Capitalization of Losses: Present Value Calculation
Capitalization of Losses: Present Value Calculation
Capitalization of Losses: Present Value Calculation
Application to Transformers
The Present Value is used as No Load Loss Value (EUR/kW)
If you know the average load factor of the transformer in use you can also calculate the present value of
the Load Losses by using the formula (load factor is in percent of max allowed current):
0.055
8760
6.50%
30
6300
In our case:
Load factor in the transformer (% of Max current)
No Load Losses value (EUR/kW)
Load losses value (EUR/kW)
45%
6300
1280
Comparison Hexaformer-Competition
Re-enter the No load and load losses value
No Load Losses Value (EUR/kW)
Load losses Present Value (EUR/kW)
6300
1280
Hexaformer standard
Competitor 1
145
170
215
1500
1600
1600
2840
3120
3410
2840
3120
3410
e in Wikipedia):
Competitor 2
225
1980
3960
3960
Capitalization of losses
Present value calculation
If you know the present value of losses please go directly to "Application to Transformers"
We use the following formula for calculation of Present Value of each kW over the life time of the product (see Present Value in Wikipedia):
Application to Transformers
The Present Value is used as No Load Loss Value (SEK/kW)
If you know the average load factor of the transformer in use you can also calculate the present value of
the Load Losses by using the formula (load factor is in percent of max allowed current):
0.55
8760
6.50%
30
63000
In our case:
Load factor in the transformer (average % of Max current)
No Load Losses value (SEK/kW)
Load losses value (SEK/kW)
45%
63000
12800
Comparison Hexaformer-Competition
Re-enter the No load and load losses value
No Load Losses Value (SEK/kW)
Load losses Present Value (SEK/kW)
55000
11000
Hexaformer standard
Competitor 1
145
240
210
1500
1700
1950
24500
31900
33000
24500
31900
33000
Competitor 2
225
1980
34200
34200