Experion LS

Quick start-up Guide


(for system integrators)

STEP 1 Device Configuration


Please ensure that all the required devices are available as per
Demo BOM.
Essential devices :

- Experion LS s/w
 Demo Machine with Windows Vista Business 32Bit sp2 loaded
 Experion LS s/w DVD

C200 Controller
 Base, Power module, CPU module, FTEB Module, I/O Module
 Network Switch (Honeywell recommended CISCO) + N/w Cables (2nos.)

HONEYWELL - CONFIDENTIAL

File Number

2. Installation Method

STEP 1 Experion LS S/w Configuration


To install Experion LS software, Please follow the
procedure as per attached document (Experion LS Demo Kit.pdf)

Microsoft Word
Document

HONEYWELL - CONFIDENTIAL

File Number

STEP 2 C200 Hardware Installation


Below is an example C200 chassis configured with:
- 7 slot chassis
- Power supply

0
1 2

FTE Bridge
Control Processor C200E

Power Supply

DI Module IDD321

3
4
5
6

DO Module ODD321
AO Module OAV081
AI Module IAH161

2
3

C200E - CPM

110 VAC Power

To 10 mbps Switch

Before Installing FTEB, Please set Rotary switch for FTE Node number (1 to
99), say 10.
Experion LS - CEE C200
3

HONEYWELL - CONFIDENTIAL

File Number

STEP 2 C200 Hardware Installation


To determine the slot location of C200 related
hardware you must:
- Set Rotary Switch node address as shown in picture.
- Start counting at zero (do not count the power supply)
- Count from left to right
- Count both spaces if the module occupies two spaces
- The ethernet connection to the FTEB is 10Mbps

HONEYWELL - CONFIDENTIAL

File Number

STEP 3 Controller Startup


Connect power cable to power supply module
Take care of grounding appropriately.
Supply the power to the system
Check the LED status at FTEB

- A & B: ON
 Red Steady no n/w cable connected
 Red Blinking n/w cable connected but Experion LS is not communicating
 Green Blinking In n/w with Experion LS is communicating after configuration.

- OK: ON, (Green Blinking)


- 4 Character LED show BP error & node number.
Check the LED status of Control Processor

- BAT: ON (Green Steady)


- OK: ON, (Green Blinking)
- 4 Character LED show ALIVE

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration

Open Configuration Studio


CLICK

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration

CLICK

Select the server.


Then, select the Connect button.

CLICK

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration

CLICK

Select Control Strategy

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration

CLICK

Select Configure process control


strategies

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration


Control Builder window opens as below:-

10

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration - FTEB


Go to System Preferences:-

11

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration - FTEB


-Go to System Preferences
-Embedded FTE
-Check Edit Network Parameters.
-In Base IP Address: type your firs
t 2 number similar to your machine
ip address.
-In Subnet Mask: type your first 2
number similar to your machine ip
subnet mask.
-In Primary Server, type your mac
hine IP address.
-In Secondary Server, no entry.
-Click OK.

12

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration - FTEB


Create FTEB Module as follow:-

13

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration - FTEB


Configure FTEB Module as below:-

0 for Demo kit.


Must match the hardware
switches found on top of the
FTEB card. e.g.31

Click OK after above


values entered.

C200 Hardware Configuration

14 Describe the Configuration of C200 Hardware and I/O

HONEYWELL - CONFIDENTIAL

EXP20R300 - EPKS CEE C200/C300/ACE

File Number

STEP 4 Controller Configuration - FTEB


- Recycle power at C200 controller.
- C200 reboot and self test.
- Check status on 4 Character LED. It should show OK and node number as
configured.
- At windows, Go to Start  Run  Type ntools e u. Following window will
pop-up.

15

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration - ntools

Click here to Start scanning..

FTEB icon should be visible

Check for sw version details for each


module. Upgrade as required. Please see
manual for upgradation procedure,

16

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration C200E

Follow these steps to add


a new control processor
module (C200E) from the
pull-down menus

C200 Hardware Configuration

17 Describe the Configuration of C200 Hardware and I/O

HONEYWELL - CONFIDENTIAL

EXP20R300 - EPKS CEE C200/C300/ACE

File Number

STEP 4 Controller Configuration C200E


Tag Name &
Item Name
Ethernet
driver

MAC ID of card
connected to
server
FTEB slot #

Driver
Name

Alarm reporting by
CEE
No redundant controller

Configure other tabs for History & Trending as per your requirements.
Press OK when done.
18

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration CEE


Configuring a CEE CEE Tree View

Click the + sign to expand


the CPM in the Project tab

Double-click to open the


configuration form

19

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration CEE

The Control Processor Module and its Control Execution Environment (


C E E ) h a v e n o w b e e n c o n f i g u r e d b u t n o t ye t d o w n l o a d e d

20

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration IO Modules


Select IO module as
shown:

21

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration IO Modules


Select the Library tab from the
tree view to display a list of
devices
- IOMODULE
 All available rack I/O modules
 Create modules as available.
 Demo kit bundle includes
DI Module IDD321
DO Module ODD321
AO Module OAV081
AI Module IAH161

22

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration IO Modules


1

2
Control Builder
Automatically
Names the IOM

23

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration IO Modules

Module slot number as installed

MAC address of the remote


racks CNI card. For Demo kit, 0
Slot number of the CNI in
the processor rack through
which this card will
Communicate. For Demo kit, 0

24

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration IO Modules

2
3

Assigned
to CEE

25

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration IO Modules

Not yet
loaded

26

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration Loading


Loading the Controller, CEE and IOMs
Verify that the
items to load
are checked
Note:
You can decide to
have the modules
go to the active
state automatically
by clicking this
checkbox, with the
Post Load State
selected, to be
Active

27

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration Activation


Activating a Control Strategy
Double-click CEE

Select Cold Start

28

HONEYWELL - CONFIDENTIAL

File Number

STEP 4 Controller Configuration Activation


Activating a
Control Strategy

Select warm start

Blue:
Blue The object is not running (inactive)
Green:
Green The object is running (active)
Red:
Red Communication failure

29

HONEYWELL - CONFIDENTIAL

File Number

STEP 5 Controller Ready


Check the LED status at FTEB
- A : ON
 Green Blinking In n/w with Experion LS is communicating after configuration.

- OK: ON, (Green Blinking)


- 4 Character LED shows OK & node number.
Check the LED status of Control Processor
- BAT: ON (Green Steady)
- OK: ON, (Green Steady)
- 4 Character LED shows RUN

SYSTEM IS READY FOR DEMO PROGRAMS DEVELOPMENT.

30

HONEYWELL - CONFIDENTIAL

File Number

Experion LS Support
Support for Demo system installation
1. Please email me (manoj.domyan@honeywell.com) or Namrata (Namrata.
mohan@honeywell.com) in case of any problems or support required while
installation or configuration.
2. For HFS TAC, email to HFS-TAC-Support@honeywell.com or
call 1-800-423-9883

31

HONEYWELL - CONFIDENTIAL

File Number