Professional Documents
Culture Documents
Cassette: Sunline Hydro
Cassette: Sunline Hydro
Cassette
HKH - HKW
IR Remote control
035T70077-002
LIST OF CONTENTS
Page
1 - Safety ....................................................................................................................2
2 - Indoor units..........................................................................................................2
3 - Technical Specifications.....................................................................................3
4 - Cooling capacities...............................................................................................3
5 - Dimensions ..........................................................................................................4
6 - Installation............................................................................................................5
7 - Condensate Drainage .........................................................................................6
8 - Water Piping Connections..................................................................................6
9 - Front Panel Installation.......................................................................................7
10 - Wiring Diagram ..................................................................................................7
11 - Service and Maintenance..................................................................................8
Parts List : (Contact York)
Decommissioning, Dismantling and Disposal
1 - Safety
2 - Indoor Units
GENERAL PRECAUTIONS
CAUTION
Before undertaking any work on the unit, make sure that the
power supply has been disconnected.
ELECTRICAL CONNECTIONS
All electrical wiring and connections must comply with local standards.
3 - Technical Specifications
Indoor
unit
W
W
V/Ph/Hz
m3/h
dBA
Models
Cooling
Heating
Capacity
Power supply
Indoor air flow
Noise level
Unit controls
HKH-HKW
25
6 900
9 400
35
9 900
13 500
Indoor
220/240-1-50
1 260
1 800
39/42/44
39/42/44
Infrared remote control with LCD display
290
290
710
710
710
710
30
41
Male
1/2"
3/4"
1/2"
3/4"
Indoor
H (mm)
W (mm)
D (mm)
Indoor
kgs
Type of connection
Diameter
Inlet
Outlet
Dimensions
Net weight
Piping
4 - Cooling capacities
HKH-HKW 25
Water entering temperature
5C
Water
temp.
diff. C
Total Sensible
capacity capacity
W
W
7C
Flow
l/h
Pressure Total
Sensible
drop
capacity capacity
kPa
W
W
10C
Flow
l/h
Pressure
Total Sensible
drop
capacity capacity
kPa
W
W
Flow Pressure
drop
l/h
kPa
Entering
6549
5689
1129
31
5589
5300
960
23
4215
4215
728
13
air temp.
6260
5564
897
20
5269
5137
753
14
3914
3914
558
25C DB
5909
5426
728
13
4905
4905
602
3582
3582
439
17C WB
5495
5275
590
4498
4498
483
3237
3425
351
Entering
7245
5928
1248
39
6254
5620
1079
29
4786
4786
822
17
air temp.
6913
5871
991
24
5903
5426
847
18
4429
4429
634
10
6
26C DB
6549
5727
803
16
5495
5238
677
11
4084
4084
502
18C WB
6141
5564
659
11
5068
5062
546
3732
3732
401
Entering
7954
6260
1367
47
6900*
5846*
1186*
35
5413
5125
935
22
air temp.
7603
6116
1091
30
6542
5689
941
22
5056
4930
728
13
27C DB
7239
5984
891
20
5495
5495
677
11
4654
4654
571
19C WB
6806
5790
734
13
5702
5282
615
4291
4291
464
Entering
8801
6486
1512
57
7603
6116
1311
43
5984
5407
1029
26
air temp.
8393
6392
1204
36
7189
5947
1029
26
5589
5213
803
16
28C DB
7960
6254
979
24
6762
5758
828
17
5162
4993
634
10
20C WB
7496
6768
809
16
6304
5558
677
11
4755
4755
508
Total Sensible
capacity capacity
W
W
7C
Flow
l/h
Pressure Total
Sensible
drop
capacity capacity
kPa
W
W
10C
Flow
l/h
Pressure
Total Sensible
drop
capacity capacity
kPa
W
W
Flow Pressure
drop
l/h
kPa
Entering
9396
8163
1620
43
8019
7605
1377
32
6048
6048
1044
18
air temp.
8982
7983
1287
28
7560
7371
1080
19
5616
5616
801
11
25C DB
8478
7785
1044
18
7038
7038
864
12
5139
5139
630
17C WB
7884
7569
846
12
6453
6453
693
4644
4914
504
Entering
10395
8505
1791
53
8973
8064
1548
40
6867
6867
1179
23
air temp.
9918
8424
1422
33
8469
7785
1215
25
6354
6354
909
14
26C DB
9396
8217
1152
22
7884
7515
972
16
5859
5859
720
18C WB
8811
7983
945
15
7272
7263
783
10
5355
5355
576
Entering
11412
8982
1962
64
9900*
8388*
1701*
48
7767
7353
1341
30
air temp.
10908
8775
1566
41
9387
8163
1350
30
7254
7074
1044
18
27C DB
10386
8586
1278
27
7884
7884
972
16
6678
6678
819
11
19C WB
9765
8307
1053
18
8181
7578
882
13
6156
6156
666
Entering
12627
9306
2169
78
10908
8775
1881
59
8586
7758
1476
36
air temp.
12042
9171
1728
49
10314
8532
1476
36
8019
7479
1152
22
28C DB
11421
8973
1404
33
9702
8262
1188
23
7407
7164
909
14
20C WB
10755
9711
1161
22
9045
7974
972
16
6822
6822
729
5 - Dimensions
Indoor Unit : HKH-HKW 25 - 35
25
880
35
880
B
C
880
290
880
290
710
710
710
710
6 - Installation
Make sure that the unit is level.
Ensure that the suspension bracket adjustment is such that
there is a 55 mm gap between the underside of the ceiling and
the top of the unit.
water piping
connections
A minimum of clearance is necessary around the units to ensure proper air circulation and easy access for maintenance.
25
300
35
300
38
electric cable entry
1500
3 5 mm
Condensate
drain
connection
Condensate
drain piping
side of the unit.
Tighten all nuts on the suspension rods and unit mounting brackets once all adjustments have been made.
Nut
Washer
38
7 - Condensate Drainage
7.1 - Installation
Insulation
PVC tube
(field supplied).
Pipe clamp
115
260
Rise
!!!
1/25 1/100
260
115
85
Water inlet
45
hanger
C
B
panel
water inlet
water outlet
HKH-HKW 25 170
220
260
1/2
1/2
HKH-HKW 35
220
260
3/4
3/4
170
40
panel
Unit
Air outlet
Hook plate
U-shaped wire
Control box
Cords and
connectors
from air
panel
Indoor unit
Long screw
Rubber plug
38
Rubber plug
10 - Wiring Diagram
HKH Units
E
2 way valve
Power Supply
220V/1Ph/50Hz
COMPONENT
Air filter
MAINTENANCE OPERATIONS
1 - Clean with a vacuum cleaner or tap gently then
wash in warm water (40C) with a mild detergent.
RECOMMENDED
FREQUENCY
Every month or more
often if necessary.
Coils
1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas
isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer
to unit installation instructions.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be
re-used, if appropriate, or returned to the manufacturer for disposal. Under NO circumstances should refrigerant be vented to atmosphere. Where
appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal of oily wastes.
3. Packaged units can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then the unit lifted
from position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit
weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4. After removal from position the unit parts may be disposed of according to local laws and regulations.
E - TEC - H0002
Europe
YORK INTERNATIONAL
Manufacturer reserves the right to change specifications without prior notice.