Professional Documents
Culture Documents
Delhi Transco Limited Training Report 1
Delhi Transco Limited Training Report 1
On
220 kV Substation, Vasant Kunj
ACKNOWLEDGEMENT
I would like to take this opportunity to express my profound sense of
gratitude and respect to all those who helped me throughout the duration of
my training. I acknowledge the efforts of those who have contributed
significantly to my training. I feel privileged to offer my sincere thanks and
deep sense of gratitude to Mr. Sameer Bidani, Astt. Manager, 220 kV
substation, Vasant Kunj, Delhi Transco Limited for helping and guiding me
throughout my training period.
ABSTRACT
A well planned, systematically executed industrial training helps a great
deal in inculcating a good work culture. It provides a linkage between
students and the industry in order to develop awareness of the industrial
approach to problem solving based on broad understanding of operations
of the industrial organizations.
During my training in NHPC I learned a lot about the various aspects
of power generation and came to know about the techniques used
practically for generating the electrical energy.
My training has been an enriching experience for me in the field of power
generation and I learned a lot about the practical application of my
knowledge of various subjects of electrical engineering in industry.
INDEX
Introduction to electricity..
.
1
1. Introduction To
DTL
..2
1.1DTL at a
glance
.2
1.2Quality
Policy
...3
1.3Quality
Objective
...3
1.4Transmission Network of DTL.
3
1.5Proposed
Substations
....6
2.3.1 Objectives
9
2.3.2 Strategies
9
4. Equipments of Substation..
..16
4.1Main Transformer.
..
16
4.2Lightning
Arrestor
23
4.3Isolator
...27
4.4Circuit
Breaker
..28
4.5Current
Transformer
..37
4.6Wavetrap
42
4.7Power Transformer & Capacitive Voltage
Transformer...43
4.8Busbar
.46
4.10 Battery Charger & Battery
Bank..47
INTRODUCTION
Electricity means only one thing: its the electrons and protons, the
electric charge as described by the scientists.
The first usage of the word electricity is ascribed to Sir Thomas Browne
in his 1646 work, Pseudodoxia Epidemica. The word electricity was
derived from a latin word electricus which itself was derived from a word
elektron(a greek word for amber).
But electricity in everyday life can be described as the electromagnetic field
energy sent out by batteries and generators or we can say it is just a
directional flow of electronsor simply electrical energy.
This movement of electrons is used by us as a source of energy in a large
number of ways like1) These electrons can produce heat and light while passing through
tungsten wires.
2) These electrons can run electric motors using the principle of
electro-magnetics which are used in fans, water pumps, lifts, etc.
3) These moving electrons can turn on various LEDs, processors, etc.
which are used in various appliances ranging from sign boards to
TVs to computers.
This electrical energy is supplied to the load end from the generating
unit with the help of conductors. To reduce the transmission losses, the
electrical energy is sent at very high values from the generating units and
then again these voltage levels are stepped down to lower voltages at
the consumer end. Transformers are used for this purpose.
The substations are constructed at different places to check the proper
functioning of such transmission and distribution networks.
1. Introduction to DTL
1.1 DTL at a glance
Delhi Transco Limited is the State Transmission Utility for the National
Capital Territory of Delhi. It is responsible for the transmission of power at
220 kV and 400 kV level and for upgrading, operating and maintaining the
high voltage network.
On July 1, 2002, The Delhi Vidyut Board (DVB) was unbundled into six
successor companies: Delhi Power Supply Company Limited (DPCL) - Holding
Company; Delhi Transco Limited (DTL) - TRANSCO; Indraprastha Power
Generation Company Limited (IPGCL) - GENCO; BSES Rajdhani Power Limited
(BRPL) - DISCOM; BSES Yamuna Power Limited (BYPL) - DISCOM; North Delhi
Power Limited (NDPL) - DISCOM. DTL and IPGCL, are wholly owned by the
Delhi Government. Delhi Transco Limited is a 'State Transmission Utility of
the National Capital of Delhi.
Over the years, DTL has evolved as a most dynamic performer, keeping pace
with the many-fold challenges that confront the ever increasing demandsupply-power-situation and achieving functional superiority on all fronts. The
Transmission losses have been brought down from 3.84% in 2002-03 to
0.83% in 2006-07, and are the lowest in the country. Delhi, being the capital
of India and the hub of commercial activities in the Northern Region, coupled
with the prosperity of population, the load requirement has been growing at
a much faster pace. Added to that, being the focus of socio-economic and
political life of India, Delhi is assuming increasing eminence among the great
cities of the world. Plus the vision-2021, aiming to make Delhi a global
Metropolitan and world class city demands greater infrastructure to enrich
many services of infrastructure development.
DTL, has been responsibly playing its role in establishing, upgrading,
operating and maintaining the EHV (Extra High Voltage) network. DTL has
also been assigned the responsibility of running the State Load Dispatch
Centre which is an apex body to ensure integrated operations of power
systems in Delhi.
Care for Environment
DTL operates its obligations in a clean, green pollution free environment and,
has been providing more green coverage to the National Capital. It is
spreading awareness among the masses to use eco-friendly electrical
appliances. DTL is also introducing Energy Conservation Building Code in
Delhi to maximize the use of natural resources and minimize the use, of
electricity. Its proposed corporate office at 400 KV Sub Station Maharani
Bagh will be a Green Building. The building is aimed to be a Platinum Rated
Green Building. More than one lakh sq meter land has been earmarked for
plantation in the ensuing year.
To
To
To
To
To
Parameters
No. of Substations
220KV Level
26
7860
574.2 + 40.206
(underground)
227
Parameters
Peak Demand
met in MW
4034
4408
Energy
consumption in 19686 20385 20810 21184 21977 22372 22006
MUs
23349
Shedding, in
MUs
450
185
Shedding
as %age of
Energy
Consumption
Transmission
losses
(in %age)
229
176
322
411
136
128
0.80%
Revenue Statistics
Year
200405
200506
200607
20072008-09
08
52.10
57.39
2.45
3.92
0.94
0.35
0.52
0.63
(9.55)
As per the projections made by Central Electricity Authority in its 17th EPS
report and the recommendations for the transmission requirements for Delhi
systems in the 11th Plan System Studies report of Central Electricity
Authority for the period 2007-2012.
Transmission Load Forecast for Delhi
As per Statistics published on DTL's website:
Year
200809
(MW)
4877
5253
5657
6092
4034
4425
4626
4837
4034
4255
4489
4735
Existing Substations
Bawana 400kV
Mundka 400kV
Bamnauli 400kV
Narela 220kV
Rohini 220kV
Subzi Mandi 220kV
provision for supply in rural areas are expected to introduce and encourage
competition in the electricity sector. It is expected that all the above
measures on the generation, transmission and distribution front would result
in formation of a robust electricity grid in the country.
2.2 Distribution
The total installed generating capacity in the country is over 148,700MW
and the total number of consumers is over 144 million. Apart from an
extensive transmission system network at 500kV HVDC, 400kV, 220kV,
132kV and 66kV which has developed to transmit the power from generating
station to the grid substations, a vast network of sub transmission in
distribution system has also come up for utilization of the power by the
ultimate consumers.
However, due to lack of adequate investment on transmission and
distribution (T&D) works, the T&D losses have been consistently on higher
side, and reached to the level of 32.86% in the year 2000-01.The reduction
of these losses was essential to bring economic viability to the State Utilities.
As the T&D loss was not able to capture all the losses in the net work,
concept of Aggregate Technical and Commercial (AT&C) loss was
introduced. AT&C loss captures technical as well as commercial losses in the
network and is a true indicator of total losses in the system.
High technical losses in the system are primarily due to inadequate
investments over the years for system improvement works, which has
resulted in unplanned extensions of the distribution lines, overloading of the
system elements like transformers and conductors, and lack of adequate
reactive power support.
The commercial losses are mainly due to low metering efficiency, theft &
pilferages. This may be eliminated by improving metering efficiency, proper
energy accounting & auditing and improved billing & collection efficiency.
Fixing of accountability of the personnel / feeder managers may help
considerably in reduction of AT&C loss.
With the initiative of the Government of India and of the States, the
Accelerated Power Development & Reform Programme (APDRP) was
launched in 2001, for the strengthening of Sub Transmission and
Distribution network and reduction in AT&C losses.
The main objective of the programme was to bring Aggregate Technical &
Commercial (AT&C) losses below 15% in five years in urban and in highdensity areas. The programme, along with other initiatives of the
Government of India and of the States, has led to reduction in the overall
AT&C loss from 38.86% in 2001-02 to 34.54% in 2005-06. The commercial
loss of the State Power Utilities reduced significantly during this period from
Rs. 29331 Crore to Rs. 19546 Crore. The loss as percentage of turnover was
reduced from 33% in 2000-01 to 16.60% in 2005-06.
The APDRP programme is being restructured by the Government of India, so
that the desired level of 15% AT&C loss could be achieved by the end of
11th plan.
2.3.1 Objectives
2.3.2 Strategies
ONAN
96000MVA
160000MVA
Vector Symbol: YNynod11
Manufactured by: Bharat Bijlee Ltd.
ONAF
128000MVA
ONAN
OFAF
HV Side-
252.0
LV Side-
839.7
420.0
1399.6
Tertiary Side-
2799.3
2799.3
2799.3
3.2.3 Isolator
High-voltage isolators are used in electrical substations to allow isolation of
apparatus such as circuit breakers and transformers, and transmission lines,
for maintenance. The major difference between an isolator and a circuit
breaker is that an isolator is an off-load device intended to be opened only
after current has been interrupted by some other control device.
Type of Isolator used: HLM (In both 220 and 66 MVA)
SMC (In 66 MVA)
4.
Equipments of Substation
4.1 Transformer
A transformer is a device that transfers electrical energy from one circuit to
another through inductively coupled conductorsthe transformer's coils. A
varying current in the first or primary winding creates a varying magnetic
flux in the transformer's core and thus a varying magnetic field through
the secondary winding.
This
varying
magnetic
field induces a
varying electromotive force (EMF), or "voltage", in the secondary winding.
Autotransformer
An autotransformer (sometimes
called autoformer) is
an
electrical transformer with only one winding. The auto prefix refers to the
single coil acting on itself rather than any automatic mechanism. In an
autotransformer
portions
of
the
same
winding
act
as
both
the primary and secondary. The winding has at least three taps where
electrical connections are made. An autotransformer can be smaller, lighter
and cheaper than a standard dual-winding transformer however the
autotransformer does not provide electrical isolation.
Autotransformers are often used to step up or down between voltages in the
110-117-120 volt range and voltages in the 220-230-240 volt range.
An autotransformer has a single winding with two end terminals, and one or
more terminals at intermediate tap points. The primary voltage is applied
across two of the terminals, and the secondary voltage taken from two
terminals, almost always having one terminal in common with the primary
voltage. The primary and secondary circuits therefore have a number of
windings turns in common. Since the volts-per-turn is the same in both
windings, each develops a voltage in proportion to its number of turns. In an
autotransformer part of the current flows directly from the input to the
output, and only part is transferred inductively, allowing a smaller, lighter,
cheaper core to be used as well as requiring only a single winding.
One end of the winding is usually connected in common to both the voltage
source and the electrical load. The other end of the source and load are
connected to taps along the winding. Different taps on the winding
correspond to different voltages, measured from the common end. In a stepdown transformer the source is usually connected across the entire winding
while the load is connected by a tap across only a portion of the winding. In a
step-up transformer, conversely, the load is attached across the full winding
while the source is connected to a tap across a portion of the winding.
Advantages of autotransformer
the primary
winding to
An instant after ignition of the arc, the test voltage is switched off
automatically by the testing device. Ultra fast switch off is highly
desirable, as the carbonization due to the electric are must be limited to
keep the additional pollution as low as possible.
The transformer oil testing device measures and reports the root mean
square value of the breakdown voltage.
After the transformer oil test is completed, the insulation oil is stirred
automatically and the test sequence is performed repeatedly. (Typically 5
Repetitions, depending on the standard)
Recently time consuming testing procedures in test labs have been replaced
by on-site oil testing procedures. There are various manufacturers of
portable oil testers.
With low weight devices in the range of 20 to 40 kg tests up to 100 kV rms
can be performed and reported on-site automatically. Some of them are
even battery-powered and come with all sorts of accessories.
Results
inside
the
transformer.
Formation
of
fault
gases
is
due
to oxidation, vaporization, insulation decomposition, oil breakdown and
electrolytic action. Oil sample tube is used to draw, retain and transport the
oil sample of transformer oil in the same condition as it is inside a
transformer with all fault gases dissolved in it. It is a gas tight borosilicate
glass tube of capacity 150 ml or 250 ml, having two airtight Teflon valves on
both the ends. The outlets of these valves have been provided with a screw
thread which helps in convenient connection of synthetic tubes while
drawing sample from transformer. Also this provision is useful in transferring
the oil into Sample oil burette of the Multiple Gas Extractor without any
exposure to atmosphere, thereby retaining all its dissolved and evolved fault
gases contents. It has got a septum arrangement on one side of the tube for
drawing sample oil to test its moisture content. Thermo foam boxes are used
to transport the above Oil Sample Tubes without any exposure to sunlight.
Complete extraction of fault gases from transformer oil is achieved by
Multiple Gas Extractor. This is a unique glass apparatus designed by Central
Power Research Institute, Bangalore, India and developed by Dakshin Lab
Agencies, Bangalore. In this apparatus, the same sample oil is exposed to
high vacuum many times until there is no further increase in the volume of
extracted fault gases. The entire extraction takes place at very high vacuum
under ambient temperature, without any escape of fault gases in to
atmosphere. A fixed volume of sample oil is directly drawn from sample tube
into degassing vessel under high vacuum, where the gases are released.
These gases are isolated using a mercury piston to measure its volume at
atmospheric pressure (Total Gas Content) and subsequent transfer to Gas
Chromatograph using gas tight syringe or auto sampler. The fault gases are
measured, in milliliter of gases per milliliter of transformer oil and converted
into parts per million. Moreover, in this method small traces of incipient fault
gases are detected at very early stage. This method alone, provides the
repeated accurate results for Total Gas Content.
Atmospheric Gases:
Carbon Monoxide
Carbon dioxide
Acetylene
Ethylene
Methane
Ethane
The gases extracted from the sample oil are injected into Gas
Chromatograph where the columns separate gases. The separated gases are
detected by Thermal Conductivity Detector for atmospheric gases, by Flame
Ionization Detector for hydro carbons and oxides of carbon. Methanator is
used to detect oxides of carbon, when they are in very low concentration.
When transformer is overloaded it generates more heat and deteriorates the
cellulose insulation. In this case DGA results show high carbon monoxide and
high carbon dioxide. In extreme cases methane and ethylene are at higher
levels. The overheating of insulation liquid results in breakdown of liquid by
heat and formation of high thermal gases. They are methane, ethane and
ethylene.
In a new transformer the levels of hydrocarbons in transformer oil after
vacuum filtration shall be 5 ppm. After commissioning a new transformer
DGA shall be done every month or earlier depending on the DGA results
observed.
In an overhauled and repaired transformer, DGA is to be done a week after
re-commission. Subsequently DGA is required every month or earlier
depending upon the DGA results.
In interpretation of the results obtained for a particular transformer, due
regard should be given to the following factors before arriving at a specific
conclusion:
Buchholz relay
In the field of electric power distribution and transmission, a Buchholz
relay is a safety device mounted on some oil-filled power transformers
1. Rod arrester
2. Horn gap arrester
3. Multigap arrester
4. Expulsion type lightning arrester
5. Valve type lightning arrester
Zinc Oxide Surge Arrestor
Zinc Oxide Surge Arrester can be made of semiconductor ceramic materials
composed mainly of zinc oxides. It has excellent non-linearity coefficient,
If the geometry and gradient are such that the ionized region continues to
grow instead of stopping at a certain radius, a completely conductive path
may be formed, resulting in a momentary spark, or a continuous arc.
Corona discharge usually involves two asymmetric electrodes; one highly
curved (such as the tip of a needle, or a small diameter wire) and one of low
curvature (such as a plate, or the ground). The high curvature ensures a
high potential gradient around one electrode, for the generation of a plasma.
Coronas may be positive or negative. This is determined by the polarity of
the voltage on the highly-curved electrode. If the curved electrode is positive
with respect to the flat electrode we say we have a positive corona, if
negative we say we have a negative corona. (See below for more details.)
The physics of positive and negative coronas are strikingly different. This
asymmetry is a result of the great difference in mass between electrons and
positively charged ions, with only the electron having the ability to undergo a
significant degree of ionizing inelastic collision at common temperatures and
pressures.
An important reason for considering coronas is the production
of ozone around conductors undergoing corona processes. A negative corona
generates much more ozone than the corresponding positive corona.
Corona discharge has a number of commercial and industrial applications:
Manufacture of ozone.
Scrubbing
particles
from
systems (see electrostatic precipitator).
air
in air-conditioning
Photocopying.
Air ionizers.
Nitrogen laser.
Power loss
Audible noise
Electromagnetic interference
Purple glow
Ozone production
Insulation damage
Situations where high voltages are in use, but ozone production are to
be minimized.
Lightning.
4.3 Isolator
In electrical engineering, a disconnector or isolator switch is used to make
sure that an electrical circuit can be completely de-energized for service or
maintenance.
Such
switches
are
often
found
in electrical
distribution and industrial applications where machinery must have its
source of driving power removed for adjustment or repair. High-voltage
isolation switches are used in electrical substations to allow isolation of
apparatus such as circuit breakers and transformers, and transmission lines,
for maintenance. Isolating switches are commonly fitted to domestic
extractor fans when used in bathrooms in the UK. Often the isolation switch
is not intended for normal control of the circuit and is only used for isolation.
Isolator switches have provisions for a padlock so that inadvertent operation
is not possible (see: Lockout-Tag out). In high voltage or complex systems,
these padlocks may be part of a trapped-key interlock system to ensure
proper sequence of operation. In some designs the isolator switch has the
additional ability to earth the isolated circuit thereby providing additional
safety. Such an arrangement would apply to circuits which inter-connect
power distribution systems where both end of the circuit need to be isolated.
MCB (Miniature Circuit Breaker)- rated current not more than 100 A.
Trip characteristics normally not adjustable. Thermal or thermalmagnetic operation. Breakers illustrated above are in this category.
SF6 circuit breakers extinguish the arc in a chamber filled with sulfur
hexafluoride gas.
Bulk oil
Minimum oil
Air blast
Vacuum
SF6
This technique has proved to be very efficient and has been widely applied
for high voltage circuit breakers up to 550 kV. It has allowed the
development of new ranges of circuit breakers operated by low energy
spring-operated mechanisms.
The reduction of operating energy was mainly achieved by the lowering
energy used for gas compression and by making increased use of arc energy
to produce the pressure necessary to quench the arc and obtain current
interruption. Low current interruption, up to about 30% of rated short-circuit
current, is obtained by a puffer blast.
Self-blast chambers
Further development in the thermal blast technique was made by the
introduction of a valve between the expansion and compression volumes.
When interrupting low currents the valve opens under the effect of the
overpressure generated in the compression volume. The blow-out of the arc
is made as in a puffer circuit breaker thanks to the compression of the gas
obtained by the piston action. In the case of high currents interruption, the
arc energy produces a high overpressure in the expansion volume, which
leads to the closure of the valve and thus isolating the expansion volume
from the compression volume. The overpressure necessary for breaking is
obtained by the optimal use of the thermal effect and of the nozzle clogging
effect produced whenever the cross-section of the arc significantly reduces
the exhaust of gas in the nozzle. In order to avoid excessive energy
consumption by gas compression, a valve is fitted on the piston in order to
limit the overpressure in the compression to a value necessary for the
interruption of low short circuit currents.
Self-blast circuit breaker chamber (1) closed, (2) interrupting low current, (3)
interrupting high current, and (4) open.
This technique, known as self-blast has now been used extensively since
1980 for the development of many types of interrupting chambers. The
increased understanding of arc interruption obtained by digital simulations
and validation through breaking tests, contribute to a higher reliability of
these self-blast circuit breakers. In addition the reduction in operating
energy, allowed by the self blast technique, leads to longer service life.
An important decrease in operating energy can also be obtained by reducing
the kinetic energy consumed during the tripping operation. One way is to
displace the two arcing contacts in opposite directions so that the arc speed
is half that of a conventional layout with a single mobile contact.
The thermal and self blast principles have enabled the use of low energy
spring mechanisms for the operation of high voltage circuit breakers. They
progressively replaced the puffer technique in the 1980s; first in 72.5 kV
breakers, and then from 145 kV to 800 kV.
The double motion technique halves the tripping speed of the moving part.
In principle, the kinetic energy could be quartered if the total moving mass
was not increased. However, as the total moving mass is increased, the
practical reduction in kinetic energy is closer to 60%.The total tripping
energy also includes the compression energy, which is almost the same for
both techniques. Thus, the reduction of the total tripping energy is lower,
about 30%, although the exact value depends on the application and the
operating mechanism. Depending on the specific case, either the double
motion or the single motion technique can be cheaper. Other considerations,
such as rationalization of the circuit-breaker range, can also influence the
cost.
In this interruption principle arc energy is used, on the one hand to generate
the blast by thermal expansion and, on the other hand, to accelerate the
moving part of the circuit breaker when interrupting high currents. The
overpressure produced by the arc energy downstream of the interruption
zone is applied on an auxiliary piston linked with the moving part. The
resulting force accelerates the moving part, thus increasing the energy
available for tripping.
With this interrupting principle it is possible, during high-current
interruptions, to increase by about 30% the tripping energy delivered by the
operating mechanism and to maintain the opening speed independently of
the current. It is obviously better suited to circuit-breakers with high
breaking currents such as Generator circuit-breakers.
Circuit Breaker Contact Resistance Measurement Test
Stationary and moving contacts are built from alloys that are formulated to
endure the abuse of electrical arcing. However, if contacts are not
maintained on a regular basis, their electrical resistance due to
repeated arcing builds up. This resistance build-up results in a
significant decrease in the contacts ability to carry current. Excessive
corrosion of contacts is detrimental to the breaker performance. One
way to check contacts is to apply dc current and measure the contact
resistance or voltage drop across the closed contacts. The breaker
contact resistance should be measured from bushing terminal to
bushing terminal with the breaker in the closed position. It is
recommended that for medium and high voltages the resistance test be
made with 100-Amps (or higher) direct current. The use of a higher
current value gives more reliable results than using lower current
Live tank
This type of tank is mounted on towers along the transmission line.
High level current passes through them so that direct contact cannot
be made.
Dead tank
This type of tank is situated on the ground. Wires are brought from the
transmission lines to the ground. It is properly earthed so that it can be
touched directly. However this leads to power loss and increase in
amount of core material.
TECHNICAL DETAILS:
1
.
Class of Accuracy
0.5
2
.
Rated Burden
5.00 VA
3
.
4
.
3KV
433 V
5
.
400 V
6
.
Frequency
50 Hz
7
.
Supply System
Ratio
50/5
150/5
300/5
400/5
1000/5
0.5
displacement
in
at % of rated
20
100
120
20
100
120
1.5
0.7
5
0.5
0.5
90
45
30
30
Burden
Rating factor
Load
Temperature and
Physical configuration.
For the IEC standard, accuracy classes for various types of measurement are
set out in IEC 60044-1, Classes 0.1, 0.2s, 0.2, 0.5, 0.5s, 1, and 3. The class
designation is an approximate measure of the CT's accuracy. The ratio
(primary to secondary current) error of a Class 1 CT is 1% at rated current;
the ratio error of a Class 0.5 CT is 0.5% or less. Errors in phase are also
important especially in power measuring circuits and each class has an
allowable maximum phase error for specified load impedance. Current
transformers used for protective relaying also have accuracy requirements at
overload currents in excess of the normal rating to ensure accurate
performance of relays during system faults.
The
load,
or
burden,
in
a
CT
metering circuit is
the
(largely resistive) impedance presented to its secondary winding. Typical
burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA, 10 VA, 15 VA, 20 VA, 30
VA, 45 VA & 60 VA. As for ANSI/IEEE burden ratings are B-0.1, B-0.2, B-0.5, B1.0, B-2.0 and B-4.0. This means a CT with a burden rating of B-0.2 can
tolerate up to 0.2 of impedance in the metering circuit before its output
current is no longer a fixed ratio to the primary current. Items that contribute
to the burden of a current measurement circuit are switch-blocks, meters
insulation has deteriorated due to the entry of dirt and moisture. The current
which flows through the insulation will also have a resistive component.
This will cause the angle of the current to be less than 90 degrees. This
difference in the angle is known as the loss angle. The tangent of the
angle which is Ir/Ic (opposite/adjacent) gives us an indication of the
condition of the insulation. A higher value for the loss angle indicates a high
degree of contamination of the insulation.
The cable or winding whose insulation is to be tested is first disconnected
and isolated. The test voltage is applied from the Very Low Frequency
power source and the Tan delta controller takes the measurements. The
test voltage is increased in steps up to the rated voltage of the cable. The
readings are plotted in a graph against the applied voltage and the trend is
studied. A healthy insulation would produce a straight line.
The test should be continued only if the graph is a straight line. A rising trend
would indicate weak insulation which may fail if the test voltage is increased
beyond the rated voltage of the cable.
There are not standard formulae or benchmarks to ascertain the success of a
tan delta test. The health of the insulation which is measured is obtained
by observing the nature of the trend which is plotted. A steady, straight
trend would indicate a healthy insulation, while a rising trend would indicate
an insulation that has been contaminated with water and other impurities.
4.6 Wavetrap
Wavetrap traps the high frequency communication signals sent on the line
from the remote substation and diverting them to the telecom/teleprotection
panel in the substation control room (through coupling capacitor and
LMU). This is relevant in Power Line Carrier Communication (PLCC) systems
for communication among various substations without dependence on the
telecom company network. The signals are primarily teleprotection signals
and in addition, voice and data communication signals. Line trap also is
known as Wave trap. What it does is trapping the high frequency
communication signals sent on the line from the remote substation and
diverting them to the telecom/teleprotection panel in the substation control
room (through coupling capacitor and LMU). The Line trap offers high
&
Capacitive
Voltage
voltage
transformer (CVT),
or capacitance
coupled
voltage
Voltage transformers
Voltage transformers (VT) or potential transformers (PT) are another type of
instrument transformer, used for metering and protection in high-voltage
circuits. They are designed to present negligible load to the supply being
measured and to have a precise voltage ratio to accurately step down high
voltages so that metering and protective relay equipment can be operated at
a lower potential. Typically the secondary of a voltage transformer is rated
for 69 V or 120 V at rated primary voltage, to match the input ratings of
protective relays.
The transformer winding high-voltage connection points are typically labeled
as H1, H2 (sometimes H0 if it is internally grounded) and X1, X2 and
sometimes an X3 tap may be present. Sometimes a second isolated winding
(Y1, Y2, Y3) may also be available on the same voltage transformer. The high
side (primary) may be connected phase to ground or phase to phase. The
low side (secondary) is usually phase to ground.
The terminal identifications (H1, X1, Y1, etc.) are often referred to as polarity.
This applies to current transformers as well. At any instant terminals with the
same suffix numeral have the same polarity and phase. Correct identification
of terminals and wiring is essential for proper operation of metering and
protective relays.
Some meters operate directly on the secondary service voltages at or below
600 V. VTs are typically used for higher voltages (for example, 765 kV
designed for such large values. CVT's offer the advantage that the voltage
divider capacitor, being itself relatively smaller and lighter, configuration
makes the transformer's iron core much smaller in size, and hence more
economical, versus what it would be if a pure magnetic transformer would be
used. Also the CVT's can be tuned to the fundamental frequency of the line,
and the capacitance prevents the inductive "fire-back" of the coils in the
transformer when a breaker trips. PT's can't provide such advantage. Some
CVT's are also used to tune to PLCC, Programmable Logic Controller Carrier
frequency, which is a signal transmitted over power lines providing interPLCC communication.
Power line carrier communication
Power
line
carrier
communication (PLCC)
is
mainly
used
for telecommunication,
tele-protection
and
tele-monitoring
between electrical substations through power lines at high voltages, such as
110 kV, 220 kV, 400 kV. PLCC integrates the transmission of communication
signal and 50/60 Hz power signal through the same electric power cable. The
major benefit is the union of two important applications in a single system.
In a PLCC system the communication is established through the power line.
The audio frequency is carried by a carrier frequency and the range of carrier
frequency is from 50 kHz to 500 kHz. The modulation generally used in these
systems is amplitude modulation. The carrier frequency range is allocated to
include the audio signal, protection and the pilot frequency. The pilot
frequency is a signal in the audio range that is transmitted continuously for
failure detection.
The voice signal is converted/compressed into the 300 Hz to 4000 Hz range,
and this audio frequency is mixed with the carrier frequency. The carrier
frequency is again filtered, amplified and transmitted. The transmission of
these HF carrier frequencies will be in the range of 0 to +32db. This range is
set according to the distance between substations.
PLCC can be used for interconnecting PBXs. The electricity boards in India
have an internal network PLCC between PBXs.
Wavetrap is connected in series with the power (transmission) line. It blocks
the high frequency carrier waves (24 KHz to 500 KHz) and let power waves
4.8 Busbar
In electrical
power
distribution,
a busbar is
a
strip
of copper or aluminium that
conducts electricity within
a switchboard, distribution board, substation or other electrical apparatus.
The size of the busbar determines the maximum amount of current that can
be safely carried. Busbars can have a cross-sectional area of as little as
10 mm but electrical substations may use metal tubes of 50 mm in diameter
(1,963 mm) or more as busbars, and an aluminium smelter will have very
large busbars used to carry tens of thousands of amperes to
the electrochemical cells that produce aluminum from molten salts.
Busbars are typically either flat strips or hollow tubes as these shapes
allow heat to dissipate more efficiently due to their high surface
area to cross-sectional area
ratio.
The skin
effect makes 5060
continuous, uninterrupted alternating current (AC) power for the facility. The
batteries may provide power for minutes, hours or days depending on the
electrical system design, although most commonly the batteries power the
UPS during brief electric utility outages lasting only seconds.
Battery rooms are also found in electric power plants and substations where
reliable power is required for operation of switchgear, critical standby
systems, and possibly black start of the station. Often batteries for large
switchgear line-ups are 125 V or 250 V nominal systems, and feature
redundant battery chargers with independent power sources. Separate
battery rooms may be provided to protect against loss of the station due to a
fire in a battery bank. For stations that are capable of black start, power from
the battery system may be required for many purposes including switchgear
operations.
The world's largest battery is in Fairbanks, Alaska, composed of NiCd cells. Sodium-Sulphor batteries are being used to store wind power.