the same conditions unless
otherwise specified.

3.3.1 OVEN
An oven with air exchange, either natural or by pressure should be used. The air shall enter the oven in such a
way that it flows over the surface of the test pieces and leaves near the top of the oven. The oven shall have
not less than 8 and not more than 20 complete air changes per hour at the specified ageing temperature. If the
insulating material on the tested wire includes a volatile softener with influence on flexibility and performance in
low temperature winding test after ageing, the air should be changed a minimum of thirty five (35) times per
hour.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

3.4

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

CABLE TEMPERATURE CLASS

Depending upon the service conditions, the cables shall be made to belong to one of the following four classes
of temperature:
o

Class 1
Class 2
Class 3
Class 4
Class 5
Class 6
Class 9

3.5

-40 to + 85 C
-40 to + 100 oC
o
-40 to + 125 C
o
-40 to + 150 C
-40 to + 175 oC
o
-40 to + 200 C
-40 to + 115 oC

CABLE OUTSIDE DIAMETER

No single value shall be outside the acceptable range of diameter as specified in Table 2.
Test Sample: The test sample length shall be approximately 4m.
Procedure: Determine the outside cable diameter by taking four sets of measurements rotated at 90 at least
1m apart. Record the overall diameter at each point. The accuracy of the measuring instrument shall be +/0.01 mm. The measuring device shall not deform the test sample when taking measurements.

3.6

CONDUCTOR

Conductors shall consist of soft annealed copper, soft annealed compressed/compacted copper, hard unannealed copper, tinned copper. The specifications for the conductors are to be in line with ASTM B1, ASTM
B3 and ASTM B33. Elongation and lay length requirements shall be per ASTM B174.
Minimum conductor strand count and diameter shall comply with Table 1. Strand count according to Structure A
C shall be agreed on with the appropriate Ford business unit before commencement of testing. The finished
cable shall meet the resistance requirements of Table 3.

3.7

CONDUCTOR DIAMETER

No single value of strand and conductor diameter shall be outside the acceptable range of diameter as
specified in Table 1 and Table 2.
Test Sample: The test sample length shall be approximately 4m.
Procedure: Determine the conductor diameter by stripping the insulation at the point of measurement and
taking four sets of measurements rotated at 90, at least 1m apart. Record the conductor diameter at each
point. The accuracy of the measuring instrument shall be +/- 0.01 mm. The measuring device shall not deform
the test sample when taking measurements.

3.8

INSULATION COLOUR

The colour of the insulation shall be specified on engineering drawings. The insulation colour tolerances are
specified in Table 9.
Where striping is specified, either one or two stripes may be used. The individual stripe shall be a minimum of
7% wide, but not more than 15% of the circumference of the wire. The stripe shall be of the same class of
material as the insulation. Where band marking is specified (for sizes 0.13 and 0.22 mm2), the band mark shall
be 3 mm +/- 1 mm wide with a 25 mm +/- 5 mm pitch.

3.9

INSULATION THICKNESS

Test samples
Prepare three test samples from a cable 3 meters in length; the samples are to be taken at intervals of 1 meter.
Strip the insulation from the cable and cut 3 X thin cross sections of insulation at the distances specified above.
PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Care must be taken to ensure that deformation of the sample does not occur during the preparation process. If
cable marking causes indentation of the insulation, take the first sample through this indentation.
Apparatus
The accuracy of the measuring instrument shall be +/- 0.01 mm; the device shall not cause deformation.
Procedure
Place the test sample under the measuring equipment, with the plane of the cut perpendicular to the optical
axis. Determine the minimum insulation thickness of each sample.
Requirement:
No single value shall be less than the appropriate insulation thickness specified in table 2.

3.10

ELECTRICAL CHARACTERISTICS

3.10.1

CONDUCTOR RESISTANCE

Procedure:
Prepare a test sample of 1m length plus the length necessary for connections. Other lengths may be used
providing that the resistance reading is adjusted using the equation below. The ends of the test sample may be
soldered.
Apparatus
Use a resistance measuring device with an accuracy of +/- 0.5% of the measured value and a thermometer
with an accuracy of +/- 0.5C.

R20 =

Rt
L[1 + 0,00393(t 20 )]

Where:
o

R20
Rt

is the corrected conductor resistance at the reference temp of 20 C, expressed in m/m.


is the conductor resistance in m, measured at the conductor temperature t.
is the unsoldered conductor in length, expressed in m,
is the conductor temperature at the time of measuring, expressed in C

L
t

Note:
The value of 0,00393 is the temperature coefficient for copper with 100% conductivity at temperatures near
20C. For coated wires or alloys, the correction factor shall be established by agreement between the supplier
and customer.
Requirement:
Resistance values should meet those specified in Table 3.

3.10.2

WITHSTAND VOLTAGE, 30 MINUTES

Test Sample:
Prepare a test sample to a minimum length of 350 mm, strip 25 mm of insulation from each end and twist them
together to form a loop.
Apparatus:
Partially fill a non-conductive vessel with salt water [3% by weight of NaCl in water] with the ends of the test
sample emerging above the bath as shown in Figure 1. Use a 50 or 60 Hz voltage source.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Immerse the test sample as shown in Figure 1 for 4 h in the bath and then apply a test voltage of 1kV (rms) for
30 min between conductor and the bath. Then increase the voltage at a rate of 500 V/s until the following value
is reached:
3 kV (rms) for cables < 0.5 mm
5 kV (rms) for cables => 0.5 mm
Requirement:
Breakdown shall not occur.

3.10.3

1 MINUTE WITHSTAND VOLTAGE

This test is only to be performed when specifically requested.


Test Sample:
Prepare a test sample to a minimum length of 350 mm, strip 25 mm of insulation from each end, and twist them
together to form a loop.
Apparatus:
Partially fill a non-conductive vessel with salt water [3% by weight of NaCl in water] with the ends of the test
sample emerging above the bath as shown in Figure 1. Use a 50 or 60 Hz voltage source. Immerse the test
sample as shown in Figure 1 for 10min in the bath and then apply a test voltage of 1kV (rms) for 1 min
Requirement:
Breakdown shall not occur.

3.10.4

INSULATION FAULTS

This test is to be carried out under production conditions. Subject all cables to the following:
Apparatus:
Use a sinusoidal voltage source at the value shown in the table below. The test electrode may consist of metal
ball chains, metal brushes, or any other type of suitable electrodes. Choose the electrode length and frequency
considering the speed of the cable running through the field of the electrode so that each point of the cable is
loaded by at least nine voltage cycles.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

OF

29

Conductor
size mm2

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Voltage Rating kV (rms)


60 V Cables

< 0.5

= > 0.5

Requirement:
No breakdown shall occur when the earthed cable is drawn through the test electrode.

3.10.5

INSULATION VOLUME RESISTIVITY

Prepare a test sample of 5 m length and remove 25 mm of insulation from each end.
Apparatus
Partially fill a non-conductive vessel with tap water at a temperature of (70 +/- 2) C. Use a resistance
measuring device with a DC voltage of 500 V. Voltages between 100 V and 500 V are allowed; however, if a
dispute arises, the referee apparatus shall be a resistance measuring device with a DC voltage of 500 V.
Procedure: Immerse the test sample for 2 h with each end emerging from the bath by 250 mm. Apply the DC
voltage between the conductor and the bath. Measure the insulation resistance 1 min after application of the
voltage. Calculate the 'Insulation volume resistivity' using the following formula:

0 = 2,725

Where:
0
L
R
D
d
lg

L R
D
lg
d

is the insulation volume resistivity, expressed in mm;


is the immersed length of the test sample in mm;
is the measured insulation resistance in ;
is the outside cable diameter in mm according to Table 1;
is the conductor diameter in mm according to Table 2;
is logarithm to the base 10.

Requirement:
The insulation volume resistivity shall not be less than 109 mm.

3.11

MECHANICAL CHARACTERISTICS

3.11.1

PRESSURE TEST AT HIGH TEMPERATURES

Note: This test may be performed on the smallest and the largest cable sizes.
Prepare 3 test samples, each of 600mm in length.
Apparatus
Perform this test with the test apparatus shown in Figure 2.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Ensure that the apparatus is free from vibrations. Apply the force F by the blade to the test sample as given by
the formula:

F=0,8 i(2Di)
Where:
F
0,8
D
i

is the total vertical force exerted on the test sample in N;


is a coefficient which carries the dimension in (N/mm);
is the appropriate "Outside cable diameter maximum" in mm according to Table 2;
is the appropriate nominal value of the "Insulation thickness" in mm according to Table 2.

The calculated force may be rounded off at the lower digit, but not beyond 3%.
Procedure:
Place the test samples as shown in Figure 2. Attach the test samples to the support so as not to bend under the
pressure of the blade. The load and the blade of the apparatus shall be perpendicular to the test sample axis.
Place the test samples under load, not preheated, for 4 h in an oven at the maximum rated cable class
temperature. Then cool the test samples within 10 s by immersion in cold water. After immersion, subject the
test samples where the pressure was applied to the '1 min withstand voltage' test as specified in 3.10.3
Requirement:
Breakdown shall not occur during the withstand voltage test.

3.11.2

LOW TEMPERATURE WINDING

This test is to be carried out on all cable sizes up to and including 10mm2, using the masses and mandrels
listed in Table 5.
Test Samples:
Prepare two test samples of 600 mm and remove 25 mm of insulation from each end.
Apparatus
A freezing chamber at(-40 +/- 2)C. Either a rotatable or a stationary mandrel may be used.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Rotatable mandrel When a rotatable mandrel is used, it shall conform to Figure 3 and the test samples shall
be fixed on the mandrel as shown in the fig. The free ends are loaded with the mass. Position the mandrel with
the test samples hanging vertically The masses and mandrels are specified in Table 5.
Stationary mandrel When a stationary mandrel is used, no mass is used. The test samples shall be wrapped
around the mandrel by hand.
Procedure:
The test samples and mandrel shall be conditioned for a minimum of 4 h in the freezing chamber. Wind at least
the 'minimum number of turns' specified in Table 5 around the mandrel within the freezing chamber at 'winding
speed' as specified in Table 5. Take care to ensure that there is continuous contact between the test samples
and the mandrel.
After the cold winding, allow the test sample to return to room temperature and conduct a visual examination of
the insulation. If no exposed conductor is visible, perform the '1 min withstand voltage' test as specified in
3.10.3.

Figure 3- Apparatus for winding

Requirement:
After winding, no conductor shall be visible. During the 'withstand voltage' test, breakdown shall not occur.

3.11.3

LOW TEMPERATURE IMPACT

This test is to be conducted on all wire sizes.


Prepare three test samples, each of 1.2 m length and remove 25 mm of insulation from each end. Perform the
'impact test' using the apparatus shown in Figure 4, positioned on a sponge rubber pad of 40mm thickness.
The mass of the hammer is specified in Table 8. Set the freezing chamber temperature to (-15 +/- 2)C.
Procedure:
Perform the 'impact test' in the middle of the test samples. Place the apparatus, positioned on the sponge
rubber pad, together with the test samples in the freezing chamber for at least 16 h. If the apparatus is precooled, a freezing time of 4h is sufficient, providing that the test samples have reached the specified
temperature. At the end of this period, place the test sample parallel to the steel base. The hammer is then

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

10

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

allowed to fall from a height of 100 mm. After the impact, allow the test samples to return to room temperature,
and make a visual examination of the insulation.
If no exposed conductor is visible, perform the '1 min withstand voltage' test as specified in 3.10.3.
Requirement:
After impact, no conductor shall be visible. During the '1 min withstand voltage' test, breakdown shall not occur.

Figure 4 Apparatus for impact

3.11.4

ABRASION RESISTANCE

Usage of test
This test is only applicable to cables with a conductor size 6 mm2, for which either 3.11.4.1 (Scrape abrasion)
or 3.11.4.2 (Sandpaper abrasion) shall be used. The customer and supplier shall define which test shall be
2
used. No abrasion test is required for conductor sizes > 6 mm .

3.11.4.1

SCRAPE ABRASION

Prepare a test sample of 1 m length and remove 25 mm of insulation from each end.
Apparatus
Use a Scrape Abrasion apparatus as detailed in figure 5a.
It consists of a device designed to abrade the surface of the insulation in both directions along the longitudinal
axis of the test sample and a counter for recording the numbers of cycles to failure. It shall be controlled so that
when the needle abrades through the insulation and makes contact with the conductor, the machine will stop
operating.
The characteristics of a suitable apparatus shall be as follows:
Diameter of needle:
Type of needle:
Frequency:
PD
May 92

3947a2e

0.45mm +/- 0.01mm


Spring wire (polished) material according to ISO 8458-2;
(55 +/- 5) cycles/min (one cycle = one reciprocating movement);
(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

11

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Displacement of the needle:


(20 +/- 1) mm;
Length of abrasion:
(15.5 +/- 1) mm;
Type of movement:
Design details shall not influence the test result;
Mass (position, value, design details): The vertical force on the test sample constant under dynamic conditions;
Test sample mounting force:
The test sample shall not move during test. If fixing is necessary, the
tension applied on the conductor shall not exceed 100 N/mm;
Stability of equipment:
The apparatus shall be so stable that the results shall not be affected;
Procedure:
Apply a total vertical force of (7 +/- 0,05) N to the test sample. Determine the number of cycles by taking four
measurements at a temperature of (23 +/- 1)C. After each reading, move the test sample 100 mm and rotate it
clockwise 90. Change the needle after each reading.

Needle diameter d:
0.45 0.01 mm

Figure 5a Apparatus for Scrape Abrasion

Requirement:
The scrape abrasion resistance shall meet the minimum abrasion requirements in Table 4.1.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

3.11.4.2

12

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

SANDPAPER ABRASION

Prepare a test sample of 1 m length and remove 25 mm of insulation from each end.
Apparatus
Measure the "Resistance to sandpaper abrasion" using 150 J garnet sandpaper tape with 5 - 10 mm
conductive strips perpendicular to the edge of the sandpaper spaced a maximum of every 75 mm. Mount a
suitable bracket to the pivoting arm (see Figure 5b) to maintain the test sample position over an unused portion
of the sandpaper abrasion tape. Exert a force of (0,63 0,05) N on the test sample by the combination of the
bracket, support rod, and pivoting arm. The total vertical force exerted on the test sample shall be the
combination of the force exerted by the bracket, pivoting arm, support rod and additional mass. The additional
mass shall be according to Table 4.2.
Procedure
Mount the test sample taut, without stretching, in a horizontal position using an area of the sandpaper abrasion
tape not previously used. Place the additional mass and bracket on top of the test sample. Draw the sandpaper
abrasion tape under the test sample at a rate of (1500 75) mm/min and record the length of sandpaper
abrasion tape necessary to expose the conductor. Move the test sample 50 mm and rotate the test sample
clockwise 90. Repeat the procedure for a total of four readings. The mean of the readings shall determine the
resistance to sandpaper abrasion.

Key
1

Support rod

Additional mass

Pivoting arm

Test sample

Bracket

Tape supporting pin, diameter = 6,9 mm

150 J, garnet sandpaper abrasion tape


Figure 5b Apparatus for sandpaper abrasion test

Requirement
The resistance to sandpaper abrasion shall meet or exceed the minimum length of sandpaper requirements
according to Table 4.2.

3.11.5

SHORT TERM HEAT AGING

This test is to be carried out on 3 sample colours, Red, White and Blue. The samples are to be prepared from
wire manufactured under production conditions.
PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

13

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Test samples:
Prepare two test samples of each colour, each of a minimum length of 350 mm and remove 25 mm of insulation
from each end.
Apparatus
Perform the short-term aging test using an oven at the upper limit temperature specified in Para 3.4 + 25C;
and winding test in a freezing chamber at (-25 +/- 2)C. The masses and mandrels are specified in Table 5.
Procedure:
The air contained in the oven shall be completely changed a minimum of eight (8) times and a maximum of
twenty (20) times per hour at the specified temperature. If the insulating material on the tested wire includes a
volatile softener with influence on flexibility and performance in low temperature winding test after ageing, the
air should be changed a minimum of thirty five (35) times per hour.
Place the test samples for 240 h in an oven. Fix the test samples by the conductor to avoid any contact
between the insulation and the supports. The test samples shall be separated by at least 20 mm from each
other and from the inner surface of the oven. Cable insulations made of different materials shall not be tested at
the same time. After aging, withdraw the test samples from the oven and maintain them at (23 +/- 5)C for at
least 16 h. After conditioning at room temperature, perform the 'winding test' (see clause 3.11.2) using the
freezing chamber and the mandrels described in table 5. After winding, allow the test samples to return to room
temperature, and make a visual examination of the insulation.
If no exposed conductor is visible, perform the '1 min withstand voltage' test as specified in 3.10.3
Requirement:
After winding, no conductor shall be visible. Colour must be identifiable after the test. During the 'withstand
voltage' test, breakdown shall not occur.

3.11.6

LONG TERM HEAT AGING (For Initial Qualification Only)

This test is to be carried out on 3 sample colours, Red, White and Blue. The samples are to be prepared from
wire manufactured under production conditions.
Test samples
Prepare two test samples of each colour, each of a minimum length of 350 mm, and remove 25 mm of
insulation from each end.
Perform the long-term aging test using an oven at the upper limit temperature specified in Para 3.4. The
masses and mandrels are specified in Table 5.
Procedure:
Follow the same procedure as 3.11.5 with the following two exceptions.
Use an ageing time of 3000 h
Perform the 'winding test' at room temperature
Apply the 1 minute withstand voltage test as specified in 3.10.3
Requirement:
After winding, no conductor shall be visible. Colour must be identifiable after the test. During the 'withstand
voltage' test, breakdown shall not occur.

3.11.7

THERMAL OVERLOAD

This test is to be carried out on 3 sample colours. Red, White and Blue. The samples are to be prepared from
wire manufactured under production conditions.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

14

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Prepare two test samples of each colour, each of 350 mm minimum length, and remove 25 mm of insulation
from each end.
Apparatus
Perform the thermal overload test using an oven at the upper limit temperature specified in Para 3.4 + 50C.
The masses and mandrels are specified in Table 5.
Procedure:
Follow the same procedure as 3.11.5 with the following two exceptions
Use an aging time of 6 h
Perform the 'winding test' at room temperature
If no exposed conductor is visible, perform the '1 min withstand voltage' test as specified in 3.10.3
Requirement:
After winding, no conductor shall be visible. Colour must be identifiable after the test. During the 'withstand
voltage' test, breakdown shall not occur.

3.11.8

SHRINKAGE BY HEAT

Test samples:
Prepare three test samples, each of 100 mm length.
Apparatus
Perform the test using an oven at (150 +/- 3)C.
Procedure:
Measure the exact length of the insulation of the test samples at room temperature (23 +/- 5)C prior to the test.
Put the test samples in the oven, in a horizontal position, so that air may circulate freely from all sides for 15
min. After cooling to (23 +/- 5)C, measure the length of the insulation again.
Requirement:
The maximum shrinkage shall not exceed 2 mm from either end.

3.11.9

LOSS OF MASS (For Initial Qualification Only)

In accordance with IEC 60811-3-2, paragraph #8.


Note: The test may be performed on the smallest and the largest cable sizes.
The maximum loss of mass shall be 1 mg/cm2.
Note: Loss of mass is required for class 1 & 2 wiring passing through the body shell luggage or passenger
compartments. Wiring used exclusively in the engine compartment is excluded.

3.11.10

FLEXIBILITY TESTS

This is to be conducted on wires 3.0 mm in a test equipment according to Figure 6a and 6b.
Procedure:
A force of 2N (F2) will be applied to the wire. The wire will be pulled through the apparatus at a speed of 50
mm/min. Once the tensile force (F1) is stable it will be measured over a wire length of 125mm.
To determine the resistance of the equipment the force (F3) can be measured by pulling an aramid roving
through the apparatus at 50 mm/min.
The force required to pull the wire through the equipment can be calculated as follows: F = F1 - F2 - F3
Requirement:
For Temp class (Para 3.4) 2, 3 and 4 wires, the force (F) should meet the requirements of Table 7.
PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

15

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Figure 6a Apparatus for flexibility test (Wire size 3 mm2)

Figure 6b Apparatus for flexibility test (Wire size 3 mm2)

3.11.11

NOTCHING RESISTANCE

This test is to be performed after Resistance to Chemical test on all the cable sizes.
Procedure:
The test set-up (see Figure 7) comprises a tensile testing machine, a notching tool (blade), a power circuit with
a small voltage and a load-sensing device (plotter or other display unit).
The notching tool must use a 0.45mm round spring wire in accordance with ISO 8458-2.
All sample sizes taken from the table under "Requirements" shall be secured in the tensile testing machine in
accordance with Figure 7.
The steel wire shall be pushed through the insulation at a constant speed of max. 10 mm/min, until an electrical
contact between the steel wire and the conductor shuts off the machine. The axes of the specimen and the
blade are at right angles to each other here.
PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

16

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

The force recorded at the time of contact is noted. After each reading the specimen is move along by 25 mm
more and rotated a total of 4 times by 90 through its longitudinal axis. The average value of the 4
measurements is the notching force

Figure 7 Apparatus for Notching


Requirement:
The initial (un-aged) notching force must meet the requirements of the following table.
Nominal cable
section

mm

0.22

0.35

0.5

0.75

1.0,
1.25

1.5

2.0

2.5

4.0

6.0

Notching force (min.)

20

30

40

50

50

60

60

70

100

120

3.11.12

RESISTANCE TO FLAME PROPAGATION

Note: This test may be performed on the smallest and the largest cable sizes.
2

Prepare three test sample of wire size 0.5 mm with at least 600 mm of insulation.
Apparatus:
Determine the 'resistance to flame propagation' using a Bunsen burner fed with appropriate gas (Figure 8),
having a combustion tube of 9 mm internal diameter, and a flame height of 100 mm. The length of the inner
blue cone of the flame shall be 50 mm.
Procedure:
Suspend the test sample in a draught free chamber and expose the test sample to the tip of the inner cone of
the flame, as shown in Figure 8. The upper end of the cable shall point from the closest wall of the chamber.
The sample shall be subject to a stress, e.g. by means of a weight over a pulley, in order to keep it strait at all
times. The angle of the cable shall be 450 + 10 relative to the vertical line. Apply the flame (500 + 5) mm from
the upper end of the insulation. Finish the exposure to the test flame when the conductor becomes visible, or
after 15 s for cables with conductor sizes < 2,5 mm and 30 s for cables with conductor sizes > 2,5 mm.
Remove the flame sideways from the cable after exposure.
Requirement:
PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

17

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Any combustion flame of insulating material shall extinguish within 30 s from the end of ignition and a minimum
of 50 mm of insulation at the top of the test sample shall remain unburned. All the three samples must pass the
test.

Figure 8 Apparatus for Resistance to flame propagation

3.11.13

COLUMN STRENGTH

Procedure: Test shall be conducted by the use of a tensile test machine and the test fixture described in Figure
9.

Figure 9 Test fixture for Column Strength Test

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

18

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Note:
This test is for the wire sizes 0.35 and 0.5 mm2. Smaller sizes are applicable only for terminals with insulation
displacement. Therefore, column strength test is not required for smaller sizes.
Prepare twenty-five (25) test samples of 40 mm +/- 0.5 mm long. Do not bend the wire prior to testing. Insert
the test wire in the appropriate cavities of the test fixture. The hole diameter shall not exceed the maximum
cable diameter for a specific wire size by more than +/- 0.03 mm. Ensure that the fixture and the wire are
vertically aligned with each other. Apply a compressive force at the constant speed of 50 +/- 0.5 mm/minute
and record the highest force attained as the wire is being compressed. This force shall be higher than the
values specified in the requirements below.
Requirements:

3.11.14

Wire Size
0.35 mm2
0.5 mm2

Min Force
15 N
15 N

HOT WATER TEST (For Initial Qualification Only)

Resistance to hot water is required on cables with all conductor sizes shall meet the requirements; however,
compliance may be demonstrated by testing examples of large and small conductor sizes only. Testing of
cables with conductor sizes of 0.35 mm and 2.5 mm is preferred.
For heavy duty cables, testing of cables with conductor sizes of 0.35 mm2 and 2.5 mm2 is acceptable if the
insulating material used is the same as the heavy duty cable.
Test samples:
Prepare two test samples, each of (2.5 +/- 0.1) m length and remove 25 mm of insulation from each end.
Apparatus:
The apparatus consists of a non-conductive vessel containing an unused salt water bath with 10 g/l of NaCl in
water at 85C for each test, a 48 V DC power source, a mandrel 5 times the outside diameter of the test
sample, and a resistance measuring device.

Figure 10 Apparatus for Resistance to Hot water


Procedure:
PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

19

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Closely wind at least three complete turns of a test sample on the mandrel and secure the wraps as shown in
Figure 10. Immerse the test sample in the bath with both ends projecting 250 mm above the bath. To avoid
interactions between materials, do not test samples with different insulating materials in the same bath.
Connect one end of the test sample and the positive electrode of the power source.
After 7 days, disconnect the power supply and measure the 'insulation volume resistivity'. Use the procedure in
3.10.5 with the following changes: Measure the 'insulation volume resistivity' in the saltwater bath at 85C. This
completes one cycle.
Repeat this procedure for a total of 5 cycles, i.e. 35 days. After conditioning, remove the test sample from the
bath, allow it to cool to room temperature, and a visual examination of the insulation. Ignore any damage
caused by the ties, which secure the coils.
If no exposed conductor is visible, perform the '1 min withstand voltage' test.
Repeat the entire test procedure using the second test sample but
with the polarity of the 48 VDC power supply reversed.
Requirement:
The 'insulation volume resistivity' shall not be less than 109 mm. A visual examination of the insulation shall
show no cracks. During the 'withstand voltage' test, breakdown shall not occur.

3.12 Resistance to chemicals


General
When any resistance to chemicals test is specified, compliance for a cable family may be demonstrated by
testing large and small sizes only.
The expressions "chemicals" and "fluids" may be used synonymous in the clause 3.12.
Purpose
This test is intended to verify resistance of the insulation to chemical loads in automotive environments where
exposure is limited.
Test setup
The test shall consist of one or several exposures to chemicals with intermediate exposure to heat ageing
conditions. Two different test media groups in accordance with Table 6 shall be tested, Media Group 1 with a
heat ageing period of 1000 hours at the actual cable class temperature, Media Group 2 with a heat ageing
period of 240 hours at the actual cable class temperature, see details under Test Performance.
Test samples
Prepare individual test samples, each 600 mm long with 25 mm of insulation removed from each end, bended
around a mandrel specified in Table 5 to an U-shape. The stripped ends should be formed as hooks, allowing
the test objects to be hung on to the grids in the oven. The number of test objects to be prepared for each
chemical according to Table 6.
Apparatus
Use an oven at the respective maximum temperature class rating according to Para 3.4. The oven shall be
equipped with grids, making it possible to hang the test objects on them. A collecting tray shall be placed in the
bottom of the oven to gather spill of chemicals.
Test Performance

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

20

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

For each fluid to be tested: Immerse 2/3 of the test objects 10 s in the fluid, then remove from the fluid and
allow to drain off for 3 minutes before storage in the oven. Care should be taken that the stripped ends are not
exposed to the fluid. Test objects from one and the same type of tested cable, but exposed to the different test
fluids, can be stored in the same oven. Test objects from different types of cables are not allowed to be stored
in the same oven.
For Media Group 1 objects, the immersing in the respective fluid shall be repeated at 240, 480 and 720 h of the
1000h test in the following way: Initially immerse 8 objects for each fluid and store in the oven. At 240 h take
out two objects and pass them on to final test according to below, the remaining 6 objects should be reimmersed and stored in the oven for another 240 h exposure. At 480 h take out another two objects for final
test, and re-immerse the remaining 4 objects. At 720 h, again take out two objects for final testing and reimmerse the remaining 2 objects for storing up to 1000 h.
Media Group 2 objects should only be immersed once, before the exposure in the actual cable class
temperature.
After fulfilled exposure, remove the test samples from the oven and maintain them at RT (23 5 oC) for 30 min.
Thereafter, perform the "Winding test" at room temperature. Make sure that the winding test is performed in the
middle of the test objects. After winding, make a visual examination of the insulation. If no exposed conductor is
visible, perform the "1 minute Withstand voltage" test.
Requirements
Insulation shall not exhibit cracks after mandrel wrap test.
No dielectric failure shall occur during withstand voltage test. The notching resistance force values of all heat
aged samples must be at least 20% of those values recorded against the comparable virgin samples.

3.13 ENVIRONMENTAL CYCLING


Prepare two samples of approximately 600 mm length and remove 25 mm of insulation from each end. For
wires <3mm use 0.75mm. For wires 3 mm2 and <10 mm2, use 4mm. For wires >10 mm2, use 25mm2.
Apparatus
Perform the test in a temperature chamber, which is capable of cycling between (-40 +/- 2)C and the maximum
wire temperature.
The chamber shall also be capable of controlling the relative humidity between (5 +/- 5)% and (90 +/- 5)%. See
Table 5 for mandrel sizes.
Procedure: Wind at least the 'minimum number of turns' specified in Table 5 around the mandrel and secure the
ends. Condition the test samples according to the temperature and relative humidity shown in Figure 11. The
cycle begins and ends with the chamber at (-40 +/- 2) C and (5 +/- 5) % relative humidity. This will constitute
one cycle.
Repeat the cycle for a total of 40 cycles. While still on the mandrel, remove the test sample from the chamber,
allow them to warm at room temperature for approximately 30 min, and unwind it from the mandrel. Make a
visual examination of the insulation, Ignore any damage caused by the clamps, which secure the ends.
Apply the 1 minute withstand voltage test as specified in 3.10.3

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

21

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Figure 11 Procedure for Environmental Cycling

Requirement:
After unwinding, no conductor shall be visible. Colour must be identifiable after the test. During the 'withstand
voltage' test, breakdown shall not occur.

3.14 RESISTANCE TO OZONE


Resistance to ozone is specified on cables with all conductor sizes shall meet the requirements however
compliance may be demonstrated by testing examples of large and small conductor areas. Testing 0,75 mm
and 16 mm is preferred. Test conditions for cables with other conductor sizes have been included for
reference purposes.
Prepare three test samples, each of 300 mm length.
Apparatus
Use an ozone chamber in accordance with IEC 811-2-1 with an
-6
atmosphere containing a mass fraction of (1 +/- 0,05) x 10 of ozone at (65 +/- 3)C.
Attention is drawn to the highly toxic nature of ozone. Efforts should be made to minimize the exposure of
workers at all times. See Table 5 for 'mandrel diameter'.
Aluminum mandrels are preferred since other materials may affect the ozone concentration.
Procedure: Wind at least the 'minimum number of turns' specified in Table 5 and secure the ends. Condition the
test samples for 192 hours in the ozone chamber. While still on the mandrel, remove the test samples from the
ozone chamber; allow them to cool to room temperature, and make a visual examination of the insulation.
Ignore any damage caused by the clamps, which secure the ends.
Requirement:
The visual examination of the insulation shall show no cracks.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

22

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

SUPPLIER'S RESPONSIBILITY

All materials supplied to this specification must be equivalent in all characteristics to the material upon which
approval was originally granted.
Prior to making any change in the properties, composition, construction, colour, processing or labeling of the
material originally approved under this specification, whether or not such changes affect the material's ability to
meet the specification requirements. The Supplier shall notify Purchasing, Toxicology and the affected
Materials Engineering activity of the proposed changes.
Substance restrictions imposed by law, regulations or Ford, apply to the materials addressed by this document.
The regulations are defined in Engineering Materials Specification WSS-M99P9999-A1 latest issue (NB: This
document is normally updated annually). Suppliers must review this specification periodically to ensure product
is validated to the latest version.

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

23

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

TABLES

5.1

Table 1 - CONDUCTOR STRANDING AND DIMENSIONS


Structure A
(symmetrical)

ISO
Conductor
size, mm2
0,13
0,22
0,35
0.5
0,5
0,75
1
1,25
1,5
2
2,5
3
4
5
6
8
10
12
16
20
25
30
35
40
50
60
70
95
120

PD
May 92

3947a2e

Min. No
of
strands

7
7
7
7
19
19
19
19
19
19
37
37
37
37
37
50
63
154
105
247
154
361
551
494
798
741
1140
836
1064

Strand
diameter
Max.
mm

Structure B
(asymmetrical)
Min. No
of
strands

0,16
0,21
0,27
0,32
0,19
0,24
0,27
0,30
0,33
0,38
0,29
0,34
0,38
0,43
0,45
0,46
0,46
0,33
0,46
0,33
0,46
0,33
0,3
0,33
0,3
0,33
0,3
0,4
0,4

(Previous editions may be used)

NA
NA
12
NA
16
24
32
NA
30
28
50
44
56
65
84
98
80
96
126
152
196
224
276
308
396
296
360
475
608

Strand
diameter
Max.
mm
NA
NA
0,21
NA
0,21
0,21
0,21
NA
0,26
0,31
0,26
0,31
0,31
0,33
0,31
0,33
0,41
0,41
0,41
0,41
0,41
0,41
0,41
0,41
0,41
0,51
0,51
0,51
0,51

Structure C
(asymmetrical)
Min. No
of
strands

NA
NA
19
NA
26
38
54
NA
76
105
140
160
224
250
320
240
320
380
512
610
790
900
1070
1200
1600
1200
1427
1936
2450

Strand
diameter
Max.
mm
NA
NA
0,16
NA
0,16
0,16
0,16
NA
0,16
0,16
0,16
0,16
0,16
0,16
0,16
0,21
0,21
0,21
0,21
0,21
0,21
0,21
0,21
0,21
0,21
0,26
0,26
0,26
0,26

Engineering Specification
Ford Global Wire specification

FRAME

5.2

24

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Table 2 WIRE DIMENSIONS


Standard Wall

Thin Wall

ISO
cond
size
mm
0.13
0.22
0.35
0.50

Conductor
max OD
mm

Nominal
mm

Minimum
mm

Minimum
Cable OD
mm

Maximum
Cable OD
mm

Nominal
mm

Minimum
mm

0.55
0.70
0.90
1.10

0.35
0.33

0.30
0.27

1.40
1.50

1.60
1.70

0.25
0.25
0.25
0.28

0.75
1.0
1.25
1.5

1.30
1.50
1.70
1.80

2.0
2.5
3.0
4.0
5.0

2.00
2.20
2.40
2.80
3.10

6.0
8.0
10.0
12.0
16.0

3.40
4.30
4.50
5.40
6.30

1.00
1.00
1.00

20.0
25.0
30.0
35.0
40.0

6.90
7.80
8.30
9.00
9.60

50.0
60.0
70.0
95.0
120.0

10.50
11.60
12.50
14.80
16.50

Ultra Thin Wall

Minimum
Cable OD
mm

Maximum
Cable OD
mm

Nominal
mm

Minimum
mm

Minimum
Cable OD
mm

Maximum
Cable OD
mm

0.20
0.20
0.20
0.22

1.10
1.20
1.40

1.05
1.20
1.40
1.70

0.20
0.20
0.20
0.20

0.16
0.16
0.16
0.16

0.85
0.95
1.10
1.30

0.95
1.05
1.20
1.40

0.30
0.30
0.30
0.30

0.24
0.24
0.24
0.24

1.70
1.90
2.10
2.20

1.90
2.10
2.30
2.40

0.20
0.20
0.20
0.20

0.16
0.16
0.16
0.16

1.45
1.65
1.70
1.95

1.60
1.75
2.0
2.10

0.35
0.35
0.40
0.40
0.40

0.28
0.28
0.32
0.32
0.32

2.50
2.70
3.10
3.40
3.90

2.80
3.00
3.40
3.80
4.20

0.25
0.25
-

0.20
0.20
-

2.25
2.55
-

2.40
2.70
-

0.80
0.80
0.80

5.90
6.60
7.30

6.50
7.40
8.30

0.40
0.40
0.60
0.60
0.65

0.32
0.32
0.48
0.48
0.52

4.00
4.60
5.50
5.80
6.40

4.30
5.0
6.00
6.50
7.20

1.10
1.30
1.30
1.30
1.40

0.88
1.04
1.04
1.04
1.12

8.10
8.40
9.70
9.60
11.20

9.10
10.40
10.90
11.60
12.40

0.65
0.65

0.52
0.52

7.00
8.20

7.80
9.40

1.50
1.50
1.50
1.60
1.60

1.20
1.20
1.20
1.28
1.28

11.50
13.40
13.50
16.00
17.70

13.50
14.60
15.50
18.00
19.70

Other conductor sizes may be used providing they meet the electrical and dimensional requirements and are agreed with the Engineering Department of the relevant Ford Business Unit
PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

5.3

25

OF

29

PART NO. ES-AU5T-1A348-AA

Table 3 - CONDUCTOR RESISTANCE (m / m, max)


ISO conductor size
mm
0.13
0.22
0.35
0.5
0.75
1
1.25
1.5
2.0
2.5
3
4
5
6
8
10
12
16
20
25
30
35
40
50
60
70
95
120

5.4

REV. LET. D

Plain Copper

Tinned Copper

136
84.4
54.4
37.1
24.7
18.5
14.9
12.7
9.42
7.60
6.15
4.71
3.94
3.14
2.38
1.82
1.52
1.16
0,955
0.743
0,647
0.527
0,473
0.368
0,315
0.259
0.196
0.153

140
86.5
55.5
38.2
25.4
19.1
15.9
13.0
9.69
7.82
6.36
4.85
4.02
3.23
2.52
1.85
1.60
1.18
0,999
0.757
0,684
0.538
0,500
0.375
0,333
0.264
0.2
0.156

ABRASION RESISTANCE

5.4.1 Table 4.1 - SCRAPE ABRASION RESISTANCE


ISO Wire Size
(mm2)

Number Of
Double Strokes

Applied
Vertical Loads (N)

0.13
0.22
0.35
0.5
0.75
1.0, 1.25
1.5 - 6

75
150
200
300
350
500
1500

7
7
7
7
7
7
7

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

FRAME

26

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

5.4.2 Table 4.2 - SANDPAPER ABRASION RESISTANCE


ISO
conductor
size
mm

Thin wall
Additional
mass

Ultra-thin wall

Minimum Additional
length of
mass
sandpaper

kg

kg

mm

0,13

200
0,1

0,22

225

Minimum
length of
sandpaper
mm

150
0,05

175

0,35

250

200

0,5

300

175

0,75

350

200

400

0,2

0,1

225

1.25

400

225

1,5

450

250

500

275

2,5

250

300
0,5

350

430

500

0,2

125

--

--

NOTE:
The total vertical force exerted on the test sample shall be the combination of
the force exerted by the bracket, pivoting arm, support rod and additional mass.

5.5

Table 5 - MANDREL DIAMETERS

Cross- sectional
area,
mm2

< 0.75
> 0.75 < 1.5
> 1.5 < 2.5
> 2.5 < 6
> 6 < 10
> 10 < 25
> 25 < 50
> 50 < 95
> 95 < 120

PD
May 92

Winding test
at Low
Temp., Short
Term Heat
Ageing, &
Chemical
resistance
6
10
15
20
40
50
75
100
125

3947a2e

Mandrel Diameter (mm)


Resistance
Long
Environm
ental
to Ozone
Term
Heat
Cycling
Ageing

6
10
15
20
40
50
75
100
125

2
3
4
5
8
10
15
20
30

(Previous editions may be used)

2
3
4
5
8
10
15
20
30

Mass

Winding
Speed

Kg

s-1

0.5
2.5
5
5
8
10
20
30
30

1
1
1
1
0.5
0.5
0.5
0.2
0.2

Min
Number
of Turns

3
3
3
3
0.5
0.5
0.5
0.5
0.5

Engineering Specification
Ford Global Wire specification

FRAME

5.6

27

OF

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Table 6 - FLUID COMPATIBILITY

Group

Media
Fluid
Engine Coolant

29

Engine Oil
Salt Water (road)
Windscreen Washer
Fluid
Gasoline
Diesel

Specification

Objects
(pcs)

50% ethylene glycol + 50%


distilled water
ISO 1817, Oil No 2
5% NaCl , 95 % Water (mass
%)
50% Iso-propanol, 50% water

8
8
8

2
240 h
2
2
2
2

Max. Force (N) for temperature class:


A2
A3
A4
1
1.5
2.2
3.5
5.5
10
10

1.7
2.3
3.6
5.0
9
17
22

1.7
2.3
3.6
5.0
9
17
22

Table 8 - IMPACT
ISO conductor
Size
a
mm
a =< 0,5
0,5 < a =< 2,5
2,5 < a =< 4
4 < a =< 10
10 < a =< 25
25 < a =< 50
50 < a =< 120

PD
May 92

2
2

Table 7 - FLEXIBILITY TEST: WIRES 3.0 mm.

Cross- sectional
area's (mm2)
0.35
0.5
0.75
1.0, 1.25
1.5
2.5
3.0

5.8

240 h + 240 h + 240 h


+ 280 h

ISO 1817, liquid C


90% ISO 1817, Oil No 3 + 10 %
p-xylene
Ethanol
85% Ethanol + 15% ISO 1817
2
liquid C
Power Steering Fluid
ISO 1817, Oil No 3
Auto. Transmission Fluid
Dexron VI
Brake Fluid
SAE RM-66-06
Battery Acid
25% H2SO4 and 75% H2O,
density 1.28
NOTE: Solutions are determined as % by volume if not otherwise specified.

5.7

Storage time in
oven at class temp.
(h)

3947a2e

Mass of the hammer (g)


Thick
wall
cable
100
100
200
300
300
400

(Previous editions may be used)

Thin
wall
cable
N/A
100
100
200
300
-

Ultra thin
wall cable
N/A
N/A
-

Engineering Specification
Ford Global Wire specification

FRAME

5.9

28

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Table 9 INSULATION COLOURS


Color

Munsell Color Coding

Black
Blue
Brown
Gray
Green
Orange
Red
Violet
White
Yellow
6

29

OF

Light

Dark

DIN 40772 or IEC


304
RAL

N2.25
4.6PB 3.8/10.2
7.5YR 4/5
N6.3/(10GY,0.2)
0.5G 6.25/6.3
8.75R 6.0/11.5
2.5R 4.2/11.2
4.4P 3.9/6.7
Not Applicable
8.4Y 8.5/8.3

Not Applicable
5.6PB 2.75/9.4
7.5YR 3/6
N5.2/(10GY,0.2)
0.5G 5.1/7.5
8.75R 5.5/13.5
4.4R 3.4/10.4
3.4P 2.8/6.7
5Y 9/1
8Y 8.5/11.2

9005
5017
8003
7000
6018
2003
3000
4005
1013
1021

DRAFT CODE:
For the purposes of identification on Engineering Drawings, wire shall be identified to this
specification in the following manner:
Example wire code: 1TAD
2. Wall Thickness (Table 2)

4. Conductor Type/Other

1TA D
3. Strand Configuration (Table 1)

1. Temperature Class (Para 3.4)


1. Temperature Class:
1
2
3
4
5
6
9

85 C
1000C
0
125 C
0
150 C
1750C
0
200 C
1150C

2. Wall Thickness (Table 2):


S
T
U
X

Standard Wall
Thin Wall
Ultra Thin Wall
Un-insulated (bare wire)

3. Strand Configuration (Table 1):


A
B
C

Symmetrical
Asymmetrical
Flexible - Asymmetrical

4. Conductor type/ Other

PD
May 92

3947a2e

(Previous editions may be used)

Engineering Specification
Ford Global Wire specification

29

FRAME
D
E
F
L
R
S
T
Y

OF

29

REV. LET. D

PART NO. ES-AU5T-1A348-AA

Bare Copper Conductor


Tinned Copper Conductor
Bare Copper Conductor, Flexible wire (Flexibility Test requirement)
Aluminium Conductor
Copper Conductor Steel Reinforced
Bare Copper Clad Steel (CCS) Conductor
Bare Copper Clad Aluminium (CCA) Conductor
Bare Copper Alloy Conductor (Ref. spec ES-BR33-1A348-AA)

Appendix A
WIRE SIZE COMPARISON CHART (FOR INFORMATION ONLY)

PD
May 92

SAE

Cross-Sectional

mm

Cross-Sectional

(AWG)

Area, Min. (mm)

(European)

Area (mm)

24 ga.

0.205

0.22

0.202 - 0.214

22 ga.

0.345

0.35

0.376 - 0.401

20 ga.

0.543

0.5

0.529 0.563

18 ga.

0.779

0.75

0.808 0.860

16 ga.

1.184

1.0

1.023 1.088

14 ga.

1.875

1.5

1.345 - 1.436

12 ga.

2.956

2.5

2.250 - 2.390

10 ga.

4.734

4.0

3.944 4.196

08 ga.

7.504

8.0

7.810 - 8.310

06 ga.

12.433

12.0

12.370 13.170

04 ga.

18.93

16.0

16.403 17.450

02 ga.

31.643

32.0

29.023 - 30.876

3947a2e

(Previous editions may be used)

You might also like