Professional Documents
Culture Documents
3AG 3AF Outdoor Vacuum Circuit-Breakers Up To 40.5kV PDF
3AG 3AF Outdoor Vacuum Circuit-Breakers Up To 40.5kV PDF
3AG 3AF Outdoor Vacuum Circuit-Breakers Up To 40.5kV PDF
Introduction
Typical users
Field Applications
Fully type-tested
n
Conforms to IEC / IS standards
n
n
Short circuit protection
n
Switching of cables
n
Switching of transformers
n
Switching of overhead lines
n
Switching of capacitor circuit
n
Auto-reclosing
n
Traction Application
3AG01
Rated voltage,
frequency
12kV, 50Hz
Rated current
up to 1600A
Rated power-frequency
withstand voltage
28kV
75kV
Rated short-circuit
breaking current
25kA
Rated short-circuit
making current (peak)
63kA
Rated short-time
withstand current
25kA, 3s
Rated operating
sequence
O-0.3s-CO-15s-CO
Service conditions
-25C to +55C
Degree of protection
IP 55
270kg
3AG01
Maximum ratings
12kV/25kA/1600A
Front view
3AG01
555
350
Dimensions
Item
Side view
555
350
185 185
A
B
Support insulator
Top terminal
2560 10
1390
395
Bottom terminal
Steel structure
Earthing terminal
400
2610 10
Front
2960 10
K
1790 10
3350 10
Vacuum interrupter
Interrupter assembly
Description
850
Top/bottom terminal
aluminium (D,E)
50
14diam.(4x)
80
40
Foundation bolts
are optional
M16 x 400
350
90
70
420
850
180
Foundation detail
1485
1265
400
Foundation Plan
M16 (8x)
1625
20
40
20
Note: Extended structure for mounting instrument transformers can be provided as an option.
1)
Type
3AF031)
Rated voltage,
frequency
17.5kV, 50Hz/60Hz
Rated current
Up to 2000A
Rated power-frequency
withstand voltage
42kV
110kV
Rated short-circuit
breaking current
25kA
Rated short-circuit
making current (peak)
65kA
Rated short-time
withstand current
25kA, 3s
Rated operating
sequence
O-0.3s-CO-15s-CO
Service conditions
-25C to +55C
Degree of protection
IP 55
360kg
3AF03
Maximum ratings
17.5kV/25kA/2000A
Front view
3AF03
555
350
Dimensions
Item
Side view
555
350
185 185
A
B
A
M
Vacuum interrupter
Support insulator
Top terminal
Bottom terminal
J
1390
395
Steel structure
Earthing terminal
400
2560 10
2610 10
Front
2960 10
K
1790 10
3350 10
F
L
Description
Interrupter assembly
850
Top/bottom terminal
aluminium (D,E)
50
14diam.(4x)
80
40
Foundation bolts
are optional
M16 x 400
350
90
70
420
850
180
Foundation detail
1485
1265
400
Foundation Plan
M16 (8x)
1625
20
40
20
Note: Extended structure for mounting instrument transformers can be provided as an option.
3AF01-45/47
Rated voltage,
frequency
36kV, 50/60Hz
Rated current
1600 / 2000A
Rated power-frequency
withstand voltage
70kV
170kV
Rated short-circuit
breaking current
25kA
Rated short-circuit
making current (peak)
65kA
Rated short-time
withstand current
25kA, 3s
Rated operating
sequence
O-0.3s-CO-15s-CO
O-0.3s-CO-3min-CO
Service conditions
-25C to +55C
Degree of protection
IP 55
650kg
3AF01
Maximum ratings
36kV/25kA/2000A
Front view
725
470
3AF01-45/47
Dimensions
Side view
222.5 222.5
725
470
Item
N
E
A
B
275
D
L
J
L
3570 H
840
3010
Front
Interrupter assembly
Vacuum interrupter
Support insulator
Base frame
Top terminal
Bottom terminal
Steel structure
Earthing terminal
320
1065
Description
90
M20 (1x)
14 (4x)
110
40
420
M20 x 400
Foundation bolts
50
1250 L
300Lx600Bx400D
600 B
Foundation detail
350
Foundation Plan
300
950
150
20
40
15
Note: Extended structure for mounting instrument transformers can be provided as an option.
3AF01
Type
3AF013)- 43/44/46/53/54/56
Rated voltage,
frequency
Rated current
1600/2000/2500A
Rated power-frequency
withstand voltage
70kV 1)
170kV 1)
Rated short-circuit
breaking current
25/31.5kA
Rated short-circuit
making current (peak)
65kA/80kA
Rated short-time
withstand current
25kA/31.5kA, 3s
Rated operating
sequence
O-0.3s-CO-15s-CO
O-0.3s-CO-3min-CO
Service conditions
-40C to +55C 2)
Degree of protection
IP 55
650kg
1)
2)
-60C on request
3)
4)
4s on request
Maximum ratings
40.5kV/31.5kA/2500A
Side view
Front view
3AF01-43/44/46/53/54/56
725
470
Dimensions
Item
275 275
725
470
A
E
A
B
1585 10
3720 +10
Vacuum interrupter
Support insulator
Base frame
Top terminal
Bottom terminal
Steel structure
Earthing terminal
Inspection window
600
B
C
Front
1565 10
3020 10
256
P
L
Description
Interrupter assembly
1730
1930
M16 (8x)
350
75
50
80
40
600
M16 x 400
800
Top/bottom terminal
14 diam. (4x)
aluminium (E,F)
Foundation detail
Foundation bolts are optional
350
Foundation Plan
650
75
20
40
20
50
1730
Note: Extended structure for mounting instrument transformers can be provided as an option.
3AF04
Rated voltage,
frequency
27.5kV, 50/60Hz
Rated current
2000A
Rated power-frequency
withstand voltage
95kV
200kV
Rated short-circuit
breaking current
31.5kA
Rated short-circuit
making current (peak)
80kA
Rated short-time
withstand current
31.5kA, 3s 2)
Rated operating
sequence
O-0.3s-CO-15s-CO
Service conditions
-40C to +40C 1)
Degree of protection
IP 55
560kg
1)
-60C on request
2)
4s on request
3AF04
Maximum ratings
27.5kV/31.5kA/2000A
Front View
Side View
222.5
Dimensions
Item
222.5
A
E
B
F
SIEMENS
1730
1930
*M16x400
Foundation Bolt
660
600
800
Base Frame
Top Terminal
Bottom Terminal
Mechanism Housing
Steel Structure
Earthing Terminal
14 DIA. (4x)
Foundation Details
75
*
M16 (8x)
350
Bottom Insulator
1730
50
350Lx800Bx400D
75
Vacuum Interrupter
650
350
Foundation Plan
Interrupter Assembly
660
164510
Front
15655
3080 10
357510
286
Description
80
40
3AF04
20
40
20
Note: Extended structure for mounting instrument transformers can be provided as an option.
3AF05
Rated voltage,
frequency
27.5kV, 50/60Hz
Rated current
2000A
Rated power-frequency
withstand voltage
95kV
200kV
Rated short-circuit
breaking current
31.5kA
Rated short-circuit
making current (peak)
80kA
Rated short-time
withstand current
31.5kA, 3s 2)
Rated operating
sequence
O-0.3s-CO-15s-CO
Service conditions
-40C to +40C 1)
Degree of protection
IP 55
630kg
1)
-60C on request
2)
4s on request
3AF05
Maximum ratings
27.5kV/31.5kA/2000A
Side View
Front View
3AF05
222.5
1450
Dimensions
222.5
Item
1195
B
F
C
SIEMENS
156510
Front
3080 10
1730
1930
Top Terminal
Bottom Terminal
Mechanism Housing
Steel Structure
Earthing Terminal
*M16x400
Foundation Bolt
80
40
75
600
*M16 (8x)
800
Base Frame
14 DIA. (4x)
50
75
Bottom Insulator
Foundation Details
350
350Lx800Bx400D
Vacuum Interrupter
650
660
Foundation Plan
Interrupter Assembly
660
164510
1
3
3580 10
286
Description
20
350
40
20
1730
Note: Extended structure for mounting instrument transformers can be provided as an option.
Description
Live tank construction
General description
Suitability
Siemens outdoor vacuum
circuit -breakers are designed to
handle all switching duties that
occur in primary distribution
systems including rapid autoreclosing. The breakers are
extremely reliable in service,
require minimum maintenance
and have a long service life due
to the use of vacuum
interrupters. They can be used
in all kinds of environments by
virtue of their small size and
weight, low vibration operation
and they are unaffected by
temperature or fire risks. Our
VCBs are suitable for stringent
duties as per IEC 62271-100.
Construction
The vacuum interrupter is
mounted in a porcelain
insulator to form an interrupter
assembly. Each such assemblies
along with the bottom
insulators are mounted on a
baseframe which has a
common operating shaft. This
assembly is mounted on a steel
structure, intended to locate the
power terminals at a safe
distance above the ground. The
structure also encloses the
operating mechanism. All the
control and actuating devices
are installed in this mechanism
housing. The circuit-breaker can
be either operated electrically
from a remote control room or
locally by hand or electrically.
The necessary mechanical ON
and OFF indications, spring
charged indication and
operation counter are provided
in the mechanism housing. Also
mounted in the mechanism
housing are the cage clamp
type terminal blocks as per
requirement for control cables.
Operation, accessories
10
Operating mechanism
The well-proven operating
mechanism of indoor vacuum
circuit-breakers 3AG/3AF have
been incorporated in the
outdoor vacuum circuit-breaker.
They are equipped with a motor
spring stored-energy operating
mechanism. The motor can be
operated either by AC or DC
standard supply voltages.
Instrument Transformers
On clients requirement the
breakers can be supplied with
an extended structure for
mounting outdoor current and
voltage transformers on the
incoming and outgoing supply
sides, respectively.
Accessories
The following accessories can
be provided:
Auxiliary switch
(5 NO+5 NC or 11 NO+11 NC)
Closing solenoid
(AC/DC voltages)
Tripping solenoid
(AC/DC voltages)
Features
Integrated mechanical
breaker position indication
CLOSED/OPEN, spring
charged indication and
mechanical counter
Unambiguous assignment of
actuating openings and
control elements to
corresponding breaker
position indications
Front operated switching
operations.
Ergonomically favorable
height of control elements
from ground
Secondary Equipment
3AG01
3AF01
3AF03
3AF04
3AF05
Product range
Circuit-breaker
Circuit-breaker with
current transformer
Circuitbreaker
Circuitbreaker
Current
transformer
Circuit-breaker with
voltage transformer
Circuit-breaker with
current transformer and
voltage transformer
Voltage
transformer
Voltage
transformer
Circuitbreaker
Circuitbreaker
Current
transformer
Tests/ Standards
Seismic capacity
Notes
Responsible for:
Technical contents:
Siemens Ltd.
Kalwa Switchboard Works
IC LMV MV C BD
Thane 400602
India
11
Notes
If not stated otherwise on the
individual pages of this catalog, we
reserve the right to include
modifications, especially regarding
dimensions and weights.
Drawings & photographs are not
binding.
All product designations used are
trademarks or product names of
Siemens AG or of other suppliers.
If not stated otherwise, all
dimensions in this catalog are given
in mm.
Western Region 1
Eastern Region
Southern Region
Mumbai
Kolkata
Chennai
Pune
ICC Trade Tower, B Wing
Senapati Bapat Marg, Pune - 411016
(
: +91 20 3046 6000
Fax: +91 20 3046 6060
Western Region 2
Vadodara
3rd Floor, OHM Business Park
Opp. Balaji Hospital
Ellora Park (East), Subhanpura
Vadodara - 390 023, Gujarat (India)
(
: +91 265 395 2111
Fax: +91 265 395 2190
Northern Region
Gurgaon
3rd Floor, Tower - B
Plot No. 6 - A, Sector - 18
Maruti Industrial Area, HUDA
Gurgaon - 122 015, Haryana (India)
(
: +91 124 383 7377
Fax: +91 124 383 6620
International Sales
R&D Technology Centre
2nd Floor, Kalwa Works, PO Box
Thane Belapur Road
Thane - 400 601, Maharashtra (India)
(
: +91 22 3326 5011
Fax: +91 22 3326 5024
Siemens Ltd.
Infrastructure & Cities Sector
Low and Medium Voltage Division
R&D Building
Thane Belapur Road
Thane 400 601
India
Tel.: +91 22 3326 5005/6
Fax: +91 22 3326 0030
www.siemens.com/medium-voltage-devices
Order No.: ENE-03-152-031
(This replaces ENE-03-152-001)
Product development is a continuous process. Consequently the data indicated in this
leaflet is subject to change without prior notice. For latest issue contact our Sales Office.
Printed in India