Design Calculation Sheet: A-Water Demand

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 1

Design calculation sheet

Project no.:
Subject:

S08060

Date:

19/10/2009
Sheet no.:
SAFA- DOMESTIC WATER CALCULATIONS
Staff Residential building

of

Computed by:
Checked by:
Approved by:

A-WATER DEMAND

FIXTURE TYPE
LAV-1
WC (FT)
WC (FV)
SHOWER
HB
UR
JS
WT
DF
KS-1

QUANTITY

36
36

0
36
0
0
1
0
0
36
FLOOR TOTAL FU

FIXTURE UNIT
1
5
10
3
2.5
5
4
2
2
4

TOTAL FU
36
180
0
108
0
0
4
0
0
144
472

REQUIRED FLOW = 120 GPM


CONNECTION SIZE = 65mm
TOTAL REQUIRED FLOW = 120 GPM =7.57 L/S
B-PRESSURES
Friction
Estimated pipe length (m)
Total Equiv. Length (m)

=
=

62
77.5

Estimated Pipe Size (inch)


Pressure drop, (psi / 100 ft)

=
=

2.5
3.95

Total Friction Loss (psi)


Total Friction Loss (m)

=
=

10
6.8

STATIC HEAD IN METERS

RESIDUAL PPRESSURE IN METERS =


FRICTION LOSS IN METERS

TOTAL HEAD IN METERS

6.8

(GROUND )

3.5
6.8
=

17.1

1.71322933 BARS

A.A.
A.A.
A.E.