Date of issue:

1.9.2015

Type Test Report


Serial No.:
Customer:
Type:
Product Code:

M3AA 180MLB 4
3GAA182420-ADK

Customer ref.:
Rating:
V
690
400
660
380
415
460

3~Motor
Insul.cl.F
IP55

Y
D
Y
D
D
D

Hz
50
50
50
50
50
60

kW
22,0
22,0
22,0
22,0
22,0
22,0

r/min
1480
1480
1477
1477
1482
1783

cos j
0,82
0,82
0,84
0,84
0,80
0,82

A
24,1
41,5
42,7
42,7
40,9
35,8

Duty
S1
S1
S1
S1
S1
S1

Eff class IE3


50Hz :
60Hz :
Resistance
Line
U1 - V1
U1 - W 1
V1 - W 1

Ambient:
0,1964
0,1952
0,1953

IE3 - 93,3(100%) - 94,1(75%) - 94,1(50%)


IE3 - 93,8(100%)

22,4 C
W
W
W

Insulation resistance at
R > 2000 Mohm

High-voltage test winding

Test

Torque
[Nm]

No load test
Locked rotor test

Line
U[V]
401,2
80,7

Overload
Volt.
130 %
Curr.
160 %
Speed 120 %

1000 V

D
D

f[Hz]
50
50

Input
I[A]
15,3
41,8

P1 [kW]
0,50
1,80

2400 V

60 s

Output
P2 [kW] n[r/min]
1500

cos j
0,05
0,31

h [%]

Thermal test ( 100% load )

141,7

400

50

41,3

23,70

22,00

1482

0,83

93,00

Partial load points:


~75% load
~50% load
~25% load

105,8
70,3
35,1

400
400
400

D
D
D

50
50
50

32,4
24,5
18,2

17,60
11,80
6,10

16,50
11,00
5,50

1489
1493
1498

0,79
0,69
0,48

93,60
93,30
90,40

[oC]

[K]
62,8

Temperature rise at rated load.


Stator winding :
Frame :
Bearing D-end :

64
67

Method
1
2
2

Ambient Temperature :

25

Measurement method
1 Resistance
2 Thermometer
3 Thermocouples

These tests have been carried out on motor no. 3GV13 11256351 001 , on date 2013-10-02
which is identical in electrical design with the above.

Manufactured and tested in accordance with rules of IEC 60034-1 and IEC 60034-2-1.
PLL determined from residual loss.
On behalf of customer
On behalf of manufacturer

Date of test
Telephone

Tested by ABB AB, LV Motors, 721 70 Vsters, Sweden


Computer print-out valid without signature.

ABB, Motors and Generators


www abb.com/motors&generators

Telefax

+46 (0)21 32 90 00
+46 (0)21 32 90 22

60s
120s