CLIENT: PHED, RAJASTHAN

CONTRACTOR: NCC LIMITED

PROJECT: CHAMBAL BHILWARA WATER SUPPLY PROJECT


PHASE1 PACKAGE1

SHEET

OF

TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY


1. Designation : 6.6KV INCOMER1 (OVER CURRENT / EARTH FAULT RELAY )
Location

: INTERMEDIATE PUMPING STATION TILSWA

2. Name Plate Details :

MAKE
SR.NO.
I>>
I>
Ie>>
Ie>

ALSTOM
15CP1540072
PLUG SET
4
0.8
2.0
0.2

TYPE

P154

TMS
0.2
0.25
0.15
0.20

3. Remarks: Fit For Commissioning


4. Equipment used for testing:
Equipments

Make

S.no

Calibration Due

Digital Mini Clamp meter

Motwane

Z10687L11

12-06-2017

Relay test kit

Sudharsan

05/14

28-08-2017

Commissioning Checks
S.No. Details
1.
Primary or secondary current injection
testing of relays for their operation such as
indication/alarm/ control etc.
2.
Insulation resistance

TESTED BY

WITNESSED BY

Status

Checked &
Found Ok
Checked &
Found Ok

Refrence

As per approved documents


As per electrical standards

APPROVED BY