Prisma Plus LV Switchboards


Disconnectable-type switchboards
Electrical distribution
Motor control

Catalogue

Contents

Index

Presentation
Electrical-distribution switchboards
Motor Control Centers
Examples of switchboard configurations
Presentation of disconnectable mounting plates
Cubicle with disconnectable mounting plates

4
6
10
14
16

Functional units
Compact NS 100/630
Multi 9 devices
1-component motor feeder
3-component motor feeder with circuit breaker
3-component motor feeder with fuse
Accessories
LCDD unit

18
19
20
22
26
30
33

Distribution
Presentation of vertical busbars with clamp connections
Selection of vertical busbars with clamp connections

36
38

Enclosures
Presentation of enclosures
Selection of enclosures

40
42

Diagrams

45

Index

Cat. no Designation

Pages

03000
03001
03002
03004

Modular device rail


Adjustable modular device rail
Rear modular device rail

19
19
19

04000
04545
04548
04550
04636
04637
04642

Horizontal busbar without holes, 50x10mm


Horizontal busbar without holes, 80x10mm
Horizontal busbar without holes, 100x10mm
1600A connection plate for 10mm horizontal bar to lateral Linergy
busbar
3200A connection plate for 10mm horizontal bars to vertical flat bar
Mounting hardware for joint > 80mm

38
38
38
39
39
39

08000
08513
08514
08516
08523
08524
08526
08536
08546
08593
08594
08603
08604
08606
08633
08634
08636
08653
08654
08656
08683
08684
08686
08693
08694
08696
08711
08717
08721
08723
08724
08726
08733
08734
08736
08743
08744
08746
08760
08765

IP30 plain door, W=300mm


IP30 plain door, W=400mm
IP30 plain door, W=650mm
IP55 plain door, W=300mm
IP55 plain door, W=400mm
IP55 plain door, W=650mm
IP30 transparent door, W=650mm
IP55 transparent door, W=650mm
IP30 door with cut-out for human/switchboard interface (HSI),
W=300mm
IP30 door with cut-out for human/switchboard interface (HSI),
W=400mm
Framework, W=300mm, D=600mm
Framework, W=400mm, D=600mm
Framework, W=650mm, D=600mm
IP30 plain roof, W=300mm, D=600mm
IP30 plain roof, W=400mm, D=600mm
IP30 plain roof, W=650mm, D=600mm
IP55 plain roof, W=300mm, D=600mm
IP55 plain roof, W=400mm, D=600mm
IP55 plain roof, W=650mm, D=600mm
IP55 plain gland plate, W=300mm, D=600mm
IP55 plain gland plate, W=400mm, D=600mm
IP55 plain gland plate, W=650mm, D=600mm
IP30 2-part gland plate, W=300mm, D=600mm
IP30 2-part gland plate, W=400mm, D=600mm
IP30 2-part gland plate, W=650mm, D=600mm
P31 sealing kit
IP55 sealing kit for side-by-side combinations
2 side plates for plinth, D=600mm
Plinth, H=100mm, W=300mm, D=400mm
Plinth, H=100mm, W=400mm, D=400mm
Plinth, H=100mm, W=650mm, D=400mm
IP30 rear panel, W=300mm
IP30 rear panel, W=400mm
IP30 rear panel, W=650mm
IP55 rear panel, W=300mm
IP55 rear panel, W=400mm
IP55 rear panel, W=650mm
2 IP30 side panels, W=600mm
2 IP55 side panels, W=600mm

42
42
42
42
42
42
42
42
42
42
42
42
42
43
43
43
43
43
43
43
43
43
43
43
43
43
42
43
43
43
43
42
42
42
42
42
42
43
43

87000
87454
87635
87648

10 micro-switches
electrical contact grease, 1kg
50 grommets, diameter 22mm

32
32
32

88000
88002
88004
88005
88006

Form 2 cover for disconnectable type busbars, D=600mm


Connection between horizontal and 100x10mm vertical busbars
Support for 50x10mm vertical bars
Support for 100x10mm vertical bars

38
39
38
38

Cat. no
88007
88010
88011
88012
88013
88020
88021
88022
88023
88030
88031
88032
88033
88034
88035
88050
88051
88052
88053
88054
88055
88063
88066
88400
88401

Designation
Connection between horizontal and vertical busbars
Fixed part of disconnectable mounting plate for NS250, 3P
Fixed part of disconnectable mounting plate for NS250, 4P
Fixed part of disconnectable mounting plate for NS630, 3P
Fixed part of disconnectable mounting plate for NS630, 4P
Moving part of disconnectable mounting plate for NS250, 3P
Moving part of disconnectable mounting plate for NS250, 4P
Moving part of disconnectable mounting plate for NS630, 3P
Moving part of disconnectable mounting plate for NS630, 4P
Moving part of disconnectable mounting plate for MCC, 50mm
Moving part of disconnectable mounting plate for MCC, 75 mm
Moving part of disconnectable mounting plate for MCC, 100 mm
Moving part of disconnectable mounting plate for MCC, 150mm
Moving part of disconnectable mounting plate for MCC, 200 mm
Moving part of disconnectable mounting plate for MCC, 300 mm
Fixed part of disconnectable mounting plate for MCC, 50mm
Fixed part of disconnectable mounting plate for MCC, 75 mm
Fixed part of disconnectable mounting plate for MCC, 100 mm
Fixed part of disconnectable mounting plate for MCC, 150mm
Fixed part of disconnectable mounting plate for MCC, 200 mm
Fixed part of disconnectable mounting plate for MCC, 300 mm
LCDD support for disconnectable functional unit, D=600mm
Multi9 raiser, H=50mm
LCDD for non-reversing motor
LCDD for reversing or 2-speed motor

Pages
39
18
18
18
18
18
18
18
18
20
23
23
19, 23, 27
23, 27
23, 27
20
23
23
19, 23, 27
23, 27
23, 27
32, 34
31
33
33

Electrical-distribution
switchboards

General presentation
Prisma Plus
disconnectable-type
switchboards

These electrical-distribution switchboards


are designed to contain a set of
disconnectable functional units.
The feeders, made up of three or four-pole
Compact NS circuit breakers up to 630 A or
Multi9 devices, are installed on
disconnectable mounting plates and
connect directly to vertical busbars via
clamps.
Upgrades or maintenance can be carried
out by qualified personnel with the
switchboard energised, thus ensuring true
continuity of service at all times.
The disconnectable mounting plates can be
installed in a cubicle 650 mm wide and 600
mm deep, perfectly compatible with all
standard Prisma Plus cubicles. The vertical
capacity is 30 modules, each 50 mm high.

PD391168

Presentation

PD391104

Connections to the disconnectable functional units are made from the front. Cables are run in an
adjacent cubicle.

The disconnectable mounting plates can be installed in a cubicle 650 mm wide and 600 mm
deep, perfectly compatible with all standard Prisma Plus cubicles. The vertical capacity is 30
modules, each 50 mm high.

General presentation
Prisma Plus
disconnectable-type
switchboards

Electrical-distribution
switchboards

Presentation

An upgradeable
switchboard

PD390694

The height of the disconnectable mounting plates is perfectly suited to the volume of
three-pole and four-pole devices. Integration of the control wires within the volume of
the functional units ensures very compact switchboards.

Addition or replacement of a feeder can


be carried out quickly by qualified
personnel, at any time and without risk.

... easy to set up


The disconnectable mounting plates can
be easily installed from the front.
Direct connection via clamps is very
easy. This system eliminates any
intermediate connections and ensures
high-quality electrical contacts.

PD390700

Combined distribution and motor-control


devices.

An electrical installation that


remains available

PD391096

Fixed part equipped with "double-contact"


clamps.

Maintenance can be carried out by


qualified personnel even with the
switchboard energised, thus ensuring
true continuity of service for the
installation.

Auxiliary connection block in the connection


compartment.

High dependability to protect


operators and the installation.

PD391106

PD390688

Optimised device density in cubicles

All components and typical switchboard


configurations are tested in test centres.
They comply with standard IEC 60439-1
(switchboards) and standard IEC
947.4.1 (switchgear).

Voltage measurement.

Motor Control Centers

General presentation
Prisma Plus
disconnectable-type
switchboards

Connections to disconnectable functional units are made from the front. Cables are run in an
adjacent cubicle.
PD391171

These Motor Control Centers are electrical


switchboards combining a set of functional
units intended for motor control and
protection.
The devices are installed on disconnectable
mounting plates and connect directly to
vertical busbars via clamps.
Each functional unit, generally connected to
a PLC via a bus, is equipped with a
communication module that can be remotely
set up to communicate with a supervisor.
The module transmits not only information
on feeder status (open, closed), but also
measurement data on overloads,
underloads, insulation, etc.
By indicating the type of fault at the source
(motor temperature rise, loss of line current,
etc.), Schneider Electric communicating
electronic relays make it possible to
optimise maintenance work.
This limits the down time of processes and
the cost of servicing.
The addition or replacement of a feeder by
qualified personnel with the switchboard
energised ensures true continuity of service.

PD391167

Presentation

The disconnectable mounting plates can be installed in a cubicle 650 mm wide and 600 mm
deep, perfectly compatible with all standard Prisma Plus cubicles. The vertical capacity is 30
modules, each 50 mm high.

General presentation

Motor Control Centers

Prisma Plus
disconnectable-type
switchboards

PD390695

The ease of fault detection, the reliability of


diagnostics and the fast servicing of
Schneider Electric motor control centers all
contribute to a high level of continuity of
service in the installation.

An upgradeable
switchboard

PD390694

Presentation

The forms and partitioning make


operational work possible by qualified
personnel with the switchboard
energised. The disconnectable
mounting plates connect directly to the
vertical busbars at the rear of the cubicle
via clamps. Addition or replacement of a
feeder can be carried out quickly, at any
time and without risk.

An electrical installation that


remains available

Installation of a protection module.

Faults (e.g. motor insulation) are


detected at their source before they
become critical. Precise maintenance
operations can be scheduled in an
optimum manner, without affecting the
continuity of service in the installation.

Local control on the LCDD unit.

High dependability to protect


operators and the installation.

PD391105

With Tesys U, the small size of the disconnectable mounting


plates make it possible to reduce the size of the switchboard by
20 to 30%.

With the circuit breaker-contactor


combinations or the Tesys U controller,
functional modules (communication and
protection) can be easily changed at all
times without having to rewire the entire
assembly.
Start-up and servicing times for
modifications are significantly reduced.
Control via the PLC takes place via a
bus that supports the most common
communication protocols on the market
(Modbus, Profibus, Devicenet,
Ethernet). Wiring is reduced to a strict
minimum.

PD390698

... easy to install

PD390697

Combined distribution and motor control


devices.

All components and typical switchboard


configurations are tested in test centres.
They comply with standard IEC 60439-1
(switchboards) and standard
IEC 60947.4 (switchgear).

Voltage measurement.

General presentation

Motor Control Centers

Prisma Plus
disconnectable-type
switchboards
Presentation

Technical characteristics
PD391108

Mechanical characteristics of enclosures


b steel sheet metal
b surface treatment: electrophoresis + hot-polymerised polyester epoxy powder,
white colour RAL 9001.
b partitioning: Form 2
b degree of protection:
v doors closed:
- IP30/31, IK08
- IP55, IK10
v doors open:
- IPxxB
b dimensions
v height:
2000 mm
v widths:
650 mm
cubicle for disconnectable mounting plates
300/400 mm cable compartment
v depth:
600 mm
b capacity: 30 modules of 50 mm.

Mechanical characteristics of disconnectable mounting plates


b steel sheet metal
b surface treatment: hot galvanised

Electrical characteristics of the switchboard


b
b
b
b
b

Communication architectures

DD382917

DD382918

Different levels of intelligence are available


depending on the communication
architecture.

DD382919

Voltage measurement on contactor supply.

Rated insulation voltage of the main busbars: 1000 V


rated operational current of the main busbars: In 3200 A
rated peak withstand current: Ipk 187 k
rated short-time current: Icw 85 kA rms/1 s
frequency: 50/60 Hz.

Bus + Tesys U controller


The PLC is connected by a BUS to the various feeders
via Tesys U controllers. These remotely-adjustable
digital relays provide not only thermal protection for the
motor, but also communication with the supervisor
managing the entire installation. They allow:
b transmission of information on feeder status (open,
closed)
b transmission of measurement data (power
consumption, etc.)
b transmission of data on the types of faults detected,
e.g. motor temperature rise or insulation faults.
Bus + "input/output" module
The PLC is connected by a BUS to the various
functional units via input/output modules (OTB). This
system simplifies wiring compared to a point-to-point
solution.

Point-to-point wiring
The various devices (circuit breaker, contactor, thermal
relay) are equipped with auxiliaries connected to the
terminal block on the functional unit. The latter is
connected point-to-point to the input/outputs of a
remote PLC. Each instruction requires a separate wire.

General presentation

Motor Control Centers

Prisma Plus
disconnectable-type
switchboards
Presentation

Motor-feeder solutions
PD391101

Solution with one component

Solution with one component.

This solution involves a Tesys U motor starter-controller that combines in a single


product all the basic functions for a motor feeder:
b disconnection and protection against short-circuits (circuit breaker)
b protection against overloads (thermal relay)
b control (contactor).
It can be equipped with a communication module for dialogue with a PLC, a
supervisor, etc.
It can be used to build low to mid-power motor feeders (up to 15 kW) with optimised
dimensions and guarantees continuity of service (total coordination).

PD391102

Solution with three components

Solution with three components.

Types of coordination

Three separate devices are combined in this solution:


b a magnetic circuit breaker or a switch-disconnector fuse offering disconnection,
interruption and protection against short-circuits
b a thermal protection relay for overload protection
b a contactor for switching.
It can be used for different types of motor feeders, whatever the degree of complexity
or their specificity. The separation between functions provides great flexibility in
selecting components. It also provides a way of meeting certain installation and
operating constraints.
The three-component solution also makes for particularly easy maintenance. When
combined with a Tesys U LUTM controller, it is compatible with all motor-feeder
management solutions.
b measurements
b communication: information on faults, operation counters, feeder status
b upgradeability.

Type 1 coordination
The basic solution.
It is used when continuity of service is not a major concern.
The cost of the devices is reduced to the strict minimum.
Before restarting, it may be necessary to repair the motor feeder. The contactor and
the thermal relay may be destroyed by an electrical fault, in spite of the circuit
breaker.
Consequences:
b machine shutdown times that are not negligible
b need for qualified maintenance personnel to repair, check and repurchase.
Example of an application: air-conditioning on commercial premises

Type 2 coordination
Ensuring continuity of service.
The contactor and the thermal relay cannot be destroyed by an electrical fault. The
contactor may have welded contacts, but they can be freed.
Consequences:
b reduced machine shutdown times
b simple operation.

Total coordination
When no damage or resetting of devices is acceptable following an electrical
fault.
Consequences:
b immediate return to operation
b no particular precautions required.

Examples of switchboard
configurations
Switchboards combining distribution
and motor-control functions

General presentation
Prisma Plus
disconnectable-type
switchboards

Incomer (cubicle 1)
Masterpact NT 3P
Drawout
Incoming cables via bottom

DD382992

Presentation

Distribution
Horizontal flat busbars, 10 mm thick
Rear, vertical busbars, connection via clamps

Disconnectable outgoing devices (cubicle 2)


Electrical distribution
NS250 3P
Motor controller
1 device (Tesys "U")
3 devices (GV2, NS80)

Enclosure
Cubicle 1 (incomer)

W = 400 mm
D = 600 mm
Cubicle 2 (disconnectable W = 650 mm
mounting plates)
D = 600 mm
Cubicle for connections
W = 400 mm
D = 600 mm

DD382993

Optimum switchboard dimensions thanks to the variety of frameworks.

10

Examples of switchboard
configurations
Switchboards combining distribution
and motor-control functions

General presentation
Prisma Plus
disconnectable-type
switchboards

Incomer (cubicle 1)
Masterpact NW20 4P
Drawout
Supply via Canalis

DD382990

Presentation

Distribution
Linergy vertical busbars
Horizontal flat busbars, 10 mm thick
Rear, vertical busbars, connection via clamps

Fixed outgoing devices (cubicle 1)


Electrical distribution
NS250 4P

Disconnectable outgoing devices (cubicle 2)


Electrical distribution
NS250 3P
Motor controller
1 device (Tesys "U")
3 devices (GV2, NS80)

Enclosure

O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF
O-OFF

Cubicle 1 (incomer)

W = 800 mm
D = 600 mm
Cubicle 2 (disconnectable W = 650 mm
mounting plates)
D = 600 mm
Cubicle for connections
W = 400 mm
D = 600 mm

DD382991

Linergy vertical busbars and rear busbars with clamp connections are compatible.

11

General presentation

Examples of switchboard
configurations
Switchboards combining distribution
and motor-control functions

Prisma Plus
disconnectable-type
switchboards

Incomer (cubicle 1)
Masterpact NW16 4P
Drawout
Incoming cables via bottom

Distribution
Horizontal flat busbars, 10 mm thick
Rear, vertical busbars, connection via clamps

Disconnectable outgoing devices (cubicle 2)


Electrical distribution
NS630 with toggle, 4P
NS630 with motor mechanism, 4P
NS250 with toggle, 4P
Multi 9

Disconnectable outgoing devices (cubicle 3)


Electrical distribution
NS250 3P
Motor controller
1 device (Tesys "U")
3 devices (GV2 + LC2D09 + LUTM)
3 devices (NS80 + LC1D80 + LUTM)
3 devices (NS80 + LC2D80 + LUTM)

Enclosure
Device cubicle 1

W = 650 mm
D = 600 mm
Device cubicle 2 (fixed
W = 650 mm
devices)
D = 600 mm
Device cubicle 3
W = 650 mm
(disconnectable mounting D = 600 mm
plates)
Cubicles for connections W = 400 mm
D = 600 mm

12

PD391162

Presentation

General presentation

Examples of switchboard
configurations
Switchboards combining distribution
and motor-control functions

Prisma Plus
disconnectable-type
switchboards

Incomer (cubicle 1)
NS1250 4P
Fixed
Supply via Canalis

PD391163

Presentation

Distribution
Horizontal flat busbars, 10 mm thick
Rear, vertical busbars, connection via clamps

Fixed outgoing devices (cubicle 2)


Electrical distribution
NS630 with toggle, 4P
NS630 with motor mechanism, 4P
NS250 with toggle, 4P
NS250 with motor mechanism, 4P

Disconnectable outgoing devices (cubicle 3)


Electrical distribution
NS250 3P
Motor controller
1 device (Tesys "U")
3 devices (GV2 + LC2D09 + LUTM)
3 devices (NS80 + LC1D80 + LUTM)
3 devices (NS80 + LC2D80 + LUTM)

W = 800 mm
D = 600 mm
Device cubicle 2 (fixed
W = 650 mm
devices)
D = 600 mm
Device cubicle 3
W = 650 mm
(disconnectable mounting D = 600 mm
plates)
Cubicles for connections W = 300 and 400 mm
D = 600 mm

PD391169

Enclosure
Device cubicle 1

13

Presentation of disconnectable
mounting plates

General presentation
Prisma Plus
disconnectable-type
switchboards

The disconnectable mounting plates can be


installed in a cubicle 650 mm wide and
600 mm deep. They are compatible with all
standard Prisma Plus cubicles.
Connections are made from the front. The
cables are run in dedicated side
compartments (W = 300 mm or 400 mm).

modular disconnectable
mounting plates
from 1 to 6 modules (50 mm)
high

The unit of height for disconnectable


mounting plates is the 50 mm module.

PD390689

Functional unit

PD391102

Presentation

PD390690

.... with a fixed and a moving part

PD390700

Connection of both distribution and motorcontrol disconnectable mounting plates to the


same busbars.

Fixed part supplied with "double-contact"


clamps.

Cubicle capacity is 30 modules, each


50 mm high.

PD391124

... installed in a cubicle 650 mm


wide and 600 mm deep

Adjacent cubicles (W = 300 mm or 400 mm)


are used for cable running.

14

Moving part for the device, supplied with


security switch.

Presentation of disconnectable
mounting plates

General presentation
Prisma Plus
disconnectable-type
switchboards

PD390691

... connected directly to insulated


busbars via clamps

PD390696

Presentation

Double-contact clamps installed on the


fixed part of the disconnectable
mounting plates.
Instantaneous and reliable connection.
No busbar wear when the moving part is
disconnected.

The LCDD unit indicates feeder status


and signals any operating faults
(thermal, overload, etc.).
It is an integral part of the functional unit.
It is used for local control of the feeder,
for example to test the settings see
page 33.

PD390698

... controlled locally or remotely

Auxiliary connection block on the


disconnectable mounting plates.

LCDD unit mounted on its support.

PD391098

Compact switchboard
The small size of the disconnectable
mounting plates, made possible by the
rigorous layout of devices, ensures
optimum cubicle filling.
Easy installation
Front access.
Direct electrical connections via clamps.
Switchboard upgradeability
Addition or replacement of a feeder can
be carried out quickly and easily, at any
time.

Every detail of device layout on the


disconnectable mounting plates has been
carefully thought out.

Continuity of service in the


installation
Servicing under energised conditions by
qualified personnel
Total safety for personnel
Fully insulated busbars.
Tested components.

PD390697

... with a number of advantages

Servicing is possible at all times and in


complete safety.

15

Cubicle with disconnectable


mounting plates

General presentation
Prisma Plus
disconnectable-type
switchboards

Based on the electrical diagram


b protection degree: IP30
b external temprature: 40 C
b voltage: 415 V.

DD382989

Presentation

DD382772

b 6 x 5.5 kW feeders
(Tesys U):
v direct
v bus + communication
module
v with LCDD

Device selection

P (kW) maxi

5,5

Disconnectable mountingplate selection

DD382995

see page 20

DD382994

Install the 1-component motor-control feeders


I (A)

Device selection

11

For switchboard
IP30 y 40
Base
+
Protection
LUB-12BL
LUCp 1 2BL

Installation

Device

Diagram number

DD382996

DOL (non-reversing)
LUB-12/32BL (base)
+ LUCpppBL (protection)

No. of 50 mm
modules

Mounting plate
fixed
moving
part
part

88050

Diagram no.
with LCDD
Bus + communication module
DOL
111
Reversing
113

88030

Type of diagram

see page 48
see page 52

Device selection

P max

Disconnectable mountingplate selection

Circuit breaker + Contactor

(kW)

18,5
22

DD382998

DD382773

b 4 x 22 kW feeders:
v direct
v bus + Tesys U
controller
v with LCDD

DD382997

Install the 3-component motor-control feeders (circuit breaker)


see page 22

+ Thermal protection

Degree of protection/exter. temp.


IP30 40 C IP55 40 C
IP30 50 C
LC

LC

NS80HMA
NS80HMA

Circuit breaker-contactor
combination

Tesys U controller
controller + current
transformers
(2)
LUTC0501
(2)
LUTC0501

Control architecture

Installation

Bus + Tesys U controller

Mounting plate
No. of
modules Fixed
Moving
(50 mm) part
part

DOL (non-reversing)

Diagram number

DD382999

NS80HMA + LC1-D50 D80 +.


NS80HMA + LC1-D115 + ..

Device
(protection)
Bus + Tesys U controller
NS80HMA

3
4

88053
88054

Type of diagram

Diagram no.

Dol
Reversing

171
173

88033
88034

see page 18 and see page 19


DD382774

b 2 x 250 A feeders
b 5 C60 feeders

Selection of
disconnectable mounting
plates for NS250

DD383000

Install the electrical-distribution feeders


Device

No. of
50 mm
modules

fixed
part

moving
part

Terminal shields
upstream (short
downstream (long
terminal shields) terminal shields)

88010
88011

88020
88021

29321
29322

29323
29324

Mounting plates +
fixed
moving
part
part

Modular rail
fixed

Disconnectable
mounting plates

Compact NS100/630

Selection of
disconnectable mounting
plates for C60

DD383001

NS100/250 3P
4P

Device

2,5
3

No. of
50 mm
modules

Multi 9 devices y 40 A, supply via comb busbars or 80 A Multiclip


Multi 9 device

16

88053

88033

03001

Cubicle with disconnectable


mounting plates

General presentation
Prisma Plus
disconnectable-type
switchboards
Presentation

Calculate the number of cubicles


required to install the feeders
b count the number of occupied modules

26 modules

b calculate the number of cubicles


(capacity of one cubicle is 30 modules)

1 cubicle

Busbar calculation

Select the catalogue


numbers
b cover
b flat busbars,
L = 2000 mm
b busbar supports
b connection between
horizontal and vertical
busbars

Permissible current for switchboards

IPy 31

Selection of vertical
busbars

Number of
bars/phase

Number of supports
for Icw (kA rms/1 s)

50
1200

IP > 31
1050

70

85

1 bar, 50 x 10 mm

1750

1530

1 bar, 80 x 10 mm

2100

1840

1 bar, 100 x 10 mm

DD383003

DD382821

Busbar calculation
Calculate the number of
busbars and supports.

Cat. no. selection


Designation

Cat. no.

Rear busbar cover for cubicle D=600mm

88002

DD383004

see page 38

DD383002

Plan the distribution system

Flat busbars, L = 2000 mm

Cat. no.

Designation
Copper bar without holes, 50 x 10 mm, L=2000mm
Copper bar without holes, 80 x 10 mm, L=2000mm
Copper bar without holes, 100 x 10 mm, L=2000mm

04545
04548
04550

Busbar supports
Cat. no.

Designation

88005
88006
88006

1 support for 50 x 10 mm bars


1 support for 80 x 10 mm bars
1 support for 100 x 10 mm bars

Connection between horizontal and vertical busbars Cat. no.


For busbars y 1600 A
For busbars > 1600 A

88004 + 04636
88004 + 04637

Door selection

Rear-panel selection

Roof selection

Gland plate selection

Framework, D = 600 mm

Cat. no.

W = 300 mm
W = 400 mm
W = 650 mm

08603
08604
08606

Door

IP30

IP55

08536

08546

DD383006

Selection of framework
and cover panels.

Transparent door

DD383007

Framework selection

IP30

IP55

W = 300 mm

08733

08743

W = 400 mm

08734

08744

W = 650 mm

08736

08746

DD383008

DD383009

DD382822

see page 42

DD383005

Select the enclosure

L = 650 mm

Rear panel

Plain roof
D = 600 mm

IP30

IP55

W = 300 mm
W = 400 mm
W = 650 mm

08633
08634
08636

08653
08654
08656

IP30

IP55

W = 300 mm
W = 400 mm
W = 650 mm

08693
08694
08696

08683
08684
08686

Gland plates
D = 600 mm

17

Compact NS 100/630
Toggle, rotary handle, motor
mechanism

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Device installation
PD391099

Device

No. of
Disconnectable Terminal shields
Safety trip for
50 mm
mounting plates
advanced opening
modules fixed
moving upstream
downstream
(1)
part
part
(short terminal (long terminal
shields)
shields)

Compact NS100/630
NS100/250 3P
4P
NS400/630 3P
4P

Note: for measurements, the current transformers are installed


in the cable compartment.

2, 5
3
3, 5
4

88010
88011
88012
88013

88020
88021
88022
88023

29321
29322
32562
32563

29323
29324
32564
32565

29270
29270
32520
32520

Vigicompact NS100/630
2, 5
88010 88020 29321
29323
29270
3
88011 88021 29322
29324
29270
Earth-leakage protection is provided by an external Vigirex type device with a
toroid installed in the cable compartment.
(1) Available capacity: 30 modules.
DD382687

NS100/250 3P
4P
NS400/630

Connection

To connect the Compact NS400/630 using cables with large cross-sectional areas
(up to 300 mm), use of the terminals below is recommended.
Terminals for copper and aluminium cables
For 1 cable from 35 to 300 mm

DD383018

DD383017

For 2 cables from 85 to 240 mm

32480.

18

Set of 3
Set of 4
Set of 3
Set of 4

32482.

32479
32480
32481
32482

Multi 9 devices

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Device installation
PD391161

Device

No. of
Mounting plates + Modular rail
50 mm
fixed
moving fixed
or
modules (1) part
part

adjustable or rear
mounted

Multi 9 devices y 40 A, supply via comb busbars or 80 A Multiclip


88033

03001

03002

03004

DD382688

Multi 9 device
3
88053
(1) Available capacity: 30 modules.

Modular rail: see catalogue Prisma Plus.

Distribution accessories
see catalogue Prisma Plus
see catalogue Prisma Plus

DD380820

DD380817

Multiclip distribution block 80 A


Comb busbars

80 A Multiclip distribution block.

Comb busbars.

19

Functional units
Prisma Plus
disconnectable-type
switchboards

1-component motor feeder


415 V Tesys U circuit breakercontactor combination

Catalogue numbers

PD391101

Presentation

The Tesys U offer combines three functions in a single device:


b protection against short-circuits (circuit breaker)
b control (contactor)
b protection against overloads (thermal relay).
It can be equipped with a communication module for continuous dialogue with the
installation.
It is used for simple motor feeders up to 32 A, which represent 85% of the total.

Advantages
b easy installation:
v easy to order: 1 base + 1 protection device
v easy to install: only one device must be wired, reduced installation times
v easy to set: locally via the LCD and keypad built into the control unit or remotely
v compact: the functional unit occupies little space in the switchboard (one 50 mm
module for disconnectable mounting plates)
b continuity of service:
v total coordination between protection devices
v protection functions modified by simply changing the control unit
v manual or automatic reset following a thermal fault
b upgradeable: modular design. Functional modules (communication and
protection) can be easily changed at all times without having to rewire the entire
assembly.

Applications
v Manufacturing and continuous and semi-continuous processes.

Selection of the Tesys U device


DD382694

P (kW) max. I max (A)

0.09
0.37
1.5
5.5
7.5
11
15

0.36
1
3.5
11
14.8
21
28.5

Device selection
For
switchboard

IP31 y 40

For
switchboard

Base +
LUB-12BL
LUB-12BL
LUB-12BL
LUB-12BL
LUB-32BL
LUB-32BL
LUB-32BL

Protection
LUCpX6BL
LUCp1XBL
LUCp05BL
LUCp12BL
LUCp18BL
LUCp32BL
LUCp32BL

Base +
LUB-12BL
LUB-12BL
LUB-12BL
LUB-12BL
LUB-32BL
LUB-32BL

IP55 y 45
IP31 y 50
Protection
LUCpX6BL
LUCp1XBL
LUCp05BL
LUCp12BL
LUCp18BL
LUCp32BL

z M: multifunction control unit


B: class 10 control unit for three-phase motor
C: class 10 control unit for single-phase motor
D: class 20 control unit for three-phase motor.
Note: Device catalogue numbers correspond to a 24 V DC control voltage. For other control
voltages, see the Telemecanique catalogue.

Selection of the disconnectable


mounting plate
DD382695

Device

DOL (non-reversing)
LUB-12/32BL (base)
+ LUCpppBL (protection)
Reversing
LUB-12/32BL (base)
+ LUCpppBL (protection)
+ LU2MB0BL (reversing block)
+ LU9MR1C (prewiring connector)
+ LU9M1 (plug-in terminal blocks)
(1) Available capacity: 30 modules.

20

Installation
Possible
installation of a
LUALB1 limiter

No. of 50 mm
modules (1)

Mounting plate
fixed part moving
part

yes

88050

88030

yes

88050

88030

Functional units
Prisma Plus
disconnectable-type
switchboards

1-component motor feeder


415 V Tesys U circuit breakercontactor combination

Catalogue numbers

DD382921

PD391112

Determining the diagram number

Architecture
Type of diagram
(control)
Bus + communication module
DOL
Reversing

The table below can be used to determine the number of the diagram corresponding
to a desired application, taking into account the following variables:
b control architecture (bus with communication module, bus + "input/output" module,
point-to-point wiring)
b type of diagram: DOL (non-reversing) or reversing
b with or without LCDD (local control and display device)
For each diagram number (e.g. 110), there is a list of products to be ordered.

Diagram no.
without LCDD
110
see page 46
112
see page 50

with LCDD
111
113

see page 48
see page 52

Communication module (1)


Type

Catalogue number

Modbus

LUL C032

(1) The offer will be expanded with other communication modules (Profibus, Ethernet, Devicenet)
in 2005.

Bus + "input/output" module


DD382918

This solution cannot be used as is with Tesys U.


An approximation (in terms of the reduction in wiring time) is possible using the
Parallel or AS-I communication module.
)Communication

module (1)

Type

Catalogue number

Parallel

LUL C00

AS-I

ASILUF C5

(1) The offer will be filled out with other communication modules (Profibus, Ethernet, Devicenet)
in 2005.

DD382917

Point-to-point wiring
DOL
Reversing

without LCDD
310
see page 102
312
see page 106

with LCDD
311
313

see page 104


see page 108

21

3-component motor feeder


Magnetic circuit breaker
+ contactor + thermal protection
415 V

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Presentation

Advantages

PD391102

b
b
b
b
b

wide choice of solutions


suitable for all types of diagrams
manual or automatic reset following a thermal fault
2 starting classes (10 and 20)
type 2 coordination

Advantages of magnetic circuit breakers over fuses:


v universal solution that can be exported to all countries
v reduced dimensions
v limited temperature rise
v faster maintenance
v reliability of the tripping curve.

Applications
Manufacturing and continuous and semi-continuous and processes.

Selection of device combinations


DD382696

The table below can be used to select the circuit breaker + contactor + thermal
protection combination as a function of the:
b the power rating of the motor
b the switchboard degree of protection
b the ambient temperature around the switchboard.
Example (C):
b motor: 22 kW, switchboard Icw: 70 kA rms/1 s
b switchboard degree of protection IP30
b ambient temperature around the switchboard: 40C
b thermal protection with Tesys U controller
Order:
1 NS80HMA circuit breaker
1 LCz-D80 contactor
1 Tesys U controller + 3 LUTC0501 current transformers.
P max I max Icw max
(kW)

(A)

Circuit
breaker

+ Contactor

0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15

1
1.5
2
2.5
3.5
5
6.5
8.4
11
14.8
18.1
21
28.5

(kA rms/1 s)
without
limiter
limiter
LA9LB920
130
130
130
130
130
130
130
130
130
50
130
50
130
50
130
50
130

18.5
22
30

35
42
57

70
70
70

NS80HMA
NS80HMA
NS80HMA

LCz-D50
LCz-D50
LCz-D65

37

69

70

NS80HMA

LCz-D80

+ Thermal protection

GV2-L05
GV2-L06
GV2-L07
GV2-L08
GV2-L08
GV2-L10
GV2-L14
GV2-L14
GV2-L16
GV2-L20
GV2-L22
GV2-L22
GV2-L32

Degree of protection/external temp.


IP31 y 40C IP55 y 40C IP55 y 45C
IP31 y 50C
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
LCz-D18
V
LCz-D18
V
LCz-D25
V
LCz-D25
V
LCz-D32
V
LCz-D40
V
LCz-D40
LCz-D50
V
V
LCz-D65
LCz-D80

V
LCz-D115

LCz-D115
18.5
22

35
42

70
70

NS80HMA
NS80HMA

NS80HMA
30
57
70
NS80HMA
37
69
70
(1)For point-to-point wiring or bus + "input/output" modules
(2) LUTM10BL (base) + LUCzT1BL (control unit) +
LULC032 (Modbus communication module).
(3) Current transformer Szz-75
(4) Current transformer Szz-100
zz 11: 3CT mounting, short start
12: 3CT mounting, long start
13: 2CT mounting, short start
14 : 2CT mounting, long start.

22

LCz-D80
LCz-D80

V
V

LCz-D80
LCz-D115
V
LCz-D80
LCz-D115 V
z 1: DOL (non-reversing)
star delta, Dalhander, 2 speed
2 : Reversing.

Relay
(thermal)

or
(1)

LRD-05
LRD-06
LRD-07
LRD-08
LRD-08
LRD-10
LRD-12
LRD-14
LRD-16
LRD-21
LRD-22
LRD-3322
LRD-3353

Tesys U controller
controller + current
transformers

(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)

16451
16451
16452
16452
LUTC0301
LUTC0301
LUTC0301
LUTC0301
LUTC0301

(2)
(2)

LUTC0501
LUTC0501

(2)
(2)

LUTC1001
LUTC1001

LRD-3355
LRD-3357
LRD-3359
LRD-05 + LAD7B10 + (3)
LRD-3363
LRD-05 + LAD7B10 + (4)

3-component motor feeder


Magnetic circuit breaker
+ contactor + thermal protection
415 V

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Dd383013

Selection of the disconnectable


mounting plate

v For a combination of devices (circuit breaker + contactor) indicated above, the


table below indicates the catalogue number of a disconnectable mounting plate (fixed
and moving parts) and the height occupied in the switchboard.
Selection takes into account the following parameters:
b the type of diagram (DOL, reversing, 2 speed, star delta, Dalhander)
b the presence or absence of a LA9LB920 limiter
b the control architecture
v point-to-point wiring
v bus + "input/output" module
v bus + Tesys U controller.
Example (C) (cont.):
b circuit-breaker combination: NS80HMA + contactor LC2-D80
b type of diagram: reversing
b control architecture: bus + Tesys U controller
Order disconnectable mounting plate 88054 (fixed part) + 88034 (moving part).
It occupies four 50 mm vertical modules.

Limiter
LA9LB920

Point-to-point

Bus+modules
(input/output)

DD382701

Installation
DD382700

Control architecture
DD382699

Circuit breaker-contactor combination

Bus + Tesys U
controller

No. of
modules
(50 mm)

DD382704

DD382703

DD382702

(1)

DOL (non-reversing)
GV2-L + LC1-D09 to D32

GV2-L + LC1-D40 to D50


NS80HMA + LC1-D50 to D65
NS80HMA + LC1-D80
NS80HMA + LC1-D115
Reversing
GV2-L + LC2-D09 to D32
GV2-L + LC2-D40 to D50
NS80HMA + LC2-D50 to D65
NS80HMA + LC2-D80
NS80HMA + LC2-D115
2 speed
GV2-L + 2LC1-D09 to D32
p
p

GV2-L + 2LC1-D40 to D50


NS80HMA + 2LC1-D50 to D65
NS80HMA + 2LC1-D80 to D115
Star delta
GV2-L + 3LC1-D09 to D32
GV2-L + 3LC1-D40 to D50
NS80HMA + 3LC1-D50 to D65
NS80HMA + 3LC1-D80
Dalhander
GV2-L + 3LC1-D09 to D32
GV2-L + 3LC1-D40 to D50
NS80HMA + 3LC1-D50 to D65
NS80HMA + 3LC1-D80

p
p
p

Mounting plate
Fixed Moving
part
part

1.5
2
3
3
3
3
4

88051
88052
88053
88053
88053
88053
88054

88031
88032
88033
88033
88033
88033
88034

2
3
4
4
4
6

88052
88053
88054
88054
88054
88055

88032
88033
88034
88034
88034
88035

2
3
4
4
4
6

88052
88053
88054
88054
88054
88055

88032
88033
88034
88034
88034
88035

4
6
6
6

88054
88055
88055
88055

88034
88035
88035
88035

4
6
6
6

88054
88055
88055
88055

88034
88035
88035
88035

(1) Available capacity: 30 modules.


with or without limiter
without limiter
with limiter

Possible combination.

p not available.

23

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

PD391111

Determining the diagram number

3-component motor feeder


Magnetic circuit breaker
+ contactor + thermal protection
415 V
The table below can be used to determine the number of the diagram corresponding
to a desired application, taking into account the following variables:
b control architecture (bus with Tesys U controller, bus + "input/output" modules,
point-to-point wiring)
b protection device: GV2 or NS80HMA
b type of diagram: DOL (non reversing), reversing, 2 speed, star delta, Dalhander.
b with or without LCDD (Local Control x Display Device)
For each diagram number (e.g. 173), there is a list of products to be ordered.
Example (C) (cont.):
b control architecture: bus + Tesys U controller
b NS80HMA protection device
b type of diagram: reversing
Diagram no.: 173.

DD382919

Architecture
Device
(control)
(protection)
Bus + Tesys U controller
GV2

NS80HMA

DD382918

Bus + "input/output" module


GV2

NS80HMA

Type of diagram

Diagram no.

Page

DOL
Reversing
2 speed
Star delta
Dalhander
DOL
Reversing
2 speed
Star delta
Dalhander

121
123
125
127
129
171
173
175
177
179

see page 54
see page 56
Not yet available
see page 58
Not yet available
see page 66
see page 68
Not yet available
see page 70
Not yet available

DOL
Reversing
2 speed
Star delta
Dalhander
DOL
Reversing
2 speed
Star delta
Dalhander

221
223
225
227
229
271
273
275
277
279

see page 72
see page 74
see page 76
see page 78
see page 80
see page 92
see page 94
see page 96
see page 98
see page 100

DOL
Reversing
2 speed
Star delta
Dalhander
DOL
Reversing
2 speed
Star delta
Dalhander

321
323
325
327
329
371
373
375
377
379

see page 110


see page 112
see page 114
see page 116
see page 118
see page 130
see page 132
see page 134
see page 136
see page 138

Point-to-point wiring
DD382917

GV2

NS80HMA

24

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

3-component motor feeder


Magnetic circuit breaker
+ contactor + thermal protection
415 V

Example of a diagram page (see page 68)

25

3-component motor feeder


Switch-disconnector fuse
+ contactor + thermal protection
415 V

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Presentation

Advantages
b
b
b
b
b

wide choice of solutions


suitable for all types of diagrams
manual or automatic reset following a thermal fault
2 starting classes (10 and 20)
type 2 coordination.

Applications
b all types of machines
b Manufacturing and continuous and semi-continuous processes.

Selection of device combinations


DD382705

The table below can be used to select the fuse + contactor + thermal protection
combination as a function of the:
b the power rating of the motor
b the switchboard degree of protection
b the ambient temperature around the switchboard.
Example (C):
b motor: 22 kW
b switchboard degree of protection IP30
b ambient temperature around the switchboard: 50C
b thermal protection with Tesys U controller.
Order:
1 GS1-J 50 A switch disconnector fuse
1 LCz-D80 contactor
1 Tesys U controller + 3 LUTC0501 current transformers.
P max I max Icw max

Sw/
Fuse
Disc.

+ Contactor

+ Thermal protection

(kW)

(A)

(kA rms/s)

0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11

1
1.5
2
2.5
3.5
5
6.5
8.4
11
14.8
18.1
21

110
110
110
110
110
110
110
110
110
110
110
110

GS1-F
GS1-F
GS1-F
GS1-F
GS1-F
GS1-F
GS1-F
GS1-F
GS1-F
GS1-F
GS1-F
GS1-F

14 x 51
14 x 51
14 x 51
14 x 51
14 x 51
14 x 51
14 x 51
14 x 51
14 x 51
14 x 51
14 x 51
14 x 51

2A
2A
4A
4A
4A
6A
8A
10 A
16 A
16 A
25 A
25 A

Degree of protection/external temp.


IP31 y 40C IP55 y 40C IP55 y 45C
IP31 y 50C
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
V
LCz-D09
LCz-D18
V
LCz-D18
V
LCz-D25
V
LCz-D25
V
LCz-D40
V
LCz-D40
V

15
18.5
22
30

28.5
35
42
57

110
110
110
110

GS1-F
GS1-F
GS1-J
GS1-J

14 x 51
14 x 51
22 x 58
22 x 58

32 A
40 A
50 A
80 A

LCz-D40
LCz-D50
LCz-D50
LCz-D65

37

69

110

GS1-J 22 x 58 100 A

V
V
LCz-D65
LCz-D80

LCz-D50
LCz-D65
V
LCz-D115

LCz-D80
LCz-D115

15
28.5
110
GS1-F 14 x 51 32 A
18.5
35
110
GS1-F 14 x 51 40 A
22
42
110
GS1-J 22 x 58 50 A
30
57
110
GS1-J 22 x 58 80 A
37
69
110
GS1-J 22 x 58 100 A
(1)For point-to-point wiring or bus + "input/output"
modules.
(2) LUTM10BL (base) + LUCzT1BL (control unit) +
LULC032 (Modbus communication module).
(3) Current transformer Szz-75
(4) Current transformer Szz-100
zz 11: 3CT mounting, short start
12 : 3CT mounting, long start
13 : 2CT mounting, short start
14 : 2CT mounting, long start.

26

LCz-D80
V
LCz-D80
V
LCz-D80
V
LCz-D80
LCz-D115
V
LCz-D80
LCz-D115
V
z 1: DOL (non reversing),
star delta, Dalhander, 2 speed.
2 :Reversing

Relay
(thermal) (1)
LRD-06
LRD-06
LRD-07
LRD-08
LRD-08
LRD-10
LRD-12
LRD-14
LRD-16
LRD-21
LRD-3322
LRD-3322

or Tesys U controller
controller + current
transformers

(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)

16451
16451
16452
16452
LUTC0301
LUTC0301
LUTC0301
LUTC0301

(2)
(2)
(2)
(2)
(2)

LUTC0301
LUTC0501
LUTC0501
LUTC1001
LUTC1001

LRD-3353
LRD-3355
LRD-3357
LRD-3361
LRD-05 + LAD7B10 + (3)
LRD-3363
LRD-05 + LAD7B10 + (4)

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

DD382850

Mounting-plate selection

3-component motor feeder


Switch-disconnector fuse
+ contactor + thermal protection
415 V
For a combination of devices (fuse + contactor) indicated above,
the table below indicates the catalogue number of a disconnectable mounting plate
(fixed and moving parts) and the height occupied in the switchboard.
Selection takes into account the following parameters:
b the type of diagram (DOL, reversing, 2 speed, star delta, Dalhander)
b the control architecture:
v point-to-point wiring
v bus + "input/output" module
v bus + Tesys U controller.
Example (C) (cont.):
b combination of GS1-J + LC2-D80
b type of diagram: reversing
b control architecture: bus + Tesys U controller
Order disconnectable mounting plate 88055 (fixed part) + 88035 (moving part).
It occupies six 50 mm vertical modules.

Point-to-point

Bus+modules
(input/output)

DD382710

Installation
DD382709

Control architecture
DD382708

Device combinations

Bus + Tesys U
controller

No. of
50 mm
modules
(1)

Mounting plate
Fixed
part

Moving
part

DD382711

DOL (non-reversing)
GS1-F + LC1-D09 to D80

88053

88033

GS1-J + LC1-D50 to D115

88055

88035

GS1-F + LC2-D09 to D25

88053

88033

GS1-F + LC2-D40 to D65

88054

88034

GS1-F + LC2-D80

88054

88034

GS1-J + LC2-D50 to D115

88055

88035

88053

88033

88054

88034

88054

88034

88055

88035

GS1-F + 2LC1-D80

88055

88035

GS1-J + 2LC1-D50 to D80

88055

88035

88055

88035

GS1-F + 3LC1-D09 to D25

88054

88034

GS1-F + 3LC1-D40 to D65

88055

88035

GS1-F + 3LC1-D80

88055

88035

GS1-J + 3LC1-D50 to D65

88055

88035

GS1-J + 3LC1-D80

88055

88035

DD382712

Reversing

2 speed
GS1-F + 2LC1-D09 to D25
p
GS1-F + 2LC1-D40 to D65

GS1-J + 2LC1-D115

DD382767

Star delta

Dalhander
GS1-F + 3LC1-D09 to D25

88054

88034

GS1-F + 3LC1-D40 to D65

88055

88035

GS1-F + 3LC1-D80

88055

88035

88055

88035

88055

88035

GS1-J + 3LC1-D50 to D65


GS1-J + 3LC1-D80

(1) Available capacity: 30 modules.


Possible combination.

p not available.

27

3-component motor feeder


Switch-disconnector fuse
+ contactor + thermal protection
415 V

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Determining the diagram number

The table below can be used to determine the number of the diagram corresponding
to a desired application, taking into account the following variables:
b control architecture (bus with Tesys U controller, bus + "input/output" modules,
point-to-point wiring)
b protection device: GS1
b type of diagram: DOL (non reversing), reversing, 2 speed, star delta, Dalhander.
b with or without LCDD (Local Control and Display Device)
For each diagram number (e.g. 153), there is a list of products
to be ordered.
Example (C) (cont.):
b control architecture: bus + Tesys U controller
b GS1 protection device
b type of diagram: reversing
Diagram no.: 153.

Device
(protection)

Type of diagram

Diagram no.

Page

GS1

DOL
Reversing
2 speed
Star delta
Dalhander

151
153
155
157
159

see page 60
see page 62
Not yet available
see page 64
Not yet available

GS1

DOL
Reversing
2 speed
Star delta
Dalhander

251
253
255
257
259

see page 82
see page 84
see page 86
see page 88
see page 90

GS1

DOL
Reversing
2 speed
Star delta
Dalhander

351
353
355
357
359

see page 120


see page 122
see page 124
see page 126
see page 128

DD382919

Architecture
(control)
Bus + Tesys U controller

DD382918

Bus + "input/output" module

DD382917

Point-to-point wiring

28

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

3-component motor feeder


Switch-disconnector fuse
+ contactor + thermal protection
415 V

Example of a diagram page (see page 62)

29

Functional units

Accessories

Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

PD390692

Selection table for auxiliary


connection blocks

Device combinations

DOL
TeSys U
GV2L + LC1-D09 to D32

GV2L + LC1-D40 to D50


NS80HMA + LC1-D50 to D65
NS80HMA + LC1-D80
NS80HMA + LC1-D115
GS1F + LC1D09 to D80
GS1J + LC1D50 to D115
Reversing
TeSys U
GV2L + LC2-D09 to D32

PD390693

Auxiliary connection block in the connection compartment.

Connection blocks
Limiter

GV2L + LC2-D40 to D50


NS80HMA + LC2-D50 to D65
NS80HMA + LC2-D80
NS80HMA + LC2 D115
GS1F + LC2-D09 to D25
GS1F + LC2-D40 D65
GS1F + LC2-D80
GS1J + LC2-D50 to D115
2 speed
GV2L + 2LC1-D09 to D32

GV2L + 2LC1-D40 to D50


NS80HMA + 2LC1-D50 to D65
NS80HMA + 2LC1-D80 to D115
GS1F + 2LC1-D09 to D25

with/without
without
without
with
with/without

with/without
without
with
with/without

without
with
with/without
with/without

GS1F + 2LC1-D40 to D65


GS1F + 2LC1-D80
GS1J + 2LC1-D50 to D80
GS1J + 2LC1-D115
Star delta
GV2L + 3LC1-D09 to D32

PD391121

Auxiliary connection block on the disconnectable mounting


plate.

Front connection in easily accessible compartments.

30

with/without

No. of
50 mm
modules

Control architecture

1
1.5
2
3
3
3
3
4
3
6

A
D

Point-topoint

Bus +
I/O mod.

D
D
D
D
C x2
D
C x2

A
A
A
A
A
A
A
C

1
2
3
4
4
4
6
3
4
4
6

A
A x2
B x2
C x2
C x2
C x2
C x2
B x2
C x2

A
A
C
C
C
C
A
C

C x2

2
3
4
4
4
6
3
4
4
6
6
6
6

A x2
B x2

A
A

C x2
C x2
C x2
B x2

C
C
C
A

C x2

C x2
C x2

C
C

C x2

Bus +
LUTM

A
A
A
A
A
A
C
A
A
A
A
C
C
A
C
C
C

GV2L + 3LC1-D40 to D50


with/without 6
C x2
C
C
NS80HMA + 3LC1-D50 to D65
6
C x2
C
NS80HMA + 3LC1-D80
6
C x2
C
C
GS1F + 3LC1-D09 to D25
4
C x2
A
A
GS1F + 3LC1-D40 to D65
6
C x2
C
C
GS1F + 3LC1-D80
6
C
GS1J + 3LC1-D50 D65
6
C x2
C
GS1J + 3LC1-D80
6
C x2
C
C
Dalhander
GV2L + 3LC1-D09 to D32
with/without 4
C x2
C
GV2L + 3LC1-D40 to D50
with/without 6
C x2
C
NS80HMA + 3LC1-D50 to D65
6
C x2
C
NS80HMA + 3LC1-D80
6
C x2
C
GS1F + 3LC1-D09 to D25
4
C x2
A
GS1F + 3LC1-D40 to D65
6
C x2
C
GS1F + 3LC1-D80
6
GS1J + 3LC1-D50 to D65
6
C x2
C
GS1J + 3LC1-D80
6
C x2
C
Component to be ordered
A Auxiliary connection block that clips to modular rail AB1DV(M)10235U.
B Auxiliary connection block that clips to modular rail AB1DV(M)10235U + Multi 9 raiser
(88066).
C Auxiliary connection block that screws to disconnectable mounting plate AB1BD101/102.
D Wieland auxiliary connection block.

Accessories

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Auxiliary connection blocks

A Clipped onto modular rail

ddd382690

Designation

Cat. no.

10
10

AB1DV10235U
AB1DVM10235U

DD382692

10-pole female connector (fixed part)


10-pole male plug-in connector (moving part)

Sold in set
quantities

C Screwed to disconnectable mounting plate


DD382689

Designation

Cat. no.

10
10

AB1BD101
AB1BD102

DD382691

10-pole male connector


10-pole female connector

Sold in set
quantities

D Wieland
Fixed part: WFK 1.5 E / 8113/35 type
Moving part: 8113 BFK type

Dd382980

Note: Not sold by Schneider Electric..

Multi 9 raiser
DD382722

Designation

Cat. no.
88066

DD382723

Multi 9 raiser, H = 50 mm

31

Accessories

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Grommets
DD382719

Designation
50 grommets, diameter 22mm

Cat. no.
87648

DD382720

For sheet metal 1 to 2.5 mm thick.

LCDD support
DD382713

Designation
LCDD support

Cat. no.
88063

DD382714

Material: galvanised steel sheet metal.

Micro-switch
DD382717

Designation

Cat. no.
87454

DD382718

10 micro-switches

Grease for electrical contacts


DD382693

Designation
1 kg of grease for electrical contacts

32

Cat. no.
87635

Functional units
Prisma Plus
disconnectable-type
switchboards

LCDD unit
Local control and display device

Catalogue numbers
Presentation
PD391103

Local-control and indication unit for a single motor feeder.


b LEDs indicate feeder status and signal any operating faults (thermal, overload,
etc.)
b a three-position switch can turn off PLC control for local control:
v for example, to test the settings of the feeders if the system is being expanded
v to carry out no-load tests following maintenance
v etc.
It is mounted on a bracket secured to the disconnectable mounting plate.
A removable, transparent cover is clipped to the front. It protects the labels and
enhances the design.
The unit is supplied with labels already marked on one side and blank on the other
to identify faults.
Note: can also be used for electrical-distribution feeders with Compact NS devices.

DD382725

Mechanical characteristics
LCDD

OFF T
RESE

0
L

TE

REMO

LOCA

b degree of protection:
Installation

IP (front)

IP (rear)

For door 0.8 to 1 mm thick


For door 1 to 1.3 mm thick
For door 1.4 to 2 mm thick

IP30
IP41
IP55

IP30
IP30
IP30

b impact strength: IK7


b operating temperature: 0 to 60 C
b Class 2 (front).

DD382724

Electrical characteristics
LCDD

OFF T
RESE

0
L

TE

REMO

LOCA

LCDD for reversing motor.

b rated insulation level: Ui = 250 V


b impulse withstand voltage: Uimp = 4 kV
b LED operational voltage: 24 V 15 %
b consumption at 24 V: 10 mA per LED + 10 mA for the KA1 relay
b Pushbutton rated operational characteristics:
v AC contactor control:
- 3 A up to 120 V AC
- 1.5 A up to 240 V AC
v DC contactor control:
- 1 A up to 30 V DC
The LCDD unit can control:
b the LC1D and F contactors, all sizes at 230 V AC
b contactors up to LC1D80/95 at 24 V DC.

Cat. no. selection


There are two models:
b for non-reversing feeder
b for reversing or 2-speed feeder.

Designation

Cat. no.

LCDD for non-reversing motor.


88400
LCDD for reversing or 2-speed motor
88401
Note: The switch and the pushbuttons are part of the Telemecanique "Harmonie" series.

33

LCDD unit
Local control and display device

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers
PD391109

Installation
The LCDD unit is very easy to install. It is mounted from the front on a bracket
secured to the disconnectable mounting plate, thus making wiring possible on a
table.
Designation

Cat. no.

LCDD support

88063

DD382726

PD390699

Material: galvanised steel sheet metal.

LCDD
OFF T
RESE

0
L

TE

REMO

LOCA

Installation on a disconnectable mounting


plate using a support.

Connection

DD382729

Connection to spring terminals on a plug-in terminal block


b 11 connection points for 0.25 to 1.5 mm cables for the LED circuit
b 8 connection points for 0.25 to 2.5 mm cables for the pushbutton circuit.

34

LCDD unit
Local control and display device

Functional units
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

DD382730

Wiring diagram

DD382731

LCDD for non-reversing motor (88400).

LCDD for reversing or 2-speed motor (88401).

DD382732

Dimensions

DD382733

88400/88401.

Door cut-out diagram.

35

Presentation of vertical busbars


with clamp connections

Distribution
Prisma Plus
disconnectable-type
switchboards

Prisma Plus electrical switchboards have a


complete and consistent distribution system
capable of supplying electrical energy
where it is needed.
b modern, high-performance busbars
b perfectly sized, prefabricated connections
b distribution blocks that blend perfectly
with the devices
b direct supply to feeders on
disconnectable mounting plates via clamps.
All components are put through rigorous
tests with Schneider Electric devices to
ensure that the resulting switchboards are
dependable and comply with international
standard IEC 60439-1.

PD391125

Catalogue numbers

PD391126

Rear vertical busbars with clamp connections.

PD391127

Rear view of an electrical-distribution disconnectable mounting plate


showing the double-contact clamps.

Rear view of a motor-protection disconnectable mounting plate


showing the double-contact clamps.

36

Distribution
Prisma Plus
disconnectable-type
switchboards

Presentation of vertical busbars


with clamp connections

PD391130

PD391128

Catalogue numbers

Connection of horizontal to rear vertical bars.


PD391131

PD391129

Installation of a motor-protection disconnectable mounting plate.

1-component motor feeder.

PD391132

Fully insulated horizontal and vertical busbars.

PD391133

Fixed part equipped with double-contact clamps.

NS400 disconnectable mounting plate for electrical distribution.

37

Selection of vertical busbars with


clamp connections

Distribution
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Calculation of busbars
Permissible current for
switchboards
IP y 31
IP > 31

Number of bars/phase

Number of supports
for Icw (kA rms/1 s)
50

1200

1050

70

85

1 bar, 50 x 10 mm

1750

1530

1 bar, 80 x 10 mm

2100

1840

1 bar, 100 x 10 mm

Note: The permissible current values for the busbars are given for an ambient temperature of
35C around the switchboard.

Selection of busbars

Busbar covers

PE391170

Presentation
Set made up of:
b 1 top plate
b 1 bottom plate with a stop to maintain the bars in position
b 2 side plates (1 left and 1 right) to which the bar supports are secured
b 1 rear plate
b 1 set of grills for the front
b 1 cover for the horizontal busbars.
Cat. no. selection
Designation

Cat. no.

Rear busbar cover for cubicle D=600mm

88002

Flat busbars, L = 2000 mm


Designation

Cat. no.

Copper bar without holes, 50 x 10 mm, L=2000mm


04545
Copper bar without holes, 80 x 10 mm, L=2000mm
04548
Copper bar without holes, 100 x 10 mm, L=2000mm
04550
Note: The lengths and drilling required on bars to enable connection with horizontal busbars are
indicated on diagram no. GHQ22364 or on the manual for the busbar cover.

Busbar supports
Designation

Cat. no.

Busbar covers.

38

88005
88006
88006
DD382735

DD382734

1 support for 50 x 10 mm bars


1 support for 80 x 10 mm bars
1 support for 100 x 10 mm bars

Bars and supports.

Selection of vertical busbars with


clamp connections

Distribution
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Connection with horizontal


busbars

Connection between horizontal and vertical busbars

PE391135

For horizontal busbars H = 50 or 80 mm


Vertical busbars y 1200 A
Vertical busbars > 1200 A
For horizontal busbars H = 100 mm
Vertical busbars y 1200 A

3P
4P
3P
4P

88007
88007
88004
88004

+ 04636 x 3
+ 04636 x 4
+ 04637 x 3
+ 04637 x 4

3P

88007
04642
88007
04642
88004
04642
88004
04642

+ 04636 x 3 +
x3
+ 04636 x 4 +
x4
+ 04637 x 3 +
x3
+ 04637 x 4 +
x4

4P
Vertical busbars > 1200 A

Catalogue number

3P

DD382737

4P

DD382770

DD382764

Busbar dimensions

Others Prisma Plus busbars


Designation
see catalogue Prisma Plus
see catalogue Prisma Plus
see catalogue Prisma Plus
see catalogue Prisma Plus
DD382739

DD382683

Horizontal flat busbars, 10 mm thick


Lateral Linergy busbars
Flat lateral busbars
PE and PEN conductors

Connection of Linergy vertical busbars to


horizontal busbars.

PEN conductor.

39

Presentation of enclosures

Enclosures
Prisma Plus
disconnectable-type
switchboards

Carefully designed in every detail, Prisma


Plus cubicles are the solution for all
common switchboard configurations up to
3200 A.
A reduced number of catalogue numbers
facilitates selection, while offering the
essential functions such as:
b multiple combination possibilities
b an array of interchangeable cover panels
and doors, IP30 or IP55, without adding
gaskets
b wide cable compartments
b total accessibility to all connection points
in the switchboard.
The discreet design, with simple lines and
oval shapes, mean Prisma Plus cubicles
blend in naturally on all commercial and
industrial sites.
The disconnectable mounting plates can be
installed in a cubicle 650 mm wide and
600 mm deep. They offer 30 modules, each
50 mm high, of useful space.
Prisma Plus enclosures comply with
standard EN 50298.

40

PD391110

Catalogue numbers

All cover panels and doors IP30 are secured using quarter-turn fasteners.
Electrical continuity is achieved naturally, without having to add clips or earthing braids.

Presentation of enclosures

Enclosures
Prisma Plus
disconnectable-type
switchboards

Enclosures
Frameworks

DD382740

Catalogue numbers

The disconnectable mounting plates can be installed in


frameworks 650 mm wide and 600 mm deep.
The cable compartments are made with frameworks
300 or 400 mm wide and 600 mm deep.
All the other 600 mm deep Prisma Plus frameworks are
compatible for side-by-side combinations.

Cover panels
Front panels
b 650 mm wide, they can be either:
v a plain door
v a transparent door
b 300 and 400 mm wide, they can be either:
v a plain door
v a door with a cut-out (for the LCDD front plate).
Rear panels
The rear panel can be made up of:
b two parts for IP30 panels
b one reinforced part for IP55 panels.
It can also be a plain door.
Side panels
A set of two panels is used.
Roof
For each size of framework, there is a plain roof.

Degree of protection

Frameworks can be combined side-by-side to create all switchboard configurations.

DD382741

Gland plates
They are mandatory, whatever the desired degree of
protection for the switchboard.
For each size of framework, there are plain gland plates
or two-part gland plates.
IP30 switchboard
Use:
b IP30 cover panels
b IP30 plain roof
b gland plates
IP31 switchboard
Use:
b IP30 cover panels
b IP30 plain roof
b IP31 sealing kit
b gland plates
IP55 switchboard
Use:
b IP55 cover panels
b IP55 plain roof
b IP55 plain gland plates
If frameworks are combined, use the IP55 sealing kit for
side-by-side combinations.

There are many solutions for framework cover panels and doors.

41

Selection of enclosures

Enclosures
Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Framework
DD382742

Framework, D = 600 mm

Cat. no.

W = 300 mm
W = 400 mm
W = 650 mm

08603
08604
08606

Supplied with a side-by-side combination kit (IP30).

Designation

Cat. no.
08717

DD382747

IP55 sealing kit for side-by-side combinations (1 kit per combination)

DD382749

DD382743

Doors
IP30

IP55

Plain door

Door
W = 300 mm
W = 400 mm
W = 650 mm

08513
08514
08516

08523
08524
08526

Transparent door

W = 650 mm

08536

08546

Door with cut-outs

W = 300 mm

08593

W = 400 mm

08594

Reversible for left or right-hand opening


Equipped with a handle and keylock (key 405). For other possibilities,
see catalogue Prisma Plus.

Rear panel
Rear panel

DD382744

IP30

IP55

W = 300 mm

08733

08743

W = 400 mm

08734

08744

W = 650 mm

08736

08746

Supplied with quarter-turn fasteners.

42

Enclosures

Selection of enclosures

Prisma Plus
disconnectable-type
switchboards
Catalogue numbers

Side panels
DD382745

Side panels
2 side panels, D = 600 mm

IP30

IP55

08760

08765

Supplied with quarter-turn fasteners.

Roof
DD382746

Plain roof
D = 600 mm

W = 300 mm
W = 400 mm
W = 650 mm

IP30

IP55

08633
08634
08636

08653
08654
08656

Supplied with quarter-turn fasteners for mounting on the framework.


Provided with markings for clear identification of cable-running zones, if necessary.

Accessories
Designation

Cat. no.

IP31 sealing kit

08711

Plinth, H = 100 mm
DD382747

The plinth is made up of two catalogue numbers:


b one catalogue number comprising four corner posts + two cross-pieces (front and
rear), that can be used in side-by-side combinations or stacked to form a plinth 200
mm high (maximum)
b one catalogue number comprising two side plates (D = 600 mm).
Each catalogue number is supplied with the necessary hardware.
Designation
Cat. no.
Plinth, H = 100 mm

W = 300 mm
W = 400 mm
W = 650 mm

08723 + 08721
08724 + 08721
08726 + 08721

Gland plates
DD382748

Gland plates
D = 600 mm

W = 300 mm
W = 400 mm
W = 650 mm

Installation accessories

See catalogue Prisma Plus.

Connection accessories

See catalogue Prisma Plus.

Dimensions

See catalogue Prisma Plus.

IP30
(in 2 parts)

IP55
(plain)

08693
08694
08696

08683
08684
08686

43

44

Contents
Prisma Plus
disconnectable-type
switchboards
Diagrams

Diagrams
Diagram No. 110
Diagram No. 111
Diagram No. 112
Diagram No. 113
Diagram No. 121
Diagram No. 123
Diagram No. 127
Diagram No. 151
Diagram No. 153
Diagram No. 157
Diagram No. 171
Diagram No. 173
Diagram No. 177
Diagram No. 221
Diagram No. 223
Diagram No. 225
Diagram No. 227
Diagram No. 229
Diagram No. 251
Diagram No. 253
Diagram No. 255
Diagram No. 257
Diagram No. 259
Diagram No. 271
Diagram No. 273
Diagram No. 275
Diagram No. 277
Diagram No. 279
Diagram No. 310
Diagram No. 311
Diagram No. 312
Diagram No. 313
Diagram No. 321
Diagram No. 323
Diagram No. 325
Diagram No. 327
Diagram No. 329
Diagram No. 351
Diagram No. 353
Diagram No. 355
Diagram No. 357
Diagram No. 359
Diagram No. 371
Diagram No. 373
Diagram No. 375
Diagram No. 377
Diagram No. 379

46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
126
128
130
132
134
136
138

45

Diagram

Diagram No. 110

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Bus + communication module

sch110

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

46

Diagram

Diagram No. 110

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Bus + communication module

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Modbus module
Prewired coil terminals
Tesys ext. handle
Control circuit breaker

Quantity
(1)
1
1
1
1
(1)*
1

Reference
LUALB1
LUBpp
LUCpppBL
LULC032
LU9BN11C
LU9AP20
GB2CD07

* : for drawers and fixed mounting plates.

DD382870

Example

Mounting plate H = 50 mm (1 module).

47

Diagram

Diagram No. 111

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Bus + communication module

sch111

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

48

Diagram

Diagram No. 111

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Bus + communication module

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Modbus module
Tesys ext. handle
Control circuit breaker
LCDD 1

Quantity
(1)
1
1
1
(1)*
1
1

Reference
LUALB1
LUBpp
LUCpppBL
LULC032
LU9AP20
GB2CD07
88400

* : for drawers and fixed mounting plates.

DD382871

Example

LCDD
OFF T
RESE

0
LOCA

TE
REMO

Mounting plate H = 50 mm (1 module).

49

Diagram

Diagram No. 112

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Bus + communication module

sch112

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

50

Diagram

Diagram No. 112

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Bus + communication module

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Modbus module
Rev. block 32A 24 V DC
Reverser coil terminals
Wired reverser control terminals
Tesys ext. handle
Control circuit breaker

Quantity
(1)
1
1
1
1
1
1
(1)*
1

Reference
LUALB1
LUBpp
LUCpppBL
LULC032
LU2MB0BL
LU9M1
LU9MRC
LU9AP20
GB2CD07

* : for drawers and fixed mounting plates.

DD382872

Example

Mounting plate H = 50 mm (1 module).

51

Diagram

Diagram No. 113

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Bus + communication module

sch113

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

52

Diagram

Diagram No. 113

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Bus + communication module

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Modbus module
Rev. block 32A 24 V DC
Reverser coil terminals
Reverser control terminals
Tesys ext. handle
Control circuit breaker
LCDD 2
Plug in relay
Protect diode 12-250 V DC
Socket add. modules

Quantity
(1)
1
1
1
1
1
1
(1)*
1
1
1
1
1

Reference
LUALB1
LUBpp
LUCpppBL
LULC032
LU2MB0BL
LU9M1
LU9MR1
LU9AP20
GB2CD07
88401
RXN21E11BD
RXW040MD
RXZ7G

* : for drawers and fixed mounting plates.

DD382873

Example

Mounting plate H = 50 mm (1 module).

53

Diagram

Diagram No. 121

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, DOL
Bus + Tesys U controller

sch121

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

54

Diagram

Diagram No. 121

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, DOL
Bus + Tesys U controller

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug in aux. 2NO
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Control base
Control unit
Modbus module
Current transformer
LCDD 1 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
3
1
1
1
3
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE20
GVAD1001
GV2AP01
GV2AP04
GB2CD07
24201
26924
07180
LC1DppP7
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88400

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382824

Examples

Mounting plate H = 100 mm (2 modules).

Mounting plate H = 150 mm (3 modules).

55

Diagram

Diagram No. 123

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, reversing
Bus + Tesys U controller

sch123

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

56

Diagram

Diagram No. 123

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, reversing
Bus + Tesys U controller

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug in aux. 2NO
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Reversing contactor 230 V 50/60 Hz
Contacts block
Control base
Control unit
Modbus module
Current transformer
LCDD 2 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
2
1
1
1
3
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE20
GVAD1001
GV2AP01
GV2AP04
GB2CD07
24201
26924
LC2DppP7
LADN11
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88401

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382879

Examples

Mounting plate H = 100 mm (2 modules).

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

57

Diagram

Diagram No. 127

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, star delta
Bus + Tesys U controller

sch127

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

58

Diagram

Diagram No. 127

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, star delta
Bus + Tesys U controller

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug in aux. 2NO
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contact block
Contact block
Control base
Control unit
Modbus module
Current transformer
LCDD 1 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
3
1
1
1
1
1
1
3
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE20
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26924
LC1DppP7
LA9Dpppp
LADS2
LA8DN11
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88400

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382880

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

59

Diagram

Diagram No. 151

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, DOL
Bus + Tesys U controller

sch151

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

60

Diagram

Diagram No. 151

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, DOL
Bus + Tesys U controller

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Control base
Control unit
Modbus module
Current transformer
LCDD 1 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
1
1
1
3
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
LC1DppP7
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88400

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.

DD382881

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 300 mm (6 modules).

61

Diagram

Diagram No. 153

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, reversing
Bus + Tesys U controller

sch153

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

62

Diagram

Diagram No. 153

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, reversing
Bus + Tesys U controller

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Reversing contactor 230 V 50/60 Hz
Contacts block
Control base
Control unit
Modbus module
Current transformer
LCDD 2 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
2
1
1
1
3
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
LC2DppP7
LADN11
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88401

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.

DD382823

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

63

Diagram

Diagram No. 157

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, star delta
Bus + Tesys U controller

sch157

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

64

Diagram

Diagram No. 157

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, star delta
Bus + Tesys U controller

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contact block
Contact block
Control base
Control unit
Modbus module
Current transformer
LCDD 1 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
3
1
1
1
1
1
1
3
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
LC1DppP7
LA9Dpppp
LADS2
LA8DN11
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88400

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.

DD382883

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

65

Diagram

Diagram No. 171

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, DOL
Bus + Tesys U controller

sch171

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

66

Diagram

Diagram No. 171

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, DOL
Bus + Tesys U controller

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Interf. E9MM230 240 CA
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Control base
Control unit
Modbus module
Current transformer
LCDD 1 (option)

Quantity
1
2
1
(1)*
1
1
1
1
1
1
1
3
1

Reference
281pp
29450
ABR2E111M
28052
GB2CD07
24201
26924
LC1DppP7
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88400

* : drawers and fixed mounting plates.

DD382884

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

67

Diagram

Diagram No. 173

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, reversing
Bus + Tesys U controller

sch173

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

68

Diagram

Diagram No. 173

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, reversing
Bus + Tesys U controller

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Interf. E9MM230 240 CA
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Reversing contactor 230 V 50/60 Hz
Contacts block
Control base
Control unit
Modbus module
Current transformer
LCDD 2 (option)

Quantity
1
2
1
(1)*
1
1
1
1
2
1
1
1
3
1

Reference
281pp
29450
ABR2E111M
28052
GB2CD07
24201
26924
LC2DppP7
LADN11
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88401

* : drawers and fixed mounting plates.

DD382885

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

69

Diagram

Diagram No. 177

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, star delta
Bus + Tesys U controller

sch177

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

70

Diagram

Diagram No. 177

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, star delta
Bus + Tesys U controller

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Interf. E9MM230 240 CA
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contacts block
Contact block
Control base
Control unit
Modbus module
Current transformer
LCDD 1 (option)

Quantity
1
2
1
(1)*
1
1
1
3
1
1
1
1
1
1
3
1

Reference
281pp
29450
ABR2E111M
28052
GB2CD07
24201
26924
LC1DppP7
LA9Dpppp
LA8DN11
LADS2
LUTM10BL
LUCpT1BL
LULC032
LUTCpppp
88400

* : drawers and fixed mounting plates.

DD382887

Examples

Mounting plate H = 300 mm (6 modules).

71

Diagram

Diagram No. 221

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, DOL
Bus + "input/output" module

sch221

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

72

Diagram

Diagram No. 221

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, DOL
Bus + "input/output" module

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Conta. ppA 1F + 1O 230 V 50/60 Hz
OTB Advantys module
Overload relay
LCDD 1 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
2
1
1
1
1
1
1
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26924
LC1DppP7
OTB1S0DM9LP
LRDpp
88400

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382888

Examples

Mounting plate H = 100 mm (2 modules).

Mounting plate H = 150 mm (3 modules).

73

Diagram

Diagram No. 223

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, reversing
Bus + "input/output" module

sch223

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

74

Diagram

Diagram No. 223

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, reversing
Bus + "input/output" module

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Reversing contactor 230 V 50/60
Contacts block
OTB Advantys module
Overload relay
LCDD 2 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
2
1
1
1
1
2
1
1
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26924
LC2DppP7
LADN11
OTB1S0DM9LP
LRDpp
88401

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382889

Examples

Mounting plate H = 100 mm (2 modules).

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

75

Diagram

Diagram No. 225

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, 2 speed
Bus + "input/output" module

sch225

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

76

Diagram

Diagram No. 225

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, 2 speeds
Bus + "input/output" module

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contact block
OTB Advantys module
Overload relay
LCDD 2 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
2
1
1
1
2
1
2
1
2
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26924
LC1DppP7
LA9Dpppp
LADN11
OTB1S0DM9LP
LRDpp
88401

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382825

Examples

Mounting plate H = 100 mm (2 modules).

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

77

Diagram

Diagram No. 227

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, star delta
Bus + "input/output" module

sch227

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

78

Diagram

Diagram No. 227

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, star delta
Bus + "input/output" module

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contact block
Contact block
OTB Advantys module
Overload relay
LCDD 1 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
2
1
1
1
3
1
1
1
1
1
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26924
LC1DppP7
LA9Dpppp
LA8DN11
LADS2
OTB1S0DM9LP
LRDpp
88400

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382890

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

79

Diagram

Diagram No. 229

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, Dalhander
Bus + "input/output" module

sch229

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

80

Diagram

Diagram No. 229

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, Dalhander
Bus + "input/output" module

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contacts block
OTB Advantys module
Overload relay
LCDD 2 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
2
1
1
1
3
1
2
1
2
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26924
LC1DppP7
LA9Dpppp
LADN11
OTB1S0DM9LP
LRDpp
88401

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382890

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

81

Diagram

Diagram No. 251

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, DOL
Bus + "input/output" module

sch251

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

82

Diagram

Diagram No. 251

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, DOL
Bus + "input/output" module

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
OTB Advantys module
Overload relay
Current transformer
LCDD 1 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
1
(1)*****
1
1
(3)*****
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
07180
LC1DppP7
LAD7B10
OTB1S0DM9LP
LRDpp
LUTCpppp
88400

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382891

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 300 mm (6 modules).

83

Diagram

Diagram No. 253

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, reversing
Bus + "input/output" module

sch253

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

84

Diagram

Diagram No. 253

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, reversing
Bus + "input/output" module

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Reversing contactor 230 V 50/60 Hz
Terminal block
Contacts block
OTB Advantys module
Overload relay
Current transformer
LCDD 2 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
1
(1)*****
2
1
1
(3)*****
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
07180
LC2DppP7
LAD7B10
LADN11
OTB1S0DM9LP
LRDpp
LUTCpppp
88401

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382892

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

85

Diagram

Diagram No. 255

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, 2 speed
Bus + "input/output" module

sch255

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

86

Diagram

Diagram No. 255

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, 2 speed
Bus + "input/output" module

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contacts block
OTB Advantys module
Overload relay
Current transformer
LCDD 2 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
2
(2)*****
1
2
1
2
(6)*****
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
07180
LC1DppP7
LAD7B10
LA9Dpppp
LADN11
OTB1S0DM9LP
LRDpp
LUTCpppp
88401

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382893

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

87

Diagram

Diagram No. 257

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, star delta
Bus + "input/output" module

sch257

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

88

Diagram

Diagram No. 257

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, star delta
Bus + "input/output" module

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contact block
Contact block
OTB Advantys module
Overload relay
Current transformer
LCDD 1 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
3
(1)*****
1
1
1
1
1
(3)*****
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
07180
LC1DppP7
LAD7B10
LA9Dpppp
LADS2
LA8DN11
OTB1S0DM9LP
LRDpp
LUTCpppp
88400

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382894

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

89

Diagram

Diagram No. 259

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, Dalhander
Bus + "input/output" module

sch259

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

90

Diagram

Diagram No. 259

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, Dalhander
Bus + "input/output" module

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contacts block
OTB Advantys module
Overload relay
Current transformer
LCDD 2 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
3
(2)*****
1
2
1
2
(6)*****
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26924
07180
LC1DppP7
LAD7B10
LA9Dpppp
LADN11
OTB1S0DM9LP
LRDpp
LUTCpppp
88401

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382895

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

91

Diagram

Diagram No. 271

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, DOL
Bus + "input/output" module

sch271

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

92

Diagram

Diagram No. 271

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, DOL
Bus + "input/output" module

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
OTB Advantys module
Overload relay
Current transformer
LCDD 1 (option)

Quantity
1
2
(1)*
1
1
1
1
1
(1)**
1
1
(3)**
1

Reference
281pp
29450
28052
GB2CD07
24201
26924
07180
LC1DppP7
LAD7B10
OTB1S0DM9LP
LRDpp
LUTCpppp
88400

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382896

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

93

Diagram

Diagram No. 273

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, reversing
Bus + "input/output" module

sch273

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

94

Diagram

Diagram No. 273

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, reversing
Bus + "input/output" module

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Reversing contactor 230 V 50/60 Hz
Terminal block
Contacts block
OTB Advantys module
Overload relay
Current transformer
LCDD 2 (option)

Quantity
1
2
(1)*
1
1
1
1
1
(1)**
2
1
1
(3)**
1

Reference
281pp
29450
28052
GB2CD07
24201
26924
07180
LC2DppP7
LAD7B10
LADN11
OTB1S0DM9LP
LRDpp
LUTCpppp
88401

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD383015

Example

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

95

Diagram

Diagram No. 275

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, 2 speed
Bus + "input/output" module

sch275

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

96

Diagram

Diagram No. 275

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, 2 speed
Bus + "input/output" module

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contacts block
OTB Advantys module
Terminal block
Overload relay
Current transformer
LCDD 2 (option)

Quantity
1
2
(1)*
1
1
1
1
2
1
2
1
(2)**
2
(6)**
1

Reference
281pp
29450
28052
GB2CD07
24201
26924
07180
LC1DppP7
LA9Dpppp
LADN11
OTB1S0DM9LP
LAD7B10
LRDpp
LUTCpppp
88401

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382898

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

97

Diagram

Diagram No. 277

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, star delta
Bus + "input/output" module

sch277

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

98

Diagram

Diagram No. 277

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, star delta
Bus + "input/output" module

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Terminal block
Contact block
Contacts block
OTB Advantys module
Overload relay
Current transformer
LCDD 1 (option)

Quantity
1
2
(1)*
1
1
1
1
3
1
(1)**
1
1
1
1
(3)**
1

Reference
281pp
29450
28052
GB2CD07
24201
26924
07180
LC1DppP7
LA9Dpppp
LAD7B10
LA8DN11
LADS2
OTB1S0DM9LP
LRDpp
LUTCpppp
88400

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382899

Example

Mounting plate H = 300 mm (6 modules).

99

Diagram

Diagram No. 279

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, Dalhander
Bus + "input/output" module

sch279

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

100

Diagram

Diagram No. 279

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, Dalhander
Bus + "input/output" module

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Auxiliary switch O-F for C60/ID
Stop plates for terminal blocks
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contacts block
OTB Advantys module
Overload relay
Current transformer
LCDD 2 (option)

Quantity
1
2
(1)*
1
1
1
1
3
(2)**
1
2
1
2
(6)**
1

Reference
281pp
29450
28052
GB2CD07
24201
26924
07180
LC1DppP7
LAD7B10
LA9Dpppp
LADN11
OTB1S0DM9LP
LRDpp
LUTCpppp
88401

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382899

Example

Mounting plate H = 300 mm (6 modules).

101

Diagram

Diagram No. 310

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Point-to-point wiring

sch310

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

102

Diagram

Diagram No. 310

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Point-to-point wiring

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Tesys ext. handle
C32H-DC 2P 2 A C curve
Auxiliary contact of NC100

Quantity
(1)
1
1
(1)*
1
1

Reference
LUALB1
LUBpp
LUCpppBL
LU9AP20
20542
27132

* : drawers and fixed mounting plates.

DD382874

Example

Mounting plate H = 50 mm (1 module).

103

Diagram

Diagram No. 311

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Point-to-point wiring

sch311

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

104

Diagram

Diagram No. 311

Prisma Plus
disconnectable-type
switchboards

1-component feeder
Tesys U circuit breaker-contactor, DOL
Point-to-point wiring

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Aux. contact mod 2 Mo
Tesys ext. handle
C32H-DC 2P 2 A C curve
Auxiliary contact of NC100
Plug in relay
Protect diode 12-250 V DC
Socket add. modules
LCDD 1

Quantity
(1)
1
1
1
(1)*
1
1
1
1
1
1

Reference
LUALB1
LUBpp
LUCpppBL
LUFN20
LU9AP20
20542
27132
RXN21E11BD
RXW040MD
RXZ7G
88400

* : drawers and fixed mounting plates.

DD382875

Example

Mounting plate H = 50 mm (1 module).

105

Diagram

Diagram No. 312

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Point-to-point wiring

sch312

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

106

Diagram

Diagram No. 312

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Point-to-point wiring

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Reversing block 32 A 24 V DC
Reverser coil terminals
Reverser control terminals
Tesys ext. handle
C32H-DC 2P 2 A C curve
Auxiliary contact of NC100

Quantity
(1)
1
1
1
1
1
(1)*
1
1

Reference
LUALB1
LUBpp
LUCpppBL
LU2MB0BL
LU9M1
LU9MR1
LU9AP20
20542
27132

* : drawers and fixed mounting plates.

DD382876

Example

Mounting plate H = 50 mm (1 module).

107

Diagram

Diagram No. 313

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Point-to-point wiring

sch313

Diagram

Not to be used for disconnectable mounting plates.


Not to be used for fixed feeders.

108

Diagram

Diagram No. 313

Prisma Plus
disconnectable-type
switchboards

1-component feeder, Tesys U


circuit breaker-contactor, reversing
Point-to-point wiring

Diagram

Equipment list
Designation
130 kA limiter
Screw clamp base ppA
Unit 24 V DC
Reversing block 32 A 24 V DC
Reverser coil terminals
Reverser control terminals
Tesys ext. handle
LCDD 2
Input relay em interf.
C32H-DC 2P 2 A C curve
Auxiliary contact of NC100
Aux. contact mod. 1NO 1NC

Quantity
(1)
1
1
1
1
1
(1)*
1
2
1
1
1

Reference
LUALB1
LUBpp
LUCpppBL
LU2MB0BL
LU9M1
LU9MR1
LU9AP20
88401
ABR2E112B
20545
27132
LUFN11

* : drawers and fixed mounting plates.

DD382877

Example

LCDD
OFF T
RESE

0
L

TE
REMO

LOCA

Mounting plate H = 50 mm (1 module).

109

Diagram

Diagram No. 321

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, DOL
Point-to-point wiring

sch321

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

110

Diagram

Diagram No. 321

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, DOL
Point-to-point wiring

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Conta. ppA 1F + 1O 230 V 50/60 Hz
Contacts block
Input relay en interf
Overload relay
LCDD 1 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
1
1
3
1
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26929
LC1DppP7
LADN11
ABR2E112B
LRDpp
88400

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382869

Example

Mounting plate H = 75 mm (1,5 module).

Mounting plate H = 150 mm (3 modules).

111

Diagram

Diagram No. 323

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, reversing
Point-to-point wiring

sch323

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

112

Diagram

Diagram No. 323

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, reversing
Point-to-point wiring

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Reversing contactor 230 V 50/60 Hz
Contacts block
Input relay en interf
Overload relay
LCDD 2 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
1
2
3
1
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26929
LC2DppP7
LADN31
ABR2E112B
LRDpp
88401

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382826

Examples

Mounting plate H = 100 mm (2 modules).

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

113

Diagram

Diagram No. 325

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, 2 speed
Point-to-point wiring

sch325

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

114

Diagram

Diagram No. 325

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, 2 speed
Point-to-point wiring

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contacts block
Input relay en interf
Overload relay
LCDD 2 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
2
1
2
3
2
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26929
LC1DppP7
LA9Dpppp
LADN31
ABR2E112B
LRDpp
88401

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382900

Examples

Mounting plate H = 100 mm (2 modules).

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

115

Diagram

Diagram No. 327

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, star delta
Point-to-point wiring

sch327

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

116

Diagram

Diagram No. 327

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, star delta
Point-to-point wiring

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contact block
Contact block
Input relay en interf
Overload relay
LCDD 1 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
3
1
1
1
3
1
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26929
LC1DppP7
LA9Dpppp
LAD8N20
LADS2
ABR2E112B
LRDpp
88400

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD382901

Example

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

117

Diagram

Diagram No. 329

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, Dalhander
Point-to-point wiring

sch329

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

118

Diagram

Diagram No. 329

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GV2 circuit breaker, Dalhander
Point-to-point wiring

Diagram

Equipment list
Designation
Limiter + Pratic raiser
Magnetic circuit breaker
Plug-in aux. INO or NC
Aux. NC inst. NC fault sig
External operator
GV2 external handle
Stop plates for terminal blocks
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Interlock for cont.
Contacts block
Input relay en interf
Overload relay
LCDD 2 (option)

Quantity
(1)
1
1
1
(1)*
(1)**
1
1
1
1
3
1
2
3
2
1

Reference
LA9LB920 + 04224
GV2-Lpp
GVAE11
GVAD1001
GV2AP01
GV2AP04
07180
GB2CD07
24201
26929
LC1DppP7
LA9Dpppp
LADN31
ABR2E112B
LRDpp
88401

* : for 6M and higher drawers and fixed mounting plates.


** : for under 6M drawers and fixed mounting plates.

DD383014

Example

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

119

Diagram

Diagram No. 351

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, DOL
Point-to-point wiring

sch351

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

120

Diagram

Diagram No. 351

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, DOL
Point-to-point wiring

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 1 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
3
(1)*****
1
3
(3)*****
1
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LADN11
ABR2E112B
LUTCpppp
LRDpp
88400

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382902

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 300 mm (6 modules).

121

Diagram

Diagram No. 353

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, reversing
Point-to-point wiring

sch353

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

122

Diagram

Diagram No. 353

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, reversing
Point-to-point wiring

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Reversing contactor 230 V 50/60 Hz
Terminal block
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 2 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
1
(1)*****
2
3
(3)*****
1
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26929
LC2DppP7
LAD7B10
LADN31
ABR2E112B
LUTCpppp
LRDpp
88401

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382903

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

123

Diagram

Diagram No. 355

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, 2 speed
Point-to-point wiring

sch355

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

124

Diagram

Diagram No. 355

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, 2 speed
Point-to-point wiring

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 2 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
2
(2)*****
1
2
3
(6)*****
2
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LA9Dpppp
LADN31
ABR2E112B
LUTCpppp
LRDpp
88401

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382904

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

125

Diagram

Diagram No. 357

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, star delta
Point-to-point wiring

sch357

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

126

Diagram

Diagram No. 357

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, star delta
Point-to-point wiring

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contact block
Contact block
Input relay en interf
Current transformer
Overload relay
LCDD 1 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
3
(1)*****
1
1
2
3
(3)*****
1
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LA9Dpppp
LADS2
LAD8N20
ABR2E112B
LUTCpppp
LRDpp
88400

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382905

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

127

Diagram

Diagram No. 359

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, Dalhander
Point-to-point wiring

sch359

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

128

Diagram

Diagram No. 359

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with GS1 disconnector fuse, Dalhander
Point-to-point wiring

Diagram

Equipment list
Designation
GSI fuse switch disconnector
Contact block 1 x OF
Contact 2 x OF 50 to 250 A
Contact 1 x OF 50 A
Black ext. handle 32-63 A
Black ext. handle 100-400 A
Internal handle 32-63 A
Internal handle 100-400 A
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 2 (option)

Quantity
1
1
1
1
(1)*
(1)**
(1)***
(1)****
1
1
1
3
(2)*****
1
2
3
(6)*****
2
1

Reference
GS1ppp
GS1AM1
GS1AF
GS1AF1
GS1AH110
GS1AH130
GS1AH01
GS1AH02
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LA9Dpppp
LADN31
ABR2E112B
LUTCpppp
LRDpp
88401

* : for GS1F on drawers and fixed mounting plates.


** : for GS1J on drawers and fixed mounting plates.
*** : for GS1F on disconnectable mounting plates.
**** : for GS1J on disconnectable mounting plates.
*****: with LCpD115/150 contactors.

DD382905

Examples

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

129

Diagram

Diagram No. 371

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, DOL
Point-to-point wiring

sch371

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

130

Diagram

Diagram No. 371

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, DOL
Point-to-point wiring

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Contacts block
Input relay en interf
Overload relay
Current transformer
LCDD 1 (option)

Quantity
1
2
(1)*
1
1
1
1
(1)**
1
3
1
(3)**
1

Reference
281pp
29450
28052
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LADN11
ABR2E112B
LRDpp
LUTCpppp
88400

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382906

Examples

Mounting plate H = 150 mm (3 modules).

Mounting plate H = 200 mm (4 modules).

131

Diagram

Diagram No. 373

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, reversing
Point-to-point wiring

sch373

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

132

Diagram

Diagram No. 373

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, reversing
Point-to-point wiring

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Reversing contactor 230 V 50/60 Hz
Terminal block
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 2 (option)

Quantity
1
2
(1)*
1
1
1
1
(1)**
2
3
(3)**
1
1

Reference
281pp
29450
28052
GB2CD07
24201
26929
LC2DppP7
LAD7B10
LADN31
ABR2E112B
LUTCpppp
LRDpp
88401

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382907

Example

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

133

Diagram

Diagram No. 375

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, 2 speed
Point-to-point wiring

sch375

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

134

Diagram

Diagram No. 375

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, 2 speed
Point-to-point wiring

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 2 (option)

Quantity
1
2
(1)*
1
1
1
2
(2)**
1
2
3
(6)**
2
1

Reference
281pp
29450
28052
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LA9Dpppp
LADN31
ABR2E112B
LUTCpppp
LRDpp
88401

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382908

Example

Mounting plate H = 200 mm (4 modules).

Mounting plate H = 300 mm (6 modules).

135

Diagram

Diagram No. 377

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, star delta
Point-to-point wiring

sch377

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

136

Diagram

Diagram No. 377

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, star delta
Point-to-point wiring

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contact block
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 1 (option)

Quantity
1
2
(1)*
1
1
1
3
(1)**
1
1
1
3
(3)**
1
1

Reference
281pp
29450
28052
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LA9Dpppp
LAD8N20
LADS2
ABR2E112B
LUTCpppp
LRDpp
88400

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382909

Example

Mounting plate H = 300 mm (6 modules).

137

Diagram

Diagram No. 379

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, Dalhander
Point-to-point wiring

sch379

Diagram

LCDD local control and display device.


Not to be used for disconnectable mounting plates.
Not to be used for fixed feeders.

138

Diagram

Diagram No. 379

Prisma Plus
disconnectable-type
switchboards

3-component feeder
with NS80HMA circuit breaker, Dalhander
Point-to-point wiring

Diagram

Equipment list
Designation
Compact NS80H-MApp
1 aux. switch C/O contact
Extended rotary handle (NS80H)
Control circuit breaker
C60N 2P 10 A C curve
Alarm contact OF and OF or SD
Cont. ppA 1F + 1O 230 V 50/60 Hz
Terminal block
Interlock for cont.
Contacts block
Input relay en interf
Current transformer
Overload relay
LCDD 2 (option)

Quantity
1
2
(1)*
1
1
1
3
(2)**
1
2
3
(6)**
2
1

Reference
281pp
29450
28052
GB2CD07
24201
26929
LC1DppP7
LAD7B10
LA9Dpppp
LADN31
ABR2E112B
LUTCpppp
LRDpp
88401

* : drawers and fixed mounting plates.


** : with LCpD115/150 contactors.

DD382909

Example

Mounting plate H = 300 mm (6 modules).

139

140

Schneider Electric Industries SAS


89, boulevard Franklin Roosevelt
F - 92500 Rueil-Malmaison (France)
Tel : +33 (0)1 41 29 85 00
http://www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been printed
on ecological paper.

http://www.schneider-electric.co

Designed: Ameg
Photos: Schneider Electric Industries SAS, Headlines
Printed:
DESW046EN

12-2004

ART 960049 2004 - Schneider Electric - All rights reserved.