Vaishli Holkar
Ashutosh Choubey
Abstract: After some damaging blackouts, voltage stability & collapse happening all over the world & across our
nation has become a concern problem [1]. The major issue in these problem is the collapse of transmission system
which is most suffered by the frequent variations load. In this paper, we focus on the reactive power of most
majoring issue in IEEE 14 bus system. For doing the above said we are using PSAT (Power System analysis
toolbox) a MATLAB Based Simulink & Simulation toolbox which utilizes Newton-Raphson method for voltage
stability analysis and reactive power controlling [1]. In this work, firstly we have analyzed IEEE-14 bus system
under the standard test data & after that analysed IEEE-14 bus system with Static-Var-Compensation under the
standard test data. After that, we have increased load data by 5%,10%,15%,20%, 25%,30%,35%,45% and so on
then we have compared all the result with the original power flow results of IEEE-14 bus system for improving a
Reactive power.
1. INTRODUCTION
In load flow, Reactive powe is the power taken by
the reactance of the circuit. This power is not
actually consumed but it flow forth and back
between source and load. Its unit is Volt-Ampreactive (VAr). Reactive power is the one which
is mostly suffered by the changes in load
demands.
In this paper, we are looking to improving the
voltage profile by controlling the reactive power
using FACTS devices in IEEE-14 bus system.
Initially, we have analysed IEEE-14 bus system
under the standard test data & after that analysed
IEEE-14 bus system with Static Var
Compensation (SVC) under the standard test data.
After that, we have increased load data by 5%,
IJRSSET
Enhancement of voltage profile for IEEE-14 Bus System by Using STATIC-VAR Compensation (SVC) when
Subjected to Various Changes in Load
2. PROBLEM DOMAIN
Voltage stability is a main issue in planning and
operating power system and is factor leading to
limit power transfer. Voltage stability is
concerned with the ability of a power system to
maintain acceptable voltages at all buses in the
system under normal condition and after being
subjected to a disturbance. A power system is set
to have entered a state of voltage instability when
a disturbance results in a progressive and
uncontrollable decline in voltage.
Inadequate reactive power support from generator
and transmission line leads to voltage instability
or voltage collapse, which has resulted in several
major system failures in the world. They are
South Florida, USA, system disturbance of 17
May 1985, (transient, 4 sec). NREB grid
disturbance in India in 1984 and 1987.
2.1 Reactive power and voltage collapse
Voltage collapse typically occurs in power system
which is usually heavily loaded, faulted and/or has
reactive power storage. Voltage collapse in a
system in stability and in involve many power
Control
2.
3.
4.
5.
6.
7.
8.
9.
3. SOLUTION DOMAIN
In this paper, voltage stability is improving by
controlling the reactive power or using FACTS
devices. In FACTS devices, Static-Var
compensation (SVC) is used for improving
voltage stability by connecting Static-Var
compensation (SVC) at a weakest nodes.
SVC is an electrical device for providing fastacting reactive power on high voltage electricity
transmission networks. An SVC is based on
thyristor controlled reactors (TCR), thyristor
switched capacitors (TSC), and/or Fixed
Capacitors (FC) tuned to Filters. A TCR consists
Enhancement of voltage profile for IEEE-14 Bus System by Using STATIC-VAR Compensation (SVC) when
Subjected to Various Changes in Load
GENERATION
Bus
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
REAL
(MW)
232.4
40.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
REACTIVE
(MVAR)
-16.9
42.4
23.4
0.0
0.0
12.2
0.0
17.4
0.0
0.0
0.0
0.0
0.0
0.0
LOAD
REAL
(MW)
0.0
21.7
94.2
47.8
7.6
11.2
0.0
0.0
29.5
9.0
3.5
6.1
13.5
14.9
REACTIVE
(MVAR)
0.0
12.7
19.0
3.9
1.6
7.5
0.0
0.0
16.6
5.8
1.8
1.6
5.8
5.0
Bus No.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
1-2
2-3
2-4
1-5
2-5
3-4
4-5
5-6
4-7
7-7
4-9
7-9
9-10
6-11
6-12
6-13
9-14
10-11
12-13
13-14
R (p.u.)
X (p.u.)
0.01938
0.04699
0.05811
0.05403
0.05695
0.06701
0.01335
0.0
0.0
0.0
0.0
0.0
0.03181
0.09498
0.12291
0.06615
0.12711
0.08205
0.22092
0.01709
0.05917
0.19797
0.17632
0.22304
0.17388
0.17103
0.04211
0.25202
0.20912
0.17615
0.55618
0.11001
0.08450
0.19890
0.25581
0.13027
0.27038
0.19207
0.19988
0.34802
Half line
charging
susceptance
(p.u.)
0.02640
0.02190
0.01870
0.02460
0.01700
0.01730
0.0064
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Voltage
(p.u.)
Phase
(rad)
P.Gen
(p.u.)
Q.Gen
(p.u.)
P.load
(p.u.)
Q.load
(p.u.)
1.06
1.0279
0.0812
1.045
-0.0359
0.4
0.1986
0.217
0.127
1.01
-0.1047
0.4
0.0613
0.942
0.19
1.0232
-0.0795
0.478
0.039
1.0273
-0.065
0.076
0.016
1.07
-0.0846
0.4
0.1255
0.112
0.075
1.0532
-0.069
1.09
-0.0076
0.4
0.2399
1.0359
-0.1038
0.295
0.166
10
1.0342
-0.1053
0.09
0.058
11
1.0482
-0.0971
0.035
0.018
12
1.0538
-0.1002
0.061
0.016
13
1.0473
-0.1018
0.135
0.058
14
1.0226
-0.1208
0.149
0.05
Bus No.
Voltage
magnitude
(p.u.)
Minimum
MVAR
Maximum
MVAR
1.045
-40
50
3
6
8
1.01
1.07
1.09
0
-6
-6
40
24
24
Bu
s
No.
Voltag
e
(p.u.)
Phase
(rad)
P.Ge
n
(p.u.)
Q.Gen
(p.u.)
P.loa
d
(p.u.)
Q.load
(p.u.)
1.06
1.028
0.0710
4
1.045
0.4
0.1649
8
0.217
0.127
1.01
0.4
0.0407
5
0.942
0.19
1.0266
0.478
0.039
1.0296
0.076
0.016
0.4
0.0377
5
0.112
0.075
0.4
0.1703
1
0.295
0.0467
4
B/W Buses
Tap-Setting
4-7
0.978
4-9
0.969
5-6
0.932
0.0358
6
0.1045
5
0.0806
6
-0.0654
0.0818
6
0.0719
9
0.0112
2
0.1065
4
1.07
1.0644
1.09
1.0581
10
1.0527
-0.1072
0.09
0.058
11
1.0576
0.0969
4
0.035
0.018
12
1.0555
-0.0976
0.061
0.016
13
1.0506
0.0999
2
0.135
0.058
14
1.0368
-0.1211
0.149
0.05
Enhancement of voltage profile for IEEE-14 Bus System by Using STATIC-VAR Compensation (SVC) when
Subjected to Various Changes in Load
Table-7. 14 bus integrated system results without SVC for varied reactive load
Original
Power Flow
Result
SET1(5%
CHANGE)
SET2(10%
CHANGE)
SET3(15%
CHANGE)
SET4(20%
CHANGE)
SET5(25%
CHANGE)
SET6(30%
CHANGE)
SET7(35%
CHANGE)
SET8(40%
CHANGE)
AVERAGE
DIFFERENC
E
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
V11
V12
V13
V14
1.0
6
1.04
5
1.0
1
1.023
2
1.027
2
1.0
7
1.053
2
1.0
9
1.035
9
1.034
2
1.048
2
1.053
8
1.047
3
1.02
26
1.0
6
1.0
6
1.0
6
1.0
6
1.0
6
1.0
6
1.0
6
1.0
6
1.0
6
0
1.04
5
1.04
5
1.04
5
1.04
5
1.04
5
1.04
5
1.04
5
1.04
5
1.04
5
0
1.0
1
1.0
1
1.0
1
1.0
1
1.0
1
1.0
1
1.0
1
1.0
1
1.0
1
0
1.022
8
1.022
5
1.022
2
1.021
9
1.021
6
1.021
2
1.020
9
1.020
6
1.021
2
0.002
0
1.027
1
1.026
9
1.026
7
1.026
4
1.026
2
1.026
1.0
7
1.0
7
1.0
7
1.0
7
1.0
7
1.0
7
1.0
7
1.0
7
1.0
7
0
1.052
5
1.051
7
1.050
9
1.050
2
1.049
4
1.048
7
1.047
9
1.047
1
1.050
2
0.003
0
1.0
9
1.0
9
1.0
9
1.0
9
1.0
9
1.0
9
1.0
9
1.0
9
1.0
9
0
1.034
4
1.033
1.032
8
1.031
4
1.029
9
1.028
5
1.027
1.047
4
1.046
6
1.045
7
1.044
9
1.044
1
1.043
3
1.042
5
1.041
6
1.044
9
0.003
3
1.053
4
1.053
1.046
7
1.046
1
1.045
5
1.044
9
1.044
3
1.043
8
1.043
2
1.042
6
1.045
1.021
1
1.01
97
1.01
82
1.01
67
1.01
52
1.01
37
1.01
22
1.01
07
1.01
67
0.00
59
1.025
7
1.025
5
1.026
4
0.000
8
1.031
5
1.030
1
1.028
6
1.027
1
1.025
6
1.024
2
1.03
0.005
9
1.025
6
1.024
1
1.022
7
1.028
5
0.005
7
1.052
6
1.052
2
1.051
7
1.051
3
1.050
9
1.050
5
1.052
2
0.001
6
0.002
8
4. CONCLUSION
From table 7 it is clear that the voltage profile is
weak at bus 9 & bus 14 when subjected to
percentage changes in load which may result in
voltage collapse. Hence a special protection
scheme can be applied on these buses to prevent
voltage collapse.
REFERENCES
[1] Jia Hongjie, Yu Xiaodan, Yu Yixin 2005 An
Improved Voltage Stability Index & its
Application Elsevier Ltd.
[2] Claudia Reis, Antonio Andrade, and F. P.
Maciel Barbosa, Methods for Preventing
Voltage Collapse,
[3] D. Murali, Dr. M. Rajaram 2010, Active and
Reactive Power Flow Control using FACTS
Devices, International Journal of Computer
Applications (0975 8887)Volume 9 No.8.
[4] S. Tara Kalyani and G. Tulsiram Das, 2008,
Simulation of Real and Reactive Power
Flow Control with UPFC Connected to a
Transmission Line, Journal of Theoritical
and Applied Information Technology, 4(1),
pp.16-22.
[5] Bindeshwar Singh, N. K. Sharma, A. N.
Tiwari, K. S. Verma, and Deependra Singh
Enhancement of Voltage Stability by
Coordinated Control of Multiple FACTS
Controllers in Multi- Machine Power System
Environments
[6] http://en.wikipedia.org/wiki/2012_India_blac
ko uts
[7] http://www.telegraph.co.uk/.../india/.../World
sbiggest- ever-blackout-as-India-is-broughtto-astandstill.htmlJ
[8] http://www.nytimes.com/2012/08/01/world/a
sia/power-outages-hit-600-million-inindia.html?pagewanted= all&_r=0
[9] http://www.pserc.wisc.edu/documents/.../Indi
a_July_31_Blackout_Event.pdf
[10] http://phys.org/pdf262863279.pdf