DYNAMIC FIRE CONTROL SYSTEM

FUMES PRESSURE SWITCH


FUCTIONING:
- Pression Functioning => Use tube P1 connected after the Extractor Fan and use the N.C. contact 1&2.
- Depression Functioning => Use tube P2 connected before the Extractor Fan and use the N.O. contact 1&3.
MOUNTING:
- The Fumes Pressure Switch can be mounted in diverse ways although its a VERTICAL model.
1) The normal way of mounting is vertically like you can see in the photo below.
In this case, the contact of the fumes pressure switch will change when the pressure will be higher than
the pressure written on the component: for example, 30Pa.

VERTICAL
==> 30Pa.

2) The other way of mounting the Fumes Pressure switch can be HORIZONTAL.
* With the connectors UP like you can see in the Photo below.
In this case, the contact of the fumes pressure switch will change when the pressure will be higher than the
pressure written on the component PLUS 10Pa.=> A 30Pa. Fumes Pressure Switch will become a 40 Pa.
HORIZONTAL with
Connectors UP => 40Pa.

* With the connectors DOWN like you can see in the Photo below.
In this case, the contact of the fumes pressure switch will change when the pressure will be higher than the
pressure written on the component MINUS 10Pa.=> A 30Pa. Fumes Pressure Switch will become a 20 Pa.

HORIZONTAL with
Connectors DOWN => 20Pa.

CEZA Electronic Systems Florence - Italy Tel. +39 (0) 55 8369084 www.ceza.it