Professional Documents
Culture Documents
Proper Control of HVAC Variable Speed Pumps: Ashrae Journal
Proper Control of HVAC Variable Speed Pumps: Ashrae Journal
JOURNAL
The following article was published in ASHRAE Journal, November 1998. Copyright 1998 American Society of Heating, Refrigerating and Air-Conditioning Engineers,
Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE.
ASHRAE Journal
41
Figure 2: Proper location of differential pressure transmitter. The differential pressure transmitter at pumps must be set at
100% design head, eliminating the value of the variable speed pump.
ASHRAE Journal
Rate of Response
One question that always arises when
dealing with variable speed pump control, specifically through the use of PID
controllers, is How fast does the process value have to be updated? The best
answer for this question is twice per second or faster. The reason is that the pressure in a system changes instantaneously, and the controllers function is
to maintain that pressure at a setpoint.
From a simplified interpretation of the
Nyquist Criterion 1 for stable control, a
controller must update approximately
twice as fast as the fastest process that it
is trying to control. In our case, pressure
imparted by the pumps changing speed
can be realized in the system within one
second.
This means that the controller must
update at least twice per second to maintain stable control, and the inputs to the
controller must be updated at the same
rate or faster than the output of the controller. Therefore, the inputs must be updated twice per second or faster to maintain stable control.
For the typical pump speed PID application, the system can be expected to
settle between 10 and 20 seconds from
the time any upset is introduced (this may
take slightly longer at system startup).
The typical application consists of a PID
controller with an update (response) rate
of twice per second and a process value
that updates at the same rate. This typical response can be seen in Figure 4a.
The system will actually run slightly
over its setpoint and then be brought back
to the correct operating point. This is normal because the controller will continue
to increase the speed of the pumps until
it receives feedback from the system
indicating that the pumps need to be
slowed. This is a small price to pay for
such a rapid response.
When the process value is not updated in a timely manner the PID response
becomes unstable. This can be seen in
46
ASHRAE Journal
Figure 3a: This diagram shows the problem of using valve position for pump
speed control.
Figure 3b: This diagram shows differential pressure reset with control valve
position.
PUMPS
Reference
1. Phillips, C. L. and R. D. Harbor. 1988. Feedback Control
Systems, New Jersey: Prentice Hall, p. 288.
ASHRAE Journal
47