OIP Transformer Outdoor Bushings

Type COT(C) 125COT (C) 1800


24kV to 550kV
up to 3150A
IEC 60137-2008

Features
Features
If you need any transformer
If you need any transformer
bushing proven in operation
bushing proven in operation
conditions around the world,
conditions around the world,
Trench has it !

Trench has it !

experience in manufacturing
available with porcelain or
of bushings
for more
than
composite
insulator
air
experience
in manufacturing
available
withonporcelain
or
100 years
side
of bushings for more than
composite insulator on air

100 years

capacitive fine graded oilpapercapacitive


insulation fine
with graded
long oilexperience
paper insulation with long

experience

computer optimized
electrical field distribution

computer optimized
electrical field distribution
proven high electrical
withstand against transient
proven
high electrical
or impulse
stresses

side

inclination in service up to
30 from
vertical. in service up to
inclination
For COT(C)
125 vertical.
and
30 from
COT(C) 170 even
For COT(C) 125 and
horizontal operation is
COT(C) 170 even
possible

horizontal operation is
possible
horizontal transport for all
types possible

horizontal transport for all


types
possiblemore
withstand against transient tan and
PD-values
or impulse
stresses
than twice as good as
excellent
long term
stability
requested
IEC PD-values
60137
tan by
and
more
due to extremely low partial
discharge
and power
lossstability
than twice as good as
excellent
long term
factordue to extremely low partial currentrequested
rating can by
easily
IECbe60137
discharge and power loss increased by exchanging
the cable
bolt with
a can easily be
oil immersed
factor part covered by
current
rating
removable
split
conductor
epoxy resin tube providing
increased by exchanging
on existing bushing
high impact resistance
the cable bolt with a
oil immersed part covered by
removable split conductor
epoxy resin tube providing
electrode embedded in
existingour
bushing
high impact resistance
Toon
preserve
the lower epoxy resin part
- avoids external shielding
electrode
embedded
in
- reduces
distance
to ground
thetransformer
lower epoxy
resin part
- lower
costs

environment the free oil


volume in COT-bushings
To preserve our
is minimized

- avoids external shielding


- reduces
distance
porcelain
cemented
into to ground
- lower
transformer
costs
flange
provides
higher

Transformer Bushings Type


COT(C) 125 to COT(C) 1800

mechanical strength than level


II of IEC
porcelain cemented into

flange provides higher


mechanical strength than level
II of IEC

environment the free oil


volume in COT-bushings
is minimized

Certified ISO 9001

Certified ISO 9001

Transformer Bushings Type


COT(C) 125 to COT(C) 1800

Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

Page 2 / 24

Page 2 / 24

40497230_00

40497230_00
40497230_04

Design
Design

10
10

Cut view
Cut view
General
design
General design
1
1
2

1 1 Top
terminal
Top terminal

6 6 Active
part
Active part

Terminal
(Aluminium
or or
Copper)
Terminal
(Aluminium
Copper)
forfor
connection
of
overhead
lines
connection of overhead
lines
or or
bus
bars
and
arcing
horns.
bus bars and arcing horns.
Trench
design
provides
aa
Trench
design
provides
maintenance
free
termination
and
maintenance free termination
and
ensures
that
thethe
connection
willwill
ensures
that
connection
become
loose
service.
notnot
become
loose
in in
service.

The
active
part
is is
made
ofofoilThe
active
part
made
oilimpregnated
wide
band
paper
impregnated wide band
paper
with
layers
ofof
aluminium
foil
with
layers
aluminium
foiltoto
control
the
electrical
field
radially
control
the
electrical
field
radially
and
axially.
Depending
on
the
and axially. Depending on the
current
rating,
the
paper
and
current
rating,
the
paper
andfoil
foil
are
wound
either
centraltube
tube
are
wound
onon
either
aa
central
solid
conductor
oror
solid
conductor

Assembly
2 2 Assembly
The
whole
bushing
tightened
The
whole
bushing
is is
tightened
together
by
the
central
tube
together by the central tube
or or
conductor.
conductor.
Head
3 3 Head
Al-casted head with oil
Al-casted head with oil
expansion chamber and oil level
expansion chamber and oil level
indicator. The chamber is
indicator. The chamber is
hermetically sealed against
hermetically
sealed against
several environmental conditions.
several environmental conditions.
4
Oil filling
4
Oil filling
COT bushings are filled with
COT
bushings
are insulating
filled with
dried,
degassed
dried,
degassed
insulating
mineral oil.
mineral oil.
5

Insulator

Insulator

Porcelain insulator made of high


grade electrotechnical
Porcelain
insulator madeporcelain
of high
according
to
IEC
60815.
The
grade electrotechnical porcelain
insulatortoisIEC
connected
the
according
60815. to
The
mounting
flange
using
cement
insulator is connected to the
and sealed with O-ring gasket.
mounting flange using cement
instead of porcelain a
and sealed with O-ring gasket.
composite insulator is also
instead of porcelain a
available.

composite insulator is also


available.

Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

44

55

Flange
7 7 Flange
Mounting
flange
with
integrated
Mounting
flange
with
integrated
test
tap
made
corrosion
free
test
tap
made
ofof
corrosion
free
aluminium
alloy,
machined
aluminium alloy, machined toto
ensure an excellent seal between
ensure
an excellent seal between
the bushing and the transformer.
the bushing and the transformer.
8

CT-Pocket
CT-Pocket
If current transformers are
If current
transformers are
required on the bushing, the
required
the bushing,
the
groundon
sleeve
can be extended.
ground sleeve can be extended.
9
Oil side end
9
Oil side end
The insulator on the oil side is
The
insulator
the resin
oil side
is It
made
of an on
epoxy
tube.
made
of an epoxy
resin
tube. It
is designed
to stay
installed
during
the
in-tank
drying
is designed to stay installed
process
the transformer
and
during
the of
in-tank
drying
can
withstand
temperatures
process of the transformer andup
to withstand
130C. temperatures up
can
to 130C.
10 End-shielding

66

10ForEnd-shielding
voltages starting between 52kV

& 300kV a special aluminium


For voltages starting between 52kV
electrode is casted into the end of
& 300kV a special aluminium
the epoxy resin tube. This end
electrode is casted into the end of
shielding controls the electrical field
the epoxy resin tube. This end
strength in this area to ground.
shielding controls the electrical field
strength in this area to ground.

Page 3 / 24

40497230_00

Page 3 / 24

10

10

40497230_00
40497230_04

One of several TRENCH winding machines

Test tap for C and tan

Substitute for E 322.81&E 322.91

Page 4 / 24

measurement

40497230_00
40497230_04

High
Highvoltage
voltagetest
testlaboratory
laboratory

Epoxy
Epoxyinsulator
insulatorwith
withembedded
embeddedend
endshield
shield
Cut
Cutview
view

Insulation
Insulation
See
See
page
page
1616

Cable
Cable

Substitute
Substitute
for
for
EE
322.81&E
322.81&E
322.91
322.91

Page
Page5 5/ 24
/ 24

40497230_00
40497230_00
40497230_04

125

800

cable

/ 1000 800
cable
1
cable )

400
1

cable ) )
12501000
rem.Co-cond.

400

35

) 16001250
fixedrem.Co-cond.
Co-cond.
Co-cond. 25001600
fixedfixed
Co-cond.
COT 170

COT 170

36

36

21

77

21

70

77

170

70

Co-cond. 31502500
fixedfixed
Co-cond.
8003150
cablefixed Co-cond. 400

170

cablecable
)
/ 1000 800
1

35

2 16001250
fixedrem.Co-cond.
Co-cond.
)

25001600
fixedfixed
Co-cond.
Co-cond.

COT 250

52

52

30

105

30

105

95

250

95

31502500
fixedfixed
Co-cond.
Co-cond.

250

COT 325

72,5

72,5

42

155

42

155

140

325

140

325

cable
3150
fixed Co-cond. 400

1250

cable )

800

400

cable

rem.Co-cond.
)
1

1000

COT 325

800

1000

cable )

35

1600

fixed Co-cond.

2500

fixed Co-cond.

3150

fixed Co-cond.

1250

rem.Co-cond. )

1600

fixed Co-cond.

2500

fixed Co-cond.

800

cable

)
16001000
fixedcable
Co-cond.

400

) 25001250
fixedrem.Co-cond.
Co-cond.
Co-cond. 31501600
fixedfixed
Co-cond.
100

58

205

185

450

8002500
cablefixed Co-cond. 400

235

400
35
-

400
35
-

100

58

205

185

450

1
16001000
fixedcable
Co-cond.
)

2 25001250
fixedrem.Co-cond.
Co-cond.
)

31501600
fixedfixed
Co-cond.
Co-cond.

Comments
related to columns 133:
29

04: Bushings test voltage2500


at 50Hz fixed
60 sec.
Co-cond.

301) Class F insulation


09:

09: ) Class F insulation

04: Bushings test voltage at 50Hz 60 sec.


2

) Removable solid rod copper conductor

11: Extension for current transformer (other extensions on request)

Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

Cantilever
test load (min)
Mass
Approx.

Cantilever test load (min)

22

2000

22
2000

2000

28
2000

2000

32

29
2000

2000

36

32
3150

2000

31

28
29

2000
31

2000

2000
38

2000

*1116 *1116
49
*1116 *1116
53

465

1300

465

2000
44
3150
49

26
*1116

2000

600

1820

600

26

2000

26

2000

35

2000

36

2000

54

3150

31

75
2000

4000

44

31
2000

2000

40
3150

2000

44
4000

2000

62
2000

3150

2000
88

4000

2000
40

2000

2000
40

2000

2000

35

2000

36

2000

54

3150

75

4000

31

2000

1300

1820
40

88

820

2540

40
40

820

52
2540
56

400

80

35

106

2000
3150

26

62

2000

53

3150 conductor
fixed Co-cond.Connection
- system see pages 17 to 23
) Removable solid rod copper

11: Extension for current transformer (other extensions on request)

Comments related to columns 133:

2000

*1116 *1116
38
*1116 *1116
44

35

10003150
cablefixed
) Co-cond. 400
2
rem.Co-cond.
)
35 400
/ 1250 800
cable

600
22

2000

COT 450

2000

3150

400

22

2000
31

400

kg

36
2000

*1116

35

mm

*1116 *1116
31
340

340

400

kg

600

235

15

Standard
creepage distance
Mass Approx.

Standard creepage distance

AD Arcing distance (min.)

400

1
3150 fixed
Co-cond. 400
1000 cable )
/ 1250 800
cable 2)
rem.Co-cond.
35 400

COT 450

mm

400 400

12501000
rem.Co-cond.
cable ) )

COT 250

CT
see fig.3
page 12
ADSpace
ArcingL4
distance
(min.)

Cable cross section


Conductor

Connection to Transformer

Connection to Transformer

Switching Impulse wet (SIL): 250/2500s


Rated current (Ir)

Rated current (Ir)


A

14
15

31
2000

25mm/kV

50

125

kV

13
14

25mm/kV

50

kV

mm
mm
mm mm
mm mm mm mm

25mm/kV

55

kV

1213

25 mm
/ kV
25 25mm/
mm kV / kV

14

55

(BIL)
Lightning
Impulse withstand voltage
(BIL)
Switching Impulse wet (SIL): 250/2500s

Transformer Power frequency voltage

24

14

kV

kV

11
12

Standard: 0, 300, 500

COT 125

24

kV

kV

1011

10

Standard: 0, 300, 500

COT 125

withstand (AC)
Transformer
Power frequency voltage
withstand
(AC)
Lightning Impulse withstand voltage

Bushing Dry Power frequency voltage

kV

kV

01
01
02
02
03
03
04
04
05
05
06
06
07
08
07
09
08
10
09
11
10
12
11
13
12
14
13
15
14
16
15
17
16
18
17
19
18
20
19
21
20
22
21
23
22
24
23
25
26
24
27
25
28
26
29
27
30
28

Bushing
Dry
Power frequency voltage
withstand
(AC)
withstand (AC)

Maximum phase to earth voltage

kV

Maximum phase to earth voltage

Highest voltage (Um)

kV

Highest voltage (Um)

Type
Type

NN

kV

09 09

Cable cross section


Conductor
CT Space L4 see fig.3 page 12

Type COT 125450

Type COT 125450


01
01
0202 0303 0404 05 05 06 06 07 07 08 08

3150
52
4000
56

2000

2000
2000

80

3150

106

4000

13: * 31mm/kV in standard

Connection system see pages 17 to 23


13: * 31mm/kV in standard

Page 6 / 24

Page 6 / 24

40497230_00

40497230_00
40497230_04

Type COT 125450

Rated current (Ir)

Rated current (Ir)

Type COT 125450


0808
1616 1717
18
18

A
800

L1

L1

L2

L2

19
19

20
20

21
21

22
22

24
24

25
25

2626

2727 2828 29 29 30 3031 3132 32 33 33

L3

L6

L7

D2

D3

D4

D5

L3

L6

12, 13:
15:

mm

D2

D3

D4

D5

D6

D7
D
min 7 t

min

761

140

621

452

80

According to IEC 137 level II or better

Brown glazed porcelain, other colours and


Other creepage distances upon request
According to IEC 137 level II or better

Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

80 184
80 184
184
80

240
240
240

210
190
30
40
24
4
210 190
190 30 30 40 40 24 24 4
210

60
60

80 184
184
80

240
240

210 190
190 40 30
210

80 184
184
80

60
60

240
240

80 184
184
80
80 184
184
80

60
60
60
60

see
see
fig.

fig.

mm

60
60
60

60
60

mm

mm

140
452
80
800
761
140 621
621
452
80
1000 761
761
140
621
452
80
1000
140
621
80
1250 761
761
140
621
80
1250
729
140
589
125
1600
140
-125
1600
729
140 589
589
125
2500 729
140
-125
2500
729
140 589
589
125
3150 729
729
140
589
125
3150
169
726
557
80
800 895
895
169 726
726
557
80
1000 895
169
557
80
800
895
169 726
726
80
1250 895
169
557
80
1000
863
169 726
694
125
1600 895
169
-80
1250
863
169
694
125
2500
169
694
125
1600 863
863
169 694
694
125
3150 863
169
-125
2500
1090 169
140 694
950
760
80
800 863
125
3150
140
950
760
80
1000 1090
140
950
760
80
800 1090
140
950
80
1250 1090
140
950
760
80
1000 1090
140
995
125
1600 1135
140
950
80
1250 1090
140
955
125
2500 1095
140
995
125
1600 1135
140
965
125
3150 1105
140
955
125
2500 1095
175
1035
845
80
800 1210
140
965
125
3150 1105
175
1035
845
80
1000 1210
1210
175
1035
845
80
800
175
1035
80
1250 1210
845
80
1000
1255 175
175 1035
1080
125
1600 1210
-80
1250
1275 175
175 1035
1100
125
2500 1210
1255
175
1080
125
1600
175
1110
125
3150 1285
125
2500
1503 175
230 1100
1273
1085
80
800 1275
125
3150
1503 175
230 1110
1273
1085
80
1000 1285
1503 230
230 1273
1273
80
1250 1503
1085
80
800
1548 230
230 1273
1318
125
1600 1503
1085
80
1000
1543 230
230 1273
1313
125
2500 1503
-80
1250
1553 230
230 1318
1323
125
3150 1548
-125
1600
230 porcelain,
1313 other colours
2500
12, 13: 1543
Brown glazed
and125
Other
creepage
distances
upon
request
230
1323
125
3150 1553
15:

L7

D6

210 190
190 30 30
210

240 210
210 190
190 40 40
240
240 210
210 190
190 40 40
240

- 40 24 24 4
-

- 24 24 4
- 24 24 4
- 24 24 4

12

19

4 12 1219 19
4 12 1220 19
4 12 1221 20
4 12 1221 21
4 12 1221 21
4 12 1219 21

60

80 184
184
80
80
80 184
184
80
80 184
184

240 230
210 190
190 30 40 40 - 24 24 4
240
240
240 230
230 190
190 30 30 40 40 24 24 4
240
240 230
230 190
190 30 30 - 40 24 24 4

60

80
80 184
184

240
240

230
230 190
190 40 30

- 24 24 4

4 12 1221 20

60
60

80
80 184
184

240
240

100
80 185
184
100 185

225
240
225

- 24 24 4
- 24 24 4

4 12 1221 21

100
60
100

230
230 190
190 40 40
230
190
230
190 40 40

100

100

100

100

185

225

200

170

40

35
16
16
6
35
16

6
14
22
14
23
6
14
22

110

120

200

240

231

170

60

110

130

290

335

242

170

60

100

100

185

225

210

170

30

100
100
100

100 185
100 185
185
100

225
225
225

210
170
30
35
16
6
210
170
30
35
16
210
170
30
16
6

100
110

100 200
185
120

225
240

210 170
170 60 30
231

60

60
60

80
80 184
184

100
100

240
240

100 185
185
100 185

100

100

100

100

110

120

110

130

100
100

225
200
170
30
200
170
30
225
200
170
30
225

185

225

200

240

290

335

100 185
185
100

100
110

200
230 170
190 30 40 35 - 16 24 6
200
170
30
35
16
6

225

185

225
225

100 290
185
130
120 185
200
100

200
200
231
242

170
170
170
170

30
40
60
60

210 170
170 40 30
210

35

16
22
16
16

16
16

6
6

12

22
16

- 35 16 16 6
-

- 22 16 6

4 12 1219 19
4 12 1220 19

4 12 1221 21
4 14 1222 21
14

6
6
6
12

14
15
16
14

22
24

14

23

14

24

15

25

16

26

25
26
22

14
22
6 14 1423 22

6 14 1424 22
6 15 1425 23

130 185
290
100

225 242
210 170
170 60 40 - - 16 1612 6 16 1426 24
335
240 210
231 170
170 30 60 35 - 16 22 6 6 14 1522 25
225
335 210
242 170
170 30 60 35 - 16 16 6 12 14 1622 26
225

100
100

100
100 185
185

225
225

210
210 170
170 30 30

100
100

100
100 185
185

225
225

210
210 170
170 40 30

110
100

120
100 200
185

240
225

231
210 170
170 60 30
242
210 170
170 60 40

110
100
110
100

110
100

130
100 290
185

110
16, 17: 120

335
225

- 35 16 16 6
- 35 16 16 6
- - 22 16 6
-

0mm. If242
L4>0mm170
add L4 to60
L1 and L.110
130 290for L4=335
24, 25, 29, 32:
Other dimensions on request.

24, 25, 29, 32:

6 15 1425 23

- 16 1612 6 16 1426 24

200L1 depends
240 on231
170 in the
60 table are
- valid22
L4. The values

16, 17:

6 14 1423 22
6 14 1424 22

16

15

25

12

16

26

L1 depends on L4. The values in the table are valid


for L4= 0mm. If L4>0mm add L4 to L1 and L.
Other dimensions on request.

Page 7 / 24

Page 7 / 24

40497230_00

40497230_00
40497230_04

COT 650

123

123

145

145

71

kV

71

84

kV

255

230

255

305

84

305

kV

230

275

kV
550

kV

kV
/

550

650

275

kV

A
800

cable

35

31502500
fixed fixed
Co-cond.
Co-cond.-

12
rem.Co-cond.
12501000
cable ))

35

COT 750

170

98

355

98

355

325

750

325

fixed Co-cond.

fixed Co-cond.

3150

fixed
Co-cond.
1

750

1000
1250

cable

400

cable )

500

800

1600

COT 1050

COT 1050

245

245

142

505

142

505

460

1050

460

173

560

510

35

1
10003150
cablefixed
) Co-cond.
500

8002500
cablefixed Co-cond.
400

750
750

1050750 7501250 800


cable )
rem.Co-cond.
2

1050

)
750 75016001000
fixed cable
Co-cond.

300

500

Co-cond.31501600
fixed fixed
Co-cond.

COT 1050

rem.Co-cond. )

fixed Co-cond.

400

35

cable )

fixed Co-cond.

1250

2500

cable

rem.Co-cond.12)

1000

38

400

300

173

560

26
27

510

Standard
creepage distance
Mass Approx.

Cantilever
test load (min.)
Mass
Approx.

Cantilever test load (min.)

AD
Arcing distance (min.)
Standard creepage distance
3625

1460

4250

1460
*5270

2150

62
3150

3150

3150

74

62
3150

3150

79

74
3150

3150

165

79
4000

3150

173

4000
165

4000

81

3150
173

4000

81
3625

3150
81

3150

101

3150
98

98

3150
81
4000

3150

101

3150

190

4000

198

4000

92

4000

92

4000

111

4000

223

117
5000

4000

236

223
4000

5000

236
4000

4000

198

4000

92

4000

92

4000

111

4000

117

4000

315

5000

4250

315
6125 *5270
236 4000
2150

3150

6125
266

5000

285

236
4000

4000

328

266
5000

4000

750 75031501600
fixed fixed
Co-cond.
Co-cond.-

332

5000
285

4000

850 75010002500
Cablefixed Co-cond.
630

350

5000
328

5000

440

5000
332

5000

fixed Cable
Co-cond.
1050850 85025001000

2400

7500

630

2400

445
7500

5000
350

5000

850

1600

fixed Co-cond.

440

5000

850

2500

fixed Co-cond.
2

445

5000

09: 1) Class F insulation

) Removable solid rod copper conductor

Connection system see pages 17 to 23

Comments related to columns 133:

04: Bushings test voltage at 50Hz 60 sec.

3100
62

62

38

11: Extension for current transformer (other extensions on request)


13: * 31mm/kV in standard

1050

3100

kg

500

Comments related to columns 133:


04: Bushings test voltage at 50Hz 60 sec.

kg

2
) 750 75025001250
fixed rem.Co-cond.
Co-cond.

850 75016003150
fixed fixed
Co-cond.
Co-cond.-

COT 1050

15

190

14
15

mm

1250

35

2500

800

1250

400

fixed Co-cond.
1600
fixed Co-cond.-

3150

1050

mm

13
14

mm

400

35

2
) 16001250
fixed rem.Co-cond.
Co-cond.
Co-cond.25001600
fixed fixed
Co-cond.

2500
170

CT
Space
L4distance
see fig.3
page 12
AD
Arcing
(min.)

400

400

16001250
fixed rem.Co-cond.
Co-cond. 2) -

COT 750

Cable cross section


Conductor
CT Space L4 see fig.3 page 12
mm

400

8003150
cablefixed Co-cond.
400
1
cablecable
)
400 400
/ 1000 800

650

12
13

mm
mm mm
mm mm mm

1
/ 1000 800
cablecable
)
1
cable 2))
rem.Co-cond.
12501000

11
12

Cable cross section


Conductor

Connection to Transformer

Rated current (Ir)

Rated current (Ir)

Switching Impulse wet (SIL): 250/2500s

Switching Impulse wet (SIL): 250/2500s

(BIL)
Lightning
Impulse withstand voltage
(BIL)

Transformer Power frequency voltage

withstand (AC)
Transformer
Power frequency voltage
withstand
Lightning(AC)
Impulse withstand voltage

Bushing Dry Power frequency voltage

Bushing
Dry(AC)
Power frequency voltage
withstand
withstand (AC)

Maximum phase to earth voltage

kV

Maximum phase to earth voltage

Highest voltage (Um)

kV

Highest voltage (Um)

kV

1011

10

25mm / kV

COT 650

kV

09

25mm / kV

02
03
03
04
04
05
06
05
07
06
08
07
09
08
10
09
11
10
12
11
13
12
14
13
15
14
16
15
17
16
18
17
19
18
20
19
21
20
22
23
21
24
22
25
23
26
24
27
25

COT 550

kV

09

Standard: 0, 300, 500

01
02

COT 550

0202 0303 0404 05 05 06 06 07 07 08 08

Standard: 0, 300, 500

01

Type
Type

NN

01
01

Connection to Transformer

TypeCOT
COT5501050
5501050
Type

09: 1) Class F insulation

11: Extension for current transformer (other extensions on request)

) Removable solid rod copper conductor

Connection system see pages 17 to 23

13: * 31mm/kV in standard

Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

Page 8 / 24

Page 8 / 24

40497230_00

40497230_00
40497230_04

Type
COT 5501050
Type COT 5501050

Rated current (Ir)

Rated current (Ir)

08 08

800
800
1000
1000
1250
1250
1600
1600
2500
2500
3150

1616

1717

1818

19
19

20
20

21
21

22
22

23
23

24
24

25
25

2626 2727 2828 29 29 30 3031 3132 3233 33

L1

L2

L3

L6

L7

D1

D2

D3

D4

L1

L2

L3

1805
310
1495
1805
1805 310
310 1495
1495

1306
1306
1306

1805
1850 310
310 1495
1540

--

1805
1805 310
310 1495
1495
1850
2089 310
310 1540
1779
2089
2052 310
310 1779
1742

1306
-

L6

L7

mm

D1

mm

D3

D4

D5

D6

D6

D7
minD7 t

min

80
80
80

110
110
110

120
120
120

--

250
290
231
170
30
35
16
8
250 290
290 231
231 170
170 30 30 35 35 16 16 8
250

80
125

110
110

120
120

--

250 290
290 231
231 170
170 40 30 250

80
80

--

125
125

110
110
110
195

120
120
120
175

---

--

125
125

195
195

175
175

--

3150
2055 310
360 1742
1695
800 2052

1506

125
80

195
110

175
130

1000
800
1250
1000
1600
1250
2500
1600
3150
2500
800
3150

2055 360
360 1695
1695
2055
2055
360
1695
2055
360
1695

1506
1506
1506

80
80
80
80

110
110
110
110

130
130

---

130
130

--

2100 360
360 1695
1740
2055

--

125
80

110
110

130
130

--

2302 360
360 1979
1942
2339
2325 360
420 1942
1905
2302
1000 2325 420 1905

--

125
125

195
195

175
175

--

800
1250
1000
1600
1250
2500
1600
3150
2500
800
3150
1000

2325
420
1905
2325
420
1905
2325
420
1905

1000
1600
1250
2500
1600
3150
2500
1000
1600
3150

2339 360
360 1740
1979
2100

D2

D5

--

125
125

1716
1716

80
125
80

195
110
110
195
110

1716
1716

80
80
80

110
110
110

80

110

125

110

125

195

125

195

3518
3563 684
684 2834
2879
3518
3563 684
684 2834
2879

2500
--

3563
3407 684
684 2879
2842
3563
3813 684
684 2879
3129

175
130
130
175
130

130
130

---

250 290
290 231
231 170
170 30 30 - 35 16 16 8
250
250 290
290 295
231 300
170 60 40 290
290 450
290 295
295 300
300 60 60 400

mm

fig.

mm

15
27
8 15 15 27 27

8 15 15 28 27
8 15 15 29 28

- 16 16 8
- 20 1612 8 20 15 30 29
- 22 2012 1222 20 31 30

400 335
450 242
295 170
300 30 60 35 - 16 2212
290
290
290 335
335 242
242 170
170 30 30 35 35 16 1612
290
335
242
170
290
335
242
170 30 30 - 35 16 1612
290
335
242
170
290
335
242
170 40 30 - - 16 1612
290
290 335
335 295
242 300
170 60 40 400
450
295
300
290
335
295
300 60 60 -

see
fig. see

1216 22 27 31
1216 16 27 27
1216 16 28 27
1216 16 29 28

- 20 1612 1220 16 30 29
- 22 2012 1222 20 31 30

290
400 335
450 242
295 170
300 30 60 35 - 16 2212 1216 22 27 31
290
335
242
170
30
35
16 12
16
27

290
335
242
170
30
35
16 12
16
27
335
242
170
30
16 12
16
28
290
335
242
170
30
35
16 12
16
27

130

290

110

130

290

335

242

170

40

195

175

290

335

335

300

60

195

175

400

450

295

300

60

195

175

400

450

295

300

30

195
195
195

175
175
175

--

400
450
295
300
30
40
22 12
22
32
400 450
450 295
295 300
300 30 30 - 40 22 2212 1222 22 33 32
400

80
125
80
125

195
195
195
195

175
175

--

400 450
450 295
295 300
300 40 30 - 40 22 2212 1222 22 34 32
400

175
200

--

400 450
450 340
295 300
300 60 30 400

--

125
125

195
195

175
200

--

400 450
450 340
295 300
300 60 40 400

2750
--

125
80

195
195

125
125

195
195

200
200
200
200

---

3742 684
650 3129
3092 2750
125
2500 3813
80
1000
125
1600 3813 684 3129
12,
13:
Brown
glazed
porcelain,
other
colours
and
125
2500 3742 650 3092

195
195
195

200
200

--

400 450
450 350
340 300
300 40 60 55 - 22 2212 1222 22 37 35
400
400
400 450
450 350
340 300
300 40 60 - - 22 2212 1222 22 38 36
400
450
350
300
400
450
350
300 50 40 - 55 22 2212 1222 22 39 37

200

2370

420

1950

2325

420

1905

2370

420

1950

2609

420

2189

2572

420

2152

2609
2572

420

2152

2500

3518
684
2834
800
3518 684
684 2834
2834
1250 3518

2500
2500
-

15:

15:

684

2189
2834

12, 13:

3518

420

3813 684
684 2842
3129
3407

125
125
125
80

80
80
80

Other creepage distances upon request


According to IEC 137 level II or better

Brown glazed porcelain, other colours and


Other creepage distances upon request
According to IEC 137 level II or better

Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

130
130
175
175

17:
195 16, 200

24, 25, 29, 32:

290
290
290
400

400

335
335
335
450

242
335
295

170
300
300

300

30
40
60
60

40

40

16
20
22
22

12

16

16

12

16

16

12

16

20

12

20

22

12

22

12
12
12

20
22
22

29
30
31
32

28
29
30
31

- 22 2212 1222 22 35 33
- 22 2212 1222 22 36 34

22

12

22

38

12

22

39

24, 25, 29, 32:

350

170

L400
on L4. 350
The values
table are- valid 22
1 depends
450
300in the50
for L4= 0mm. If L4>0mm add L4 to L1 and L.
Other dimensions on request.

16, 17:

450

242

L1 depends on L4. The values in the table are valid


for L4= 0mm. If L4>0mm add L4 to L1 and L.
Other dimensions on request.

Page 9 / 24

Page 9 / 24

40497230_00

40497230_00
40497230_04

04

05

COT 1300

COT 1300

362

362

209

625

209

625

570

570

1300

950

1300

COT 1425

420

420

243

695

243

695

630

630

1425

1050

1425

COT 1550

550

550

318

750

318

750

680

680

1550

1175

1550

1000

cable

2500

Fixed cond.

1000

cable

1600

Fixed cond.

Fixed cond.
Fixed cond.

COT 1675

550

550

318

750

318

750

680

680

1675

1175

1675

COT 1800

550

550

318

870

318

870

18

17
18

Comments related to columns 133:

790

790

1800

1300

1800

Mass
Approx.
Cantilever
test load (min)

Cantilever test load (min)

Mass Approx.

Standard creepage distance

Standard creepage distance

5000
5000

2800
2800

9115

2800

540

5000

500

5000

9115

5000

500

5000

530

5000

560

5000

865

5000

560

5000

3300 3300
*13750*13750
930

865
5000

5000

3300 3300
*13750*13750
990

930
5000

5000

3800 3300
14350*13750
940

990
5000

5000

940
5000

5000

3300

2800

2800
*13750

3800 3800

14350
1000

3800 3800

3800 3800
14350

1030

5000
1000

5000

980

5000
1030

5000

5000
980

5000

3800 3800

1100

5000
1060

5000

630

630
-

4200
4200
4200

14350

1050

3800
4200

1150

14350

4200

1200

4200

Connection
see
17 to133:
23
Commentssystem
related
topages
columns

13: * 31mm/kV in standard for Type COT 1425

04: Bushings test voltage at 50Hz 60 sec.

11: Extension for current transformer (other extensions on request)

Connection system see pages 17 to 23

13: * 31mm/kV in standard for Type COT 1425

Page 10 / 24

540

5000

11: Extension for current transformer (other extensions on request)

Substitute for E 322.81&E 322.91

5000

1060
14350

Page 10 / 24

5000

530

04: Bushings test voltage at 50Hz 60 sec.

Substitute for E 322.81&E 322.91

480

3800 3800

Fixed cond.

Fixed cond.

480

9115

630

2500

2500

9115

2800

kg

Fixed cond.

2800
2800

630

Fixed cond.

1600

1600

cable

630

2800

2800

cable

1000

2800

2800

1000

Fixed cond.

630

10002500
cableFixed cond. 630

2500

630

10002500
cableFixed cond. 630

25001600
FixedFixed
cond.cond.
COT 1800

630

2500
Fixed cond. 630
cable

Fixedcable
cond.
117516001000

15
14

630

1000

25001600
FixedFixed
cond.cond.

13
12 COT 1675

16

Fixed cond.

117516001000
Fixedcable
cond.

12
11

17

Fixed cond.

1600

25001600
FixedFixed
cond.cond.

09 COT 1550
10

15

2500

105016001000
Fixedcable
cond.

08
09

16

2500

06 COT 1425
07

14
13

Fixed cond.

cable

1600

05

10
11

1600

950

06

07
08

cable

1000

mm

25m m/kV

03

04

25 mm / kV

02

03

15

mm
mm
mm mm
kg
mm mm mm mm
mm

1000

950

14
15

25m m/kV

950

1314

25 mm / kV

Switching Impulse wet (SIL): 250/2500s

Switching Impulse wet (SIL): 250/2500s

1175

AD Arcing distance (min.)

1175

510

AD Arcing distance (min.)

510

560

CT Space L4 see fig.3 page 12

560

209

kV

1213

Cable cross section


Conductor
CT Space L4 see fig.3 page 12

209

362

kV

1112

Cable cross section


Conductor

362

kV

1011

10

Standard: 0, 300, 500

COT 1175

kV

09

Standard: 0, 300, 500

COT 1175

kV

kV

09

Connection to Transformer

kV

Rated current (Ir)

kV

Rated current (Ir)

Transformer Power frequency voltage

kV

(BIL)
Lightning
Impulse withstand voltage
(BIL)

Bushing Dry Power frequency voltage

01
02

Transformer
Power frequency voltage
withstand (AC)
withstand
Lightning(AC)
Impulse withstand voltage

Maximum phase to earth voltage


kV

Maximum phase to earth voltage

Highest voltage (Um)


kV

kV

01

Bushing
Dry
Power frequency voltage
withstand
(AC)
withstand (AC)

0202 0303 0404 0505 06 06 07 07 08 08

Highest voltage (Um)

Type
Type

NN

01
01

Connection to Transformer

TypeCOT
COT11751800
11751800
Type

5000

1100

5000

1050

5000

5000
5000

1150

5000

1200

5000

40497230_00

40497230_00
40497230_04

Type
COT
11751800
Type
COT
11751800
1616

1717

1818

19
19

20
20

21
21

22
22

23
23

24
24

25
25

2626

2727 2828 29 29 30 3031 3132 32 33 33

L1

L2

L3

L6

L7

D1

D2

D3

D4

D5

Rated current (Ir)

Rated current (Ir)

08 08

1000

L1

L2

L3

L6

L7

4270

720

3550

3240

125

D2

D3

D4

D5

D6

D7

400

450

390

330

40

250

235

400

450

390

330

40

250

235

400

450

390

330

40

3550

3240

125

250

1600

4230

720

3510

125

250

2500

4230

720

3510

125

250

4230
4230
4270

720
720
720

3510
3510
3550

3240

125
125
125

250

235
235
235

235

mm

see
fig. see

fig.

mm

235

720

1000

D1

250

4270

2500

mm

D7

mm

1000

1600

D6

400
400
400

400

450
450
450

450

390
390
390

390

330
330
330

330

40

40
40
40

55
55

55
-

22
22
22

22

12

22

12

22

12

22

12

22

12

22

12

12
12
12

22
22
22
22

40

22

40

22

41

22

41

22

40

22

41

41
41
40

4270
720
3550
1000
3510
1600 4230 720

3240

125

250

4230
720
3510
1600
3510
2500 4230 720

125

250

250

235

400

450

125
125

250
280

235
291

380

400
530

450 477
390 400
330 40 40 68 - 23 2212 1225 2242 41
590

2500
5055 720
820 3510
4235
10004230

3995

125
125

250

235

235

235

400

400

400

450

450

450

390

390

390

390

330

330

330

330

40
40

40
40

55
-

22
22

12
12

22
22

41
41

1000
4965 820
820 4235
4145
16005055

3995
-

125
125

280
280

291
291

380
380

530
530

590 477
477 400
400 40 40 - 68 23 2312 1225 2543 42
590

1600
4965 820
820 4145
4145
25004965

--

125
125

280
280

291
291

380
380

530
530

590 477
477 400
400 50 40 590

2500
5790 820
1055 4145
4735
10004965

4495

125
125

280
280

291
291

380
380

530
530

590 455
477 500
400 40 50 68 - 23 2312 1225 2542 43
590

- 23 2312 1225 2543 43

5700 1055
1055 4735
4645
16005790
1000

4495

125
125

280
280

291
291

380
380

530
530

590
590 455
455 500
500 40 40 - 68 23 2312 1225 2543 42

5700 1055
1055 4645
4645
25005700
1600

--

125
125

280
280

291
291

380
380

530
530

590
590 455
455 500
500 50 40 -

5935 1055
1200 4645
4735
10005700
2500

4495
-

125
125

280
280

291
291

380
380

530
530

590
590 455
455 500
500 40 50 68 - 23 2312 1225 2542 43

280

291

380

530

590

455

500

40

1600 5845 1200 4645


5935
1200 4735
1000
2500

1600

1000

2500

1600

5845

5845

6345

5845

6245

1200

1200

1200

1200

1200

4645

4645

4495
-

5145

4895

5045

4645

125

125

125

280

530

590

455

500

50

125

125

280

280

291

380

530

590

455

500

40

125

280

291

380

530

590

455

500

40

280

291

380

530

590

455

500

50

380

125

280

1600

6245

1200

5045

125

280

125

1200 porcelain,
5055 other-colours125
2500
12, 13:6255
Brown glazed
and
15:

12, 13:
15:

Other creepage distances upon request


According to IEC 137 level II or better

Brown glazed porcelain, other colours and


Other creepage distances upon request
According to IEC 137 level II or better

Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

500

380

4895
-

455

291

5145

5055

590

280

1200

1200

530

280

6345

6255

380

125

1000

2500

291
291
291
291
291

280 16, 17:


291

380
380
380
380

24, 25, 29, 32:

16, 17:

24, 25, 29, 32:

530
530
530

590
590

455

500

50

68
-

23

23

12

23

12

23

12

12
12
12

590
455
500 50
23
L530
1 depends on L4. The values in the table are valid
for L4= 0mm. If L4>0mm add L4 to L1 and L.
Other dimensions on request.

12

40

68

23

12

23

12

500

40

23

23

455

500

40

68

12

590

455

500

23

530

590

455

40

- 23 2312 1225 2543 43

23

12

25
25
25
25
25

43

25

43

25

42

25

43

42
43
43

25

42

25

43

25

43

43

L1 depends on L4. The values in the table are valid


for L4= 0mm. If L4>0mm add L4 to L1 and L.
Other dimensions on request.

Page 11 / 24

Page 11 / 24

40497230_00

40497230_00
40497230_04

Dimensional
Drawing
Dimensional
Drawing
D6

D6View A

View A

L6

D5

L6

D5

L3
L2

AD

L3
Fig. 1

Fig. 2
COT 5501050 (Um =245kV),
3150 A

Fig. 1

L L2

AD

D4

Fig. 2

COT 1050 (Um=300kV), 2500A

D4

1175 1800
COTCOT
5501050
(Um =245kV),
3150 A

COT 1050 (Um=300kV), 2500A


COT 1175 1800

e L7

L4 L7

D1
Only for COT
420 kV

L1

L4

30

D1

L1
Only for COT
420 kV

L1
D7
Fig. 3

D7
Substitute for E 322.81&E 322.91

Fig. 3

Substitute for E 322.81&E 322.91

30

D
Fig. 4

Fig. 5

L1

D40497230_00

Page 12 / 24
Fig. 4

Page 12 / 24

Fig. 5

40497230_00
40497230_04

Porcelain
and composite
insulator
Porcelain
and composite
insulator
Porcelain
Insulator
(Type
COT)
Porcelain
Insulator
(Type
COT)

BrownBrown
color color
(RAL 8016)
(RAL 8016)

Composite
(Type
COTC)
CompositeInsulator
Insulator
(Type
COTC)

Gray
color
Gray
color
(ANSI gray N70)
(ANSI gray N70)

D4

D4

Alternate sheds
Alternate
sheds
(ANSI gray N70)
(ANSI gray N70)

D4

D4

Helicoil
sheds
Helicoil
sheds
(ANSI gray N70)

(ANSI gray N70)

D4

D4

D4

D4

All COT(C) can be equipped with silicone rubber insulators upon request without affecting dimensions
except D4

All COT(C) can be equipped with silicone rubber insulators upon request without affecting dimensions
Page 13 / 24
40497230_00
except D4
Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

Page 13 / 24

40497230_00
40497230_04

Standard
Standard
levelindicator
indicator
OilOil
level
COT
125,
COT170
170
COT 125, COT

Oil level
indicator
Oil level
indicator
COTCOT
250
COT
250 1050
COT 1050

20

20

60
Fig. 6

Fig. 7

60
Air escape screw

Test tap (2kV)


Fig. 6

22

O-ring gasket

Fig. 7

Test tap (2kV)

Air escape screw

O-ring gasket

22
6
Multiple spring contact

Flat gasket

Fig. 8

Fig. 9

Multiple spring contact

Fig. 8
Substitute for E 322.81&E 322.91

Substitute for E 322.81&E 322.91

Flat gasket
Page 14 / 24

Page 14 / 24

40497230_00

Fig. 9

40497230_00
40497230_04

Options
Options
Magnetic
oil level
indicator
(95)
Magnetic
oil level
indicator
(95)
COT
250

COT
1800
COT 250 COT 1800

Arcing
horns
Arcing
horns

Type

Type

S
min

S max

min mm

COT125
170
COT

--

COT 170

COT 250

220

270

COT 325

300

390

COT 450

430

520

COT 550

420

650

COT 650

500

750

COT
COT550
750

420
500

650
850

COT
650
COT 1050

500
750

750
1200

COT 750

500

850

COT 1050

750

1200

COT 450

Fig. 10

220
300
430

- -

270
390
520

Fig. 11

Voltage tap according to ANSI/IEEE (20kV)

Oil sampling device


Valve

Fig. 10
Multiple
spring contact

Voltage tap according to ANSI/IEEE (20kV)

Fig. 11

Oil sampling device


Valve

Multiple spring contact

Fig. 12

Substitute for E 322.81&E 322.91

COT 325

mm -

COT 125

COT 250

Substitute for E 322.81&E


322.91
Fig. 12

max

Fig. 13

Page 15 / 24

Page 15 / 24

Fig. 13

40497230_00

40497230_00
40497230_04

Recommendations
for
Recommendations
forlead
leadout
out arrangement
arrangement
Embeddedshield
shield
Embedded

External
shieldshield
External

These bushings
bushings
are
These
are
equipped on the lower
equipped on the lower
end with a cone shaped
end with a cone shaped
epoxy resin tube and an
epoxy
resin tube
and an
embedded
electrode.
embedded
electrode.
Therefore,
additional
Therefore,
additional
barriers or electrodes
may be oromitted
and
barriers
electrodes
distance
ground and
is
may
be toomitted
reduced
distance to ground is
reduced

R1

R1

Oil conditions:
Mineral
oil with less than 10ppm water content and
S
dielectric strength higher than 60kV (acc. to IEC 60156)

Oil conditions:

Fig. 14

Mineral oil with less than 10ppm water content and


Draw lead insulation
dielectric strength higher than 60kV (acc. to IEC 60156)
COT 550750

COT 1050

Fig. 14

40

35,7

28

40

50

30

15

50

30

5 thickness75

COT 250

10

COT 325

10

120

COT 450

12

135

COT 550

12

COT 650

15

COT 750

15

Fig. 16

S
15

COT COT
1050 325

80 (Um=245kV)
94 (Um=300kV)
Fig. 17

S
80 (Um=245kV)
94 (Um=300kV)

Fig. 16 for E 322.81&E 322.91


Substitute

Substitute for E 322.81&E 322.91

Fig. 17

Page 16 / 24

Page 16 / 24

mm

COT 170

COT 125

Min.

5 insulation
65

COT 250

28

Min. distance to
grounded parts

COT 125
Type

COT 170

Fig. 15

Min.
insulation
thickness

Cable insulation and distance to grounded


S
R
R1
parts

COT 1050

35,7

Cable insulation and distance to grounded


parts

Type

Draw lead insulation

COT 550750

Fig. 15

COT COT
1175 450
to
COT COT
1800 550

20
-

S
5
5
10
10
12
12

85

145
180
225
300
-

Min. distance
to
grounded parts
-

mm

65
75
85

R1

250

275

300

120 375

135
See spec

40497124
145

250

COT 650

15

180

275

COT 750

15

225

300

COT 1050

20

300

375

COT 1175
to
COT 1800

See spec
40497124

40497230_00

40497230_00
40497230_04

Removable
split conductor
Removable
split conductor
COT
1175
COT 1175
COT 125
125
COT
1250
A
1250 A

Cable bolt

Cable bolt

Removable
split Removable
conductor

split conductor

30
3 fixing screws

30

3 fixing screws

Position of standard split


conductor.
Others positions on request

Position of standard split


conductor.
Others positions on request

30
29

Fig. 18

30

Oil side end


COT 125, COT 170

Oil side end

29

Fig. 18

1600 3150A

1250A

1000A
40

40

COT 125, COT 170

1600 3150A

1250A

1000A
40

40
30
29
Conductor 35

30

40

80

80
Cable

125

Fig. 19

80

Removable29
copper conductor

Fig. 20

Conductor 35

80
Substitute
for E 322.81&E
Cable
Fig. 19 322.91

Substitute for E 322.81&E 322.91

Page 17 / 24

125

Fig. 21

40

80
Page 17 / 24
Removable copper conductor

Fixed copper-conductor

80

Fig. 20

40497230_00

Fixed copper-conductor

Fig. 21

40497230_00
40497230_04

Oil side
endend
Oil side
COT
COTCOT
250 250
COT
450450
1600
A1600 A

1250A
1250A

1000A
1000A

30

30
29

90
35

35,7
80

Cable

90

Conductor 35

35,7

80

29

Conductor 35

Cable

80
Removable copper conductor

Fig. 22

80
Fixed copper-conductor
35

Fig. 23

80

2500A

Removable copper conductor

Fig. 22

80

3150A

Fixed copper-conductor

Fig. 23

125

125

125

125

40

94
Fixed copper-conductor

104
Fixed copper-conductor

Fig. 25

40

40

94

104

Fixed
copper-conductor
Substitute for
E 322.81&E
322.91

Substitute for E 322.81&E 322.91

Fig. 24

3150A

2500A

40

Fig. 24

Fig. 25

Page 18 / 24

Page 18 / 24

Fig. 26

40497230_00

Fixed copper-conductor

Fig. 26

40497230_00
40497230_04

Oil side
Oilend
side end
COT
750
COT 750
COT 550
550
COT
1600
A A
1600

1250A
1250A

1000A
1000A

30

30
41

28

41

28

29

15

15

Conductor 35

29

90

90

Conductor 35

35,7

35

35,7 68
68
Cable

68

Cable

68

Removable copper conductor

Fig. 27

68

2500A

35

Fixed copper-conductor

68

3150A

Removable copper conductor

Fig. 27

Fig. 28

Fig. 29

Fixed copper-conductor

Fig. 28

Fig. 29

3150A

2500A
15
22,5

15
125

22,5

125
40

195

125

86

40

114

125

150

195

160

40

240

Fixed copper-conductor

86

150

Fig. 30

Fixed copper-conductor with removable screwed shield Fig. 31

40

114

160
240

Fixed
copper-conductor
Substitute
for E 322.81&E
322.91

Substitute for E 322.81&E 322.91

Fig. 30

Page 19 / 24
40497230_00
Fixed copper-conductor with removable screwed shield Fig. 31

Page 19 / 24

40497230_00
40497230_04

Oil side
endend
Oil side
1050,
= 245
COTCOT
1050,
UmUm
= 245
kVkV
1600
A
1600 A

1250A
1250A

1000A
1000A

30

30

30

30
14

14

40

78

50

78

50
29

25

40

Cable

Cable

90
35

Conductor 38

119

119

119
80

119

29
Conductor 38

25

80

90

Removable copper conductor

Fig. 32

119

2500A
Fig. 32

Fixed copper-conductor

Fig. 33

Removable copper conductor

119

Fixed copper-conductor

Fig. 33

170

40

95

170

260
Fig. 35

40

Fixed copper-conductor with removable screwed shield Fig. 36

95

180
260

134

Substitute for E 322.81&E 322.91

230

125
180

134

Fixed copper-conductor

230

125

125

Substitute for E 322.81&E 322.91

Fig. 34

3150A

125

40
Fixed copper-conductor

Fig. 34

3150A

2500A

40

35

Fig. 35

Page 20 / 24Fixed copper-conductor with removable


40497230_00
screwed shield

Page 20 / 24

Fig. 36

40497230_00
40497230_04

Oil side
Oilend
side end
COT Um
1050,
300 kV
COT 1050,
= Um
300=kV
1000A
1000A

1600A
1600A

30

30

14

14

55

50

50
90

25

55
25
95

95

90

35
95

35

134
Cable

134

134

95

Fixed copper-conductor

Fig. 37

134

2500A
Cable

Fig. 38

Fixed copper-conductor

Fig. 37

Fig. 38

2500A

230

125
170

40

230

125
180

170

260

40 with removable screwed shield


Fixed copper-conductor

Fig. 39

180
260
Page 21 / 24
Substitute for E 322.81&E 322.91Fixed copper-conductor with removable screwed shield

Substitute for E 322.81&E 322.91

Page 21 / 24

Fig. 39

40497230_00

40497230_00
40497230_04

Oil side
endend
Oil side
1175
1300
COTCOT
1175
1300
1000A

1000A

1600A
1600A

120
80

120

80
55
110

125

55

190

Oil side connector according to customer request

110

125

Cable with fixed shield

190

Fixed conductor

Fig. 40

Fig. 41

Oil side connector according to customer request

COT 1425 1800

Cable with fixed shield

1000A

Fixed conductor

Fig. 40

1600A

Fig. 41

COT 1425 1800


1000A

1600A

68

280
210

160

68

280

210

160

210

160

330

Oil side connector according to customer request

Cable with fixed shield

Fixed conductor

Fig. 42

210

160

330
Substitute forCable
E 322.81&E
with322.91
fixed

Substitute for E 322.81&E 322.91

Fig. 43

shield

Fig. 42

Page 22 / 24

Page 22 / 24

Oil side connector according to customer request

40497230_00

Fixed conductor

Fig. 43

40497230_00
40497230_04

Oil sideOilend
shields
side: External
end : External
shields
FIXED
SHIELD
FIXED
SHIELD

SHIELD
BAYONET
SYSTEM
SHIELDWITH
WITH
BAYONET
SYSTEM

3 x M6 depth 15mm equidistant


on a drilling diameter D

3 x M6 depth 15mm
Fig. 44 equidistant
on a drilling diameter D
SCREWED SHIELD

Fig. 44

SCREWED SHIELD

Detail A

Detail A
Connection according to
customer drawing
Fig. 45

Fig. 46

Connection according to
customer drawing
Substitute for E 322.81&E 322.91

Page 23 / 24

Fig. 45

Substitute for E 322.81&E 322.91

40497230_00
Fig. 46

Page 23 / 24

40497230_00
40497230_04

Product Range

Quality

Bushings for

At Trench quality is a way of life.


Trench quality assurance
complies with the most stringent
standards of ISO 9001 and ISO 14001.

Power Transformers
up to 550 kV, 3150A
High Current Application
up to 52 kV, 31,5KA

Certified by AFAQ since 1994

Transformer to SF6
connection up to 550kV
Gas-insulated Switchgear
(GIS) up to 800 kV, 6000A
Generators
up to 36 kV, 50000 A
Railways
Buildings , Wall
up to 245 kV, 5000 A
Bushings according
Standard IEC 60137
Bushings according to
customers special specification

Trench Limited
Bushing Sales Office

1865 Clements Road


Pickering, ON
L1W 3R8
Canada
Phone : +1-647-925-9799
+1-647-925-9793
Fax: +1-416-751-6952

Trench France SAS

16, rue du Gnral Cassagnou


B.P.80070
F-68302 Saint-Louis Cedex France
Phone: +33 3 89 70 23 23
Fax: +33 3 89 70 23 59
imprimerie de saint-louis

substitute for E 322.81&E 322.91

40497230_04

www.trenchgroup.com

Sales-bushing.fr@trench-group.com

All rights reserved.


Brands and trademarks used in this document
are the property of Trench
Subject to change without prior notice.
The information in this document contains general
descriptions of the technical options which are not
necessarily available in every single case. The required
features must therefore be defined in each individual case
when concluding the contract.