Trafo Sizing - LV Transformer
Trafo Sizing - LV Transformer
60
Feeder Description
Butterfly damper
261.1
Load/ Demand
Factor
E
Standby Qty
Actual Power
(KVA)
H
0.95
323.34
Total KVA Required
Considering 110 margin
Net KVA Rating of Transformer
Total Power
(KVA)
I = CXH
323.34
323
356
800
KVA
Voltage Drop & Over Load Calculation for Starting Highest Rating Motor
Part A % Volatge Drop Calculation
Net Demand KVA on the transformer =
Net Demand KVA of Motor i.e. Motor Rating [(KWx Load Factor) / ( P.F.x Efficiency)]=
Total Base load (Running Load) =
323
323
0
INPUT DATA
Rating of Transformer in MVA
Transformer Primary Voltage ( KV)
Transformer Secondary Voltage ( KV)
% Impedance of the Transformer (Including 10% tol.)
Ztrf (p.u.)
MV Bus Voltage ( KV)
Fault kA at Transformer HV Terminals (kA) =
Fault MVA at Transformer HV Terminals =
Base KV
Base MVA
Base Current = Base MVA *1000/ ( 1.732 X Base KV) Amp
Base Impedance = (Base KV)2 / Base MVA
Zsource =Source Impedance = Base MVA / Fault MVA
Zt = Total Impedance = Ztrf + Zsource
0.80
11
0.415
5
0.05
11
3.00
57.16
0.415
0.8
1113.00
0.2153
0.0140
0.06400
MOTOR DATA
Name of the Motor
Motor KW Rating
Terminal Voltage (kV)
Motor Efficiency
Running Power Factor
Starting Current = 6.5 X I full load
Starting Power Factor
Full Load Current(A) = Motor KW / ( 1.732 X kV X pf X eff )
Starting Current(A) = 6.5 X Full load Current
Starting Current in p.u = Starting Current / Base Current ( Ia)
Pump
261.1
0.415
0.95
0.85
6.50
0
449.9
2924.0
2.6272
-31.79
-90
-90
0.0021
-2.6272
0.000
0.7
0.00
0.000
2.627
-45.58
-45.58
-89.96
=
=
0.0000
0.0021
0.0000
-2.6272
R=
X=
0.100
0.070
Ohm/ KM)
Ohm/ KM)
R=
X=
0.128
0.071
Ohm/ KM)
Ohm/ KM)
90
3
3.33333333E-005
2.34666667E-005
20
0.001
35.15
0.004
35.15
2
0.000064
0.00003525
50
Ifull load
0.004
0.017
28.85
28.85
0.16813
0.04
0.1681
0.0001
0.0099
-54.85
0.0057
-0.0081
0.0446
0.2010
-61.15
-13.54
0.0215
0.1954
-0.0390
-0.0471
0.0834
0.3345
19.40
334.48
-13.54
3.35
%
0.0811
0.3339
-0.0195
0.0195
2.63
-89.96
Voltage Drop & Over Load Calculation for Starting Highest Rating Motor
Part A % Volatge Drop Calculation
Net Demand KVA on the transformer =
323
Net Demand KVA of Motor i.e. Motor Rating [(KWx Load Factor) / ( P.F.x Efficiency)]=
323
0.50
11
0.415
4
0.04
11
3.00
57.16
0.415
0.5
695.62
0.3445
0.0087
0.04875
90
Pump
261.1
0.415
0.95
0.85
4.50
0
449.9
2024.3
2.9101
-31.79
-90
-90
0.0023
-2.9101
0.000
0.7
0.00
0.000
2.910
-45.58
-45.58
-89.96
=
=
0.0000
0.0023
0.0000
-2.9101
R=
X=
0.100
0.070
Ohm/ KM)
Ohm/ KM)
R=
X=
0.160
0.071
Ohm/ KM)
Ohm/ KM)
3
3.33333333E-005
2.34666667E-005
20
0.001
35.15
0.002
35.15
2
0.00008
0.0000355
50
Ifull load
0.004
0.013
23.93
23.93
0.14186
0.04
0.1419
0.0001
0.0069
-54.85
0.0040
-0.0056
0.0370
0.1656
-66.07
-13.74
0.0150
0.1608
-0.0338
-0.0393
0.0687
0.3486
15.99
348.63
-13.74
2.69
%
0.0668
0.3482
-0.0163
0.0163
2.91
-89.96