Professional Documents
Culture Documents
2010 Iet (DPSP)
2010 Iet (DPSP)
Abstract
The protection system design in common MV and LV
distribution networks is determined by a passive paradigm,
i.e. no generation is expected in the network. With distributed
sources, the networks get active and conventional protection
turns out to be unsuitable. In most cases, the issue is
investigated with synchronous generators, while other
generator types like Doubly Fed Induction Generators (DFIG)
or induction generators are also available. The capability of
the generators of DG systems to feed the fault during
disturbances would affect the results considerably. In this
paper, the important issues such as the ones mentioned above
are analyzed with different types of DG generators, and the
results are compared to highlight the impact of different DG
types on the specified issues. This study is useful from the
utilities' point of view, since it is not necessary to attract their
attention to the extreme conditions. Sometimes, the type of
the DG sources is so, that their contribution to the fault level
is negligible and can be ignored, while in some cases the
impact of another type of generator for DG is not negligible.
1 Introduction
Distributed Generation (DG) has been broadly used in recent
years to supply energy. The electric energy production from
DG is progressively taking an important part of the total
amount of the required energy in power systems. The
interconnection of DG brings a great change to the
configuration of the utility distribution network. The overall
problem when integrating DG in existing networks is that
distribution systems are planned as passive networks, carrying
the power unidirectionally from the central generation (HV
level) downstream to the loads at MV/LV level. The
protection system design in common MV and LV distribution
networks is determined by a passive paradigm, i.e. no
generation is expected in the network. With distributed
sources, the networks get active and conventional protection
turns out to be unsuitable. The following points will outline
the most important issues:
I fi
A
(1)
t T DS
B ,M i
C
(
)
1
M
I
i
Pi
I Pi min d I Pi d I pi max
T D S i m in d T D S i d T D S i m ax
(2)
(3)
t j ,i t i t CT I j ,i ....... i , j N
(4)
T D S
I f j ,i
j ,i
j ,i
B ;
1
3 Sample System
The sample system used for the simulation is presented in
Fig. 2. It is composed of two voltage levels 132kV and 33kV.
The distribution system is fed from three 132/33 kV
substations located at buses 1, 12 and 27. Each feeder is
protected by two directional overcurrent relays located at the
feeder ends. There are 39 relays at the distribution level in
this sample system.
(5 )
I Pj
Ifj,i is the fault current passing from the back-up relay j for a
fault in the protected region of relay i.
j ,i
F2
F2
F2
D3 ('t mb
E3 ('t mb
't mb
))2
(6)
't mb
where:
t b t m CTI
(7)
Figure 2: IEEE 30 bus sample system used for simulation.
4 Simulation Results
Three different generator types are considered: synchronous
generator, asynchronous generator and doubly fed induction
generator (DFIG). The synchronous generators are 10 MVA
with 0.9 power factor lagging. Their transient reactance is
0.15 p.u. based on the nominal power of the machines. The
specifications of different generators are tabulated in Table 1.
Four asynchronous generators are considered in each selected
bus for DG installation. The set of four asynchronous
generators are connected to the network by a step-up
transformer with 6.6kV/33kV ratio, 10 MVA size and 5%
leakage transformer. The specifications of asynchronous
generator and DFIGs are the same, in order to easily compare
them.
When the fault is far from the DG units, then this difference is
negligible. For example, when the DG units are installed at
bus 24, for a fault on bus 30, the injected fault currents from
the synchronous, asynchronous and DFIG generators are
213A, 202.9A and 202.2A, respectively, that 135.2%, 129.3%
and 130.6% of nominal currents of the related units, installed
at bus 24.
Fig. 3 shows the CTI for the relays that experience lack of
coordination after installation of DG units at bus 24. As can
be deduced from this figure, the indicated primary and backup relay pairs had acceptable CTI before DG application,
while their CTIs are reduced after that, and in some instances
the CTI becomes negative, which means the back-up relay
operates before the primary relay.
S
(MVA)
10
2.5
2.5
P
(MW)
9
2.25
2.25
Power
Factor
0.9
0.9
0.9
No. of
Units
1
4
4
Load
Current
(A)
Fault
Location
DG Type
Bus10
Bus24
---
Synchronous
170.4
157.5
---
Induction
153.6
156.9
--Bus24
Fault
Current
(A)
Bus30
DG Location
DFIG
153.8
157.1
Synchronous
357.6
878.5
Induction
345.4
689.5
DFIG
356.2
724.9
Synchronous
170.5
213
Induction
175.8
202.9
DFIG
176.3
205.2
Synchronous
1*Unit
Induction
4*Unit
DFIG
4*Unit
Bus10
11610
14100
12600
Bus12
14450
16700
13400
Bus15
1180
1300
1400
Bus16
2010
2300
2400
Bus17
1690
1900
2000
Bus18
1110
1000
1300
Bus19
690
600
800
Bus21
300
320
340
Bus24
570
600
760
Bus27
2330
2520
3240
Bus30
2210
2760
3520
Bus10
10.01
12.16
10.86
Bus12
12.46
14.4
11.55
Bus15
1.02
1.12
1.21
Bus16
1.73
1.98
2.07
Bus17
1.46
1.64
1.72
Bus18
0.96
0.86
1.12
Bus19
0.59
0.52
0.69
Bus21
0.26
0.28
0.29
Bus24
0.49
0.52
0.66
Bus27
2.01
2.17
2.79
Bus30
1.91
2.38
3.03
Induction
DFIG
Bus10
Bus12
Bus15
96.5
---
---
Bus16
64.5
43
64
Bus17
77
46.5
51.5
Bus18
94.5
---
52.5
Bus19
---
---
---
Bus21
---
---
---
Bus24
---
---
---
Bus27
42
27
28.5
Bus30
42
23.5
25
References
[1] Alberto J. Urdaneta, Harold Restrepo, Saul Marquez,
"Coordination Of Directional OverCurrent Relay Timinng Using
Linear Programming" , IEEE Transactions on Power Delivery, Vol.
11, No. 1, January 1996.
[2] Bijoy Chattopadhay, M.S.Sachdev, T.S.Sidhu, "An On-Line
Coordination Algorithm For Adaptive Protection Using Linear
Programming Technique", IEEE Transactions on Power Delivery,
Vol. 11, No. 1, January 1996.
7 Conclusion
In this paper, the coordination of directional overcurrent
relays is analyzed with different types of DG generators. The
results are compared to highlight the impact of different DG
types on this issue. It is shown that the effect of synchronous
generator as DG unit is more pronounced than the other types
of generators like DFIG and asynchronous. It is also shown
that the integrity of relay coordination can be preserved by
using series reactance fault current limiter. The impact of
other types of FCLs is under investigation by the authors.