Site Visit Report

Date: 11.04.2014
Site ID: MR545952
Site Name: Bondo
Co ordinates:
Vendor: Netis
Sub-Contractor:
Site Supervisor: Ken
Eaton Engineer:
Emmanuel

Lat:

Long:

Site Visit Inspection

Tower Strengthening

Observations

Missing members Diagonal, Part Nos. 504, horizontals - 503A,


503B, 707A, 707B, Internal bracings
Missing bolts
Missing connector
Usage of some bolts of Grade 4.8 instead of Grade 8.8
Gaps between members, indicative of inadequately torqued tower

Photos
Page 1 of 7

Site Visit Report

Missing Diagonal, indicated in red arrow (Tower Part No. 504)

Missing bolt

Page 2 of 7

Site Visit Report

Missing member

Critical area (Tower Leg), with required bolts swapped with smaller bolts

Page 3 of 7

Site Visit Report

M24

M1
2

M12 were installed instead of the required M24

The M12 bolts used are of Grade 4.8 used instead of Grade 8.8

Page 4 of 7

Site Visit Report

Missing connector between section 3 and 4, below is photo with connector

Page 5 of 7

Site Visit Report

Internal bracings missing

Gaps are sometimes indicative of inadequately torqued bolts

Page 6 of 7

Site Visit Report

Missing bolt between the diagonals

Page 7 of 7