1.
HVAC
HVAC
Plot
(Psychrometric Chart)
HVAC
HVAC
Design Condition Room
Load
- 95 FDB, 75 FWB
( 35 DBC, 23.9 WBC )
- 78 FDB, 50%RH
( 25.6 DBC, 50% RH )
- RSH 200,000 BTUH
- RLH 50,000 BTUH
43
2 1
Plot Return, R
Room Sensible Heat Ratio (RSHR)
90% RH (
)
44 18
R
SHR = 0.8 90%RH
Supply, S
Cooling Coil 57.2 FDB (14 DBC)
2 R S
() Process
Load (Conditioned
Space)
Return Air (
Load Ratio Line)
) OA
Cooling Coil Coil Curve Supply, S
Cooling Coil
Supply, S
) Supply Air CFM 1
8,740 CFM
) Cooling Coil Load
Coil Sensible Heat (qS) = 1.1 x CFM x t
= 1.1 x 8,740 x (95.0 -57.2)
= 363,000 BTUH
Coil Latent Heat (qL) = 4,840 x CFM x W
= 4,840 x 8,740 x (0.0141-0.0090)
= 216,000 BTUH
Coil Total Heat (qT) = Coil Sensible Heat +
Coil Latent Heat
= 363,000 + 216,000
= 579,000 BTUH
45
4 2
W W
Cooling Coil ( OA S)
Psychrometric Chart 4
Plot Psychrometric Chart
Cooling Coil Cooling
Coil 8,740 CFM Total Heat =
579,000 BTUH SH = 360,000 BTUH
Entering Condition 95 FDB, 75 FWB
Leaving Condition 57.2 FDB 90% RH
Cooling
Coil Cooling Coil
HVAC
46 18
(Ventilation Load)
Load
Cooling Coil
Ventilation Load
qS = 1.1 x 8,740 x (95-78) = 163,000 BTUH
qL = 4,840 x 8,740 x (0.0141-0.0102)
= 165,000 BTUH
qT = 163,000 + 165,000 = 328,000 BTUH
Ventilation Load Room
Load Cooling Coil Load
Plot Psychrometric Chart
Concept
Psychrometric Chart
6
Condition Space 8,740 CFM (
RSH
)
Exhaust
M
Cooling Coil Supply, S
Conditioned Space Room
Load S
R
Coil Load
6 3
47
) Mixture Condition
= 82.9 DBF
tM tM
Chart RHM = 47%
WM = 0.0114 lb/lb
) Coil Load
qS = 1.1 x 8,740 x (82.9-57.2)
= 247,000 BTUH
qL = 4,840 x 8,740 x (0.0114-0.0090)
= 101,000 BTUH
qT = 247,000 + 101,000 = 348,000 BTUH
Plot
Psychrometric Chart
Specify
Cooling Coil Coil
8,740 CFM Total Heat = 348,000 BTUH SH
7 4
48 18
9 5
Fan Fan Motor Heat Gain
ASHRAE Handbook
Fundamentals
Plot Psychrometric
Chart Fan Motor
Coil Load
49
7.
Psychrometric Chart CFM
Cooling Coil
Room Total Heat (RTH), Room Sensible
Heat (RSH) Room Latent Heat (RLH)
Load Plot Load Ratio Line
Psychrometric Chart CFM
Mixing
Plot
Schematic Diagram HVAC
Specify
Plot
Psychrometric Chart
Plot Psychrometric
Chart
[1] Rudoy and Cuba. Cooling and Heating Load Calculation Manual, ASHRAE GRP158,
Chapter 6 and Appendix A6.
50 18