Professional Documents
Culture Documents
ARI Certified Performance Test Form
ARI Certified Performance Test Form
ARI Certified Performance Test Form
TM
Model#
Serial #
19XR3032237BES64
20573
Date:
15-Jun-11
RUN AVG
DATE: 15-Jun-11
JOB#: 650304
LOAD: 100.0%
TIME: 10:08 AM
S/N: 20573
LOAD:
CAPACITY, TONS
100.0%
DESIGN
ACTUAL % DESIGN VAR FL( %) ARI/MIN
EVAPORATOR:
150.00
156.83
104.55%
5.0%
142.5
---201.52
CONDENSER:
CHILLER VOLTS:
DESIGN
AVERAGE PH (A-B) PH (C-B) PH (C-A)
460
468.77
COMPR #1:
468.39
468.34
468.06
CHILLER AMPS:
DESIGN AVERAGE
COMPR #1:
185.20
185.38
PH - A
184.47
PH - B
184.89
ARI/MAX
---44.25
87.24
ARI/MAX
378.00
488.25
ARI/MAX
157.5
ARI/MIN
414.0
ARI/MAX
506.0
PH - C
186.79
65030420573-01.xISx
Page 1
ARI/MIN
ARI/MAX
.897
RUN AVG.
JOB#: 650304
DATE: 15-Jun-11
S/N: 20573
TIME: 10:08 AM
DESIGN
2.78
1.69
ACTUAL
2.76
1.45
% DESIGN
99.28%
85.87%
VAR (%)
115%
115%
ARI/MAX
3.19
1.95
OIL TEMP
DEG-FHT
127.4
REFRIG
CHARG-LB
818
DESIGN (FT)
6.40
3.90
VFD:
MOTOR TEMP:
THRUST BEARING TEMP:
DISCH TEMP:
PCT IGV:
PCT DIFFUSER:
0
98
140
118
32
0
FLASC P
PSIA
133.22
AMBIENT
DEG-FHT
74
Hz
DegF
DegF
DegF
%
%
CERTIFIED BY:
Customer Witness:
Customer Witness:
Customer Witness:
Customer Witness:
Carrier Sales:
Test Technician:
Product Engineer:
65030420573-01.xlsx
Page 2