AUC068 Weekly Valve Check List 43H

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 1

Weekly Inspection Checklist

Facility

Location

Cambooya Pty Ltd

43 - 45 Herbert St,
Artarmon NSW

AUC068.00-01

Date

4/1/2016

VALVE CHECKS
Instructions to Inspector
- Fill out this form while making the inspection. Record the condition of the valve as found and tick the appropriate box.
- Physical inspection: (1) open valve fully (2) close three turns (3) return to fully open position (4) back off turn.
- The report should be held for review by the next FM Global Engineer.
Frequency Key

No.

Weekly visual
Monthly physical

All valves
GV

BV

Gate valves and non-indicating valves (ISY)

Annual physical

OSY

IBV

Outside screw & yoke and indicating butterfly valves

Valve Location

Type

Size

Area Controlled

Herbert St

GV

100

Public supply to site


(street valve)

Herbert St

GV

100

Public supply (booster conn.)

Pump House

GV

80

Hydrant pump suction side

Pump House

GV

80

Hydrant pump discharge side

Pump House

GV

100

Sprinkler pump suction side

Pump House

GV

100

Sprinkler pump discharge side

Pump House

GV

100

Sprinkler alarm valve

Pump House

GV

80

Pump House

GV

80

Fully open

Fully closed

Locked

Street valve is
not closed

Must be open

Need to be
checked by fire
contractor

Must be open

Sprinkler pump annubar line

Must be closed

Sprinkler pump annubar line

Must be closed

Green light on

No red lights

Fuel level

Acceptable?

> 85%

FIRE PUMP CONTROL PANELS


Electric hydrant fire pump
Diesel sprinkler fire pump

Must be open
Must be open
Must be open
Must be open
Must be open

The control panels should only show a green light, unless management informed of a system impairment.
FUEL TANK
Diesel sprinkler fire pump
The fuel tank should remain full, or very close to it. If they are not, please alert fire contractors.
COMMENTS
All okay

Inspectors name

Jason Knevett

Signed