Notes:: DB-950133 001 00 P M88

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

M88

NOTES:

PLANT NO.

1. TINNED BRAID APPLIED BUTT EDGE ON


CYLINDRICAL PORTION OF CONDUCTOR
AND HALF LAPPED ON TAPERED PORTION.

DB-950133 001 00

INDEX

DRAWING NUMBER

SHT. NO.

REV. NO.

1 1/2 "

1 1/2 "

1 1/2 "

1 1/2 "

2. CAUTION: USE THE SPECIAL RUBBER CEMENT


UNDER THE FIRST LAYER ONLY OF NOZONE
AND NEOPRENE TAPES. DO NOT USE THE
CEMENT BETWEEN THE SUCCESSIVE LAYERS
OF EITHER TAPE. ALSO BE SURE THE
CEMENT HAS BECOME TACKY BEFORE
APPLYING TAPES.

A
B
D

C
P

3. CAUTION: UNDERLYING SEMI-CONDUCTING


TAPE MUST BE REMOVED TO END OF
FACTORY APPLIED SHIELDING.

E
H

10

SEE
NOTE 1

4. REFER TO SAES-P-124.01 FOR INSTRUCTIONS


ON MAKING THE JOINT.

10

SEE
NOTE 2

SEE
NOTE 3

12

AND

AND

AND

13

11

DESCRIPTION OF MATERIAL
ITEM
NO.

JOINT DIMENSIONS
SPLICE KIT
14-900-122 14-900-129
SAMS NO.
G&W
CAT. NO.
CABLE
SIZE
CABLE
SAMS NO.
A
B
C
D
E
F
G

14-900-136

14-900-144

14-900-151

14-900-158

14-900-165

14-900-172

105U2RNH

105UO1RNH

105UO2RNH

105UO4RNH

105U350RNH 105U500RNH

14-900-179

105U8RNH

105U6RNH

105U4RNH

NO. 8 AWG.
SOLID

NO. 6 AWG
CONCENTRIC
CLASS C

NO.4 AWG
NO. 2 AWG NO. 1/0 AWG NO. 2/0 AWG NO. 4/0 AWG 350,000 CM 500,000 CM
CONCENTRIC CONCENTRIC CONCENTRIC CONCENTRIC CONCENTRIC CONCENTRIC CONCENTRIC
CLASS C
CLASS C
CLASS C
CLASS C
CLASS C
CLASS C
CLASS C

15-087-134 15-087-141
4 1/4 "
4"
1 3/4 "
3"
3/4 "
0.201"
43/64 "

4 1/4 "
4"
1 3/4 "
3"
3/4 "
0.251"
23/32 "

15-087-148

15-087-155

15-087-162

15-087-169

15-087-183

15-087-197

4 1/2 "

4 1/2 "

4 1/2 "

4 1/2 "

4 3/4 "

4 3/4 "

4 1/4 "

4 1/4 "

4 1/4 "

4 1/4 "

2"

2"

2"

2"

3"

3"

3"

3"

1"

1"

1"

1"

0.315"
25/32 "

0.395"
55/64 "

0.504"
31/32 "

0.565"
1 1/32 "

15-087-203
5"

4 1/2 "

4 1/2 "

4 3/4 "

2 1/4 "

2 1/4 "

2 1/2 "

3"

3"

3"

1 1/4 "

1 1/4 "

1 1/2 "

0.713"

0.920"

1.102"

1 3/16 "

1 25/64 "

1 9/16 "

0.71"

0.76"

0.82"

0.90"

1.01"

1.07"

1.23"

1.43"

1.60"

0.83"

0.88"

0.94"

1.06"

1.17"

1.23"

1.39"

1.61"

1.78"

9"

9"

9"

9"

9 1/2 "

9 1/2 "

L
P
S

8 1/2 "
3/4 "
1/4 "

8 1/2 "
3/4 "
1/4 "

3/4 "
1/4 "

3/4 "
1/4 "

3/4 "
1/4 "

3/4 "
1/4 "

3/4 "
1/4 "

3/4 "
1/4 "

1/4 "

PURPOSE

SPLIT TINNED COPPER


CONNECTOR

FOR JOINING THE CONDUCTORS

STEARINE CANDLE

FOR SOLDERING FLUX

50/50 BAR SOLDER

FOR APPLYING THE CONNECTOR AND


FOR ATTACHING THE GROUND WIRES

DRY COTTON TAPE

FOR PROTECTING THE INSULATION, FOR


TEMPORARY LASHINGS; AND FOR CLEANING
OFF SURPLUS SOLDER ON THE CONNECTORS

SANDPAPER

FOR DRESSING THE PENCILS AND FOR


ROUGHENING SURFACES

WOODEN SPATULA

FOR APPLYING THE SPECIAL RUBBER CEMENT

SPECIAL RUBBER CEMENT

FOR USE WITH NOZONE AND NEOPRENE


TAPES (SEE NOTE 2)

7
8

3/4 " WIDE NOZONE TAPE

5/8 " TINNED TINSEL COPPER


FOR SHIELDING THE JOINT
SHIELDING BRAID
(SEE NOTE 1)

10

TINNED FLEXIBLE GROUND


WIRE

FOR GROUNDING THE HAND APPLIED


SHIELDING BRAID

11

FOR USE IN FORMING A JACKET


3/4 " WIDE NEOPRENE TAPE
(APPLY HALF LAPPED)

12

FOR OVERALL JOINT PROTECTION


3/4 " WIDE ANHYDROUS TAPE
(APPLY TWO HALF-LAPPED LAYERS)

13

P & B PAINT

FORMERLY STD. DWG. AB-036860 SHT. 001 REV. 01

FOR INSULATING EACH CONDUCTOR


(APPLY HALF LAPPED)

10"
3/4 "

MATERIAL

FOR PAINTING OVER THE ANHYDROUS TAPE

REV.
DATE
NO.

BY JO/EWO

SAUDI
DRAWN BY

MHJ

DESCRIPTION

ARABIAN

OIL COMPANY

CHECKED BY
09-19-2001

DATE STARTED

CHKD. CERT. APPD.

SCALE

NONE

DATE COMPLETED

OPRG. DEPT.

ENG. DEPT.

APPD FOR CONSTR.


THIS DRAWING IS NOT TO BE USED FOR

CERTIFIED

CONSTRUCTION OR FOR ORDERING


MATERIAL UNTIL CERTIFIED AND DATED

BY

DATE

STRAIGHT TWO WAY JOINTS FOR


1/C RUBBER INSULATED, SHIELDED,
NEOPRENE JACKETED CABLE, 5KV, UNGROUNDED
SAUDI ARABIA

LIB. DWG
PLANT NO.

M88

INDEX

DRAWING NUMBER

SHT. NO.

REV. NO.

DB-950133 001

00

Saudi Aramco 2634 ENG. (3/91)