SPECIFICATION
FOR
DRY TYPE LIGHTING
TRANSFORMER
6-51-0042 Rev. 4
Page 2 of 6
Abbreviations:
ANAN
BIS
BS
CEA
IEC
IEEE
IP
IS
KVA
MSL
MV
NEMA
PO
PVC
VDE
Mr. UA Patro
Members:
Mr. AK Tickoo
Mr. MP Jain
Mr. BR Bhogal
Mr. Arun Kumar
Mr. KK Gera
Mr. Saeed Akhtar
952
ENGINEERS
LIMITED
tzarCarolfaigtegw INDIA
(A Saki of hula Undertaking)
SPECIFICATION
FOR
DRY TYPE LIGHTING
TRANSFORMER
6-51-0042 Rev. 4
Page 3 of 6
CONTENTS
1.0 SCOPE
5.0 CONSTRUCTION
6.0 TERMINALS
7.0 ACCESSORIES
953
SPECIFICATION
FOR
DRY TYPE LIGHTING
TRANSFORMER
RZETA-Bk ENONEERS
taPegNIW INDIA LIMITED
Reds1341.1)
1.0
6-51-0042 Rev. 4
Page 4 of 6
SCOPE
The intent of this specification is to define the requirements for design, manufacture, testing,
packing and supply of dry type lighting transformers suitable for indoor location.
2.0
2.1
The equipment shall comply with the requirements of latest revision of following standards
issued by BIS.
IS: 1271
IS: 2705 Part I & III :
IS: 10028
IS: 11171
IS/ IEC: 60529
2.2
In case of imported equipments standards of the country of origin shall be applicable if these
standards are equivalent or stringent than the applicable Indian standards.
2.3
The equipment shall also conform to the provisions of CEA Regulations and other statutory
regulations currently in force in the country.
2.4
In case Indian standards are not available for any equipment, standards issued by IEC/ BS/
VDE/ WEE/ NEMA or equivalent agency shall be applicable
2.5
In case of any conflict between requirements specified in various applicable documents for the
project, the most stringent one shall prevail. However owner's decision in this regard will be
final and binding.
3.0
GENERAL REQUIREMENTS
3.1
All the offered equipment shall be brand new with state of the art technology and proven field
track record. No prototype equipment shall be offered.
3.2
Vendor shall ensure spare parts and maintenance support services for the offered equipment at
least for 10 years from the date of supply.
3.3
Vendor shall give a notice of at least one year to the user of equipment and EIL, before
phasing out the product/ spares to enable the end user for placement of order for spares and
services.
4.0
SITE CONDITIONS
Transformer shall be suitable for installation and satisfactory operation in tropical, humid and
corrosive atmospheres. The transformer shall be designed to operate under site conditions as
specified in data sheet. If not specifically mentioned therein, design ambient temperature of
40C and altitude not exceeding 1000m above MSL shall be considered.
5.0
CONSTRUCTION
5.1
The transformer shall be dry type, ANAN cooled suitable for indoor installation. Transformer
shall be housed in, freestanding enclosure of welded sheet steel frames with expanded metal
screens of suitable size or louvres backed by wire-mesh. Transformer and the enclosure shall
be suitably reinforced to prevent distortion during handling.
954
IA Govt of
inu undertakong)
SPECIFICATION
FOR
DRY TYPE LIGHTING
TRANSFORMER
6-51-0042 Rev. 4
Page 5 of 6
5.2
The transformer shall be double wound core type with cold rolled grain oriented silicon steel
insulated laminations and clamped to minimise vibrations and noise. Core fastening bolts
shall be insulated to reduce losses and to avoid hot spots. All parts of the magnetic circuit
shall be effectively connected to the earth system.
5.3
The winding shall be of copper and shall be designed for full load current and to withstand the
thermal and electromagnetic stresses arising due to the through fault current. The current
carrying winding joints shall be electrically brazed. Foil type windings are not acceptable.
5.4
5.5
Vector group of transformer shall be DYn11. The windings shall be provided with class 'B'
insulation for lighting transformers upto 100 KVA and class 'H' insulation for rating more
than 100 KVA.
5.6
Transformer shall have minimum degree of protection as IP-23, However, Marshalling box
and cable termination box shall have degree of protection not less than lP-55.
5.7
Different non current carrying parts of the transformers shall be connected by copper flexibles
for earth continuity purpose.
5.8
All the fasteners and bolts shall be galvanized. All surfaces to be painted shall be thoroughly
cleaned, descaled, made free from rust and shall be epoxy painted.
6.0
TERMINALS
6.1
6.2
Cable boxes shall be supplied with cable lugs and glands. For MV PVC power/control cables
single compression cable glands and crimped type tinned copper cable lugs shall be supplied.
Gland plate shall be removable type. For single core cables, gland plate shall be of nonmagnetic material.
7.0
ACCESSORIES
Tappings shall be provided on the Primary side. Tap changer shall be off-circuit type. Under
conditions of external short circuit, the tap changing equipment shall be capable of carrying
the same current as the winding. Tap changer regulation range shall be +7.5% with each step
of 2.5%. Tap changing mechanism shall be easily accessible and it shall be possible to change
the taps without opening the main transformer enclosure.
Base channels shall be provided with skids and pulling eyes to facilitate handling. Tag plate
shall be provided.
8.0
NOISE LEVEL
Audible noise level for lighting transformers shall not exceed the limits specified as below:
KVA
0-50
50
51-150
55
151-300
58
301-500
60
955
Ogell 2151-ft
wily INDIA LIMITED
maw
1.11771
9.0
ORM)
(A Govt
of Ma Undertaking)
SPECIFICATION
FOR
DRY TYPE LIGHTING
TRANSFORMER
6-51-0042 Rev. 4
Page 6 of 6
Routine tests and special tests as listed below shall be carried out on all transformers:
9.1.1 Visual and Dimensional check
9.1.2
Bill of Material
Measurement of winding resistance
9.1.3
9.1.4
Measurement of voltage ratio and check of voltage vector relationship
Measurement of impedance voltage and load loss
9.1.5
Measurement of no- load loss and current
9.1.6
9.1.7
Induced over voltage withstand test
9.1.8
Separate-source voltage withstand test (HV Test)
Measurement of insulation resistance before and after HV test
9.1.9
9.1.10 Noise level check
9.1.11 Correctness of nameplate
9.1
9.2
9.2.1
9.2.2
9.2.3
9.2.4
Type tests and special tests as listed below shall be carried out on one transformer of each
rating if called for in purchase documents:
Partial discharge test
Temperature rise test
Short circuit test
Lightning impulse test
10.0