for
Raw Water Pump House and River Water
Intake Pump House
Client
Consultant
L&T Construction
Water & Renewable Energy
L&T DOCUMENTS NO::LT-DG-LE130733-1-E510 REV B ( FOR INTAKE SYSTEM)
LT-DG-LE130733-3-ES513 REV B ( FOR RWPH SYSTEM)
Compiled by
C B Ramesh, Chennai.
9884370326,
Contents
Sl.No
Descriptiion
Page No
Setting calculations for Transformer Feeders -River water intake Pump House
10
13
15
20
Setting for 3.3 kV Switch Boards River Water Intake Pump House
35
48
10
54
11
60
12
62
13
64
14
67
15
70
16
72
17
79
18
95
19
102
20
106
REFERENCE DOCUMENTS
Drawing Title
File reference
Drawing No
SINGLE LINE DIAGRAM FOR CONTROL METERING & PROTECTION DIAGRAM OF 11kV,3.3kV
AND 415 V SYSTEMS FOR RIVER WATER INTAKE PUMP HOUSE
LT/DC/LE130733/1/E402/REV D/SHEET 2 OF 3
revision D
SINGLE LINE DIAGRAM FOR CONTROL METERING & PROTECTION DIAGRAM OF 11kV,3.3kV
AND 415 V SYSTEMS FOR RIVER WATER INTAKE PUMP HOUSE
LT/DC/LE130733/1/E402/REV D/SHEET 3 OF 3
revision D
SINGLE LINE DIAGRAM FOR CONTROL METERING & PROTECTION DIAGRAM OF 11kV,3.3kV
AND 415 V SYSTEMS FOR RIVER WATER INTAKE PUMP HOUSE
LT/DC/LE130733/1/E402/REV D/SHEET 1 OF 3
revision D
11 kV Switch Board
09041-E-BM-CS-DD-0217,sh1-sh175
LT/DG/LE130733/1/E481/REVD-revision D
Technical Data sheet for 500 kW ,6 pole,3.3kV Vertical Intake Electrical Motor
Characteristic curves of 500 kW , 6pole,3.3kV Vertical Intake Electrical Motor
10
Value
500
3300
111.5
4.5 x IA
4.8X IA
1.6
2.9
30
180
117.08
12
501.75
12
15
Value
units
kW
V
A
sec
sec
min
min
A
sec
A
sec
sec
Units
160 A
1A
111.5 A
IA x CT ratio
111.5 x 1/160
0.70 A
111.5 x 105/100
117.08 A
117.5 x 1/160
0.73 A
4.5X IA
=4.5 x111.5
501.75 A
=501.75x1 / 160
3.14 A
=111.5 x 110 / 100
122.65 A
=122.65x1/160
0.77
0.77
= 1.3 x501.75
652.275 A
=652 x1/160
6.52
6.5 A
5
7
Setting Calculation for Distribution Transformers TR3 & TR4 in River water Intake Power house
11 kV
3450 V
100/1A
400 /1A
1500 kVA
Transformer capacity
PT
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 3.3 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
Vp
Vs
1500
11
3.45
100/1
CTRP 100
400/1
CTRS 400
Z
6.25%
7488
4634
78.73
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 78.73/0.95
91.16
Transformer HV side CT Secondary Pick up Current
Isfl
0.91
IDMT setting at 11 kV side
0.91
Setting proposed on HV side Ip
0.9
Curve
Normal Inverse
Transformer LV side current as per name plate
251.00
Relay drop off Ratio
0.95
LV Pick up Current
1.1 x LV Currrent/ Drop off ratio
=1.1 x 251/0.95
290.63
Transformer LV side CT Secondary Pick up Current
=290.63/400
Relay setting for over current
0.726578947
Setting proposed on LV side Ip
0.7
Curve
Normal Inverse
Fault current at 3.3kV Bus as per report,for MINIMUM SOURCE Fault
4634.00
HV side current due to fault at 3.3 kV bus
1453.39
HV side CT Secondary current due to fault at 3.3kV bus
14.53
HV side Current fault at Transformer HV side
7488.00
HV side CT current due to fault at Transformer HV side
74.88
Setting proposed on HV side relay I>>
14.53 x 1.2=17.43
Setting proposed on HV side relay I>>
18.00
Setting proposed on LV side relay I>>
6
However the HV side I>> is set at 3/4 and LV side I>> 2/2.5 to coordinate with 400 Amps fuse in the upstream
kVA
kV
kV
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Setting Calculation for Distribution Transformers TR1 & TR2 in River water Intake Power house
11 kV
433 V
50/1A
800 /1A
500 kVA
Transformer capacity
PT
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
Vp
Vs
500
11
0.433
50/1
CTRP 50
800/1
CTRS 800
Z
4.00%
7488
15170
26.24
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 26.24/0.95
30.39
Transformer HV side CT Secondary Pick up Current
Isfl
0.61
IDMT setting at 11 kV side
0.6
Setting proposed on HV side Ip
0.6
Curve
Normal Inverse
Transformer LV side current as per name plate
666.70
Relay drop off Ratio
0.95
LV Pick up Current
1.1 x LV Currrent/ Drop off ratio
=1.1 x 666.7/0.95
771.97
Transformer LV side CT Secondary Pick up Current
=777.1/800
Relay setting for over current
0.964960526
Setting proposed on LV side Ip
1
Curve
Normal Inverse
Fault current at 0.415kV Bus as per report,for MINIMUM SOURCE Fault
15170.00
HV side current due to fault at 0.415 kV bus
597.15
HV side CT Secondary current due to fault at 0.415kV bus
11.94
HV side Current fault at Transformer HV side
7488.00
HV side CT current due to fault at Transformer HV side
149.76
Setting proposed on HV side relay I>>
11.94 x 1.2=14.38
Setting proposed on HV side relay I>>
14.50
Setting proposed on LV side relay I>>
10
However the HV side I>> is set at 6/10 and LV side I>> 5/10 to coordinate with 400 Amps fuse in the upstream
kVA
kV
kV
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
13
10
500 kVA
1500 kVA
2000 kVA
500 kVA
1500 kVA
2000 kVA
2000/11/1.732
104.9758556
Ip setting
TMS setting
This should be 150 milliseconds greater than fault clearing time of down stream relay
In this case the 1500 kVA Transformer feeder is set at
tms=0.65,Ip=0.9 and CTR=100/1
Fault current-1453 Amps
t=tms x ((0.14)/((If/Is)
0.02
-1))
t=0.65 x ((0.14)/(1453/90)0.02-1))
1.59
1.74
11
0.6
0.6
Amps
+15%
115*11000/100
12650
11000/110
110 x 12650/11000
126.5
+20%
120*11000/100
13200
11000/110
110 x 13200/11000
132
PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at
PT ratio
Relay set voltage 1st element
Undervoltage
In 11 kV switch board ,over voltage 1 Element set at
-15%
85*11000/100
9350
9350/110
110 x9350/11000
93.5
-20%
80*11000/100
8800
11000/110
110 x8800/11000
88
PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at
PT ratio
Relay set voltage 1st element
12
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
13
GRID
GRID
RKSR02
CAB11
cab1
PP_boundry
CAB12
cab2
RWIT_boundry
CAB13
cab3
RKSR03
IC2_RWIT
BC_RWIT
IC1_RWIT
50
51
HTP_RWIT_BUS B
50
51
50
51
HTP_RWIT_BUS A
VCB1
VCB3
VCB2
50
51
VCB4
50
51
TR4
50
51
50
51
415V_PMCC_BC
50
51
415V_PMCC_OG1
3.3kV_HTP_OG4
50
51
CAB23
CAB22
CAB21
REL_IC1
VTP2
50
51
VTP3
REL_IC2
IC2
415V_PMCC_BUS B
415V_PMCC_BUS A
50
51
3.3kV_HTP_OG3
50
51
VTP1
3.3kV_HTP_BUS B
3.3kV_HTP_OG2
3.3kV_HTP_OG1
50
51
3.3kV_HTP_IC2
50
51
50
51
3.3kV_HTP_BUS A
CAB9
BD2
3.3kV_HTP_IC1
50
51
VCB7
50
51
TR2
BD1
CAB8
VCB6
50
51
CAB7
TR3
50
51
CAB5
cab4
CAB6
TR1
VCB5
50
51
3.3kV_HTP_BC
50
51
50
51
415V_PMCC_OG2
REV. DATE
ECO#
DESCRIPTION
DWN APP
DWG N o.:
E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :
14
SC ALE :
PART No.:
D WG SIZE :
REV.
15
RKSR02
Ik" : 13320.14A
GRID
CAB11
cab1
PP_boundry
CAB12
cab2
RWIT_boundry
CAB13
cab3
RKSR03
Ik" : 13230.54A
GRID
IC2_RWIT
BC_RWIT
IC1_RWIT
50
51
HTP_RWIT_BUS B
Ik" : 5985.61A
50
51
HTP_RWIT_BUS A
Ik" : 6073.41A
50
51
VCB1
VCB3
VCB2
50
51
50
51
TR4
50
51
415V_PMCC_BC
50
51
415V_PMCC_OG1
3.3kV_HTP_OG4
50
51
CAB23
50
51
50
51
CAB22
REL_IC1
IC1
3.3kV_HTP_OG3
50
51
CAB21
VTP1
Ik" : 4441.39A
3.3kV_HTP_BUS B
Ik" : 4063.72A
3.3kV_HTP_OG2
3.3kV_HTP_OG1
415V_PMCC_BUS A
Ik" : 14887.35A
3.3kV_HTP_IC2
50
51
50
51
3.3kV_HTP_BUS A
Ik" : 4486.58A
VCB7
50
51
CAB9
BD2
3.3kV_HTP_IC1
50
51
50
51
TR2
BD1
CAB8
VCB6
CAB7
TR3
50
51
CAB5
cab4
CAB6
TR1
VCB5
50
51
3.3kV_HTP_BC
50
51
VCB4
VTP2
Ik" : 4441.39A
50
51
REL_IC2
IC2
50
51
VTP3
Ik" : 4027.31A
415V_PMCC_BUS B
Ik" : 14869.81A
415V_PMCC_OG2
REV. DATE
ECO#
DESCRIPTION
DWN APP
DWG N o.:
E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :
16
SC ALE :
PART No.:
D WG SIZE :
REV.
RKSR02
11000
RKSR03
11000
HTP_RWIT_BUS A
11000
HTP_RWIT_BUS B
11000
VTP1
3450
VTP2
3450
VTP3
3450
3.3kV_HTP_BUS A
3300
3.3kV_HTP_BUS B
3300
415V_PMCC_BUS A
415
415V_PMCC_BUS B
415
LL Fault - IEC60909 Method
Bus Name
Pre Fault
Voltage
RKSR02
11000
RKSR03
11000
HTP_RWIT_BUS A
11000
HTP_RWIT_BUS B
11000
3.3kV_HTP_BUS A
3300
VTP1
3300
VTP2
3300
3.3kV_HTP_BUS B
3300
VTP3
3300
415V_PMCC_BUS A
415
415V_PMCC_BUS B
415
LG Fault - IEC60909 Method
Bus Name
Pre Fault
Voltage
RKSR02
11000
RKSR03
11000
HTP_RWIT_BUS A
11000
HTP_RWIT_BUS B
11000
3.3kV_HTP_BUS A
3300
VTP1
3300
VTP2
3300
3.3kV_HTP_BUS B
3300
VTP3
3300
415V_PMCC_BUS A
415
415V_PMCC_BUS B
415
LLG Fault - IEC60909 Method
Bus Name
Pre Fault
Voltage
RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B
11000
11000
11000
11000
3300
3300
3300
3300
3300
415
415
Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13320
13231
6073
5986
4441
4441
4027
4487
4064
14887
14870
13320
13231
6073
5986
4441
4441
4027
4487
4064
14887
14870
13290
13212
6043
5968
4290
4290
3951
4334
3987
14881
14866
13242
13185
5997
5942
4072
4072
3841
4113
3877
14872
14861
13200
13162
5956
5920
3897
3897
3752
3936
3789
14864
14856
13122
13122
5881
5881
3604
3604
3604
3641
3641
14848
14848
Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13298
13218
5547
5471
3919
3879
3879
3553
3520
12958
12944
13298
13218
5547
5471
3919
3879
3879
3553
3520
12958
12944
13271
13202
5521
5456
3786
3748
3748
3487
3454
12953
12941
13228
13178
5481
5433
3596
3559
3559
3391
3359
12946
12937
13191
13158
5446
5414
3442
3407
3407
3315
3282
12940
12934
13122
13122
5381
5381
3187
3154
3154
3187
3154
12928
12928
0.5 Cycle
Initial
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13223
13177
4081
4057
4854
4745
4745
4521
4427
13267
13259
13223
13177
4081
4057
4854
4745
4745
4521
4427
13267
13259
13207
13168
4073
4052
4735
4630
4630
4459
4366
13264
13257
13183
13154
4060
4045
4561
4462
4462
4368
4277
13260
13255
13162
13142
4049
4039
4417
4322
4322
4294
4205
13256
13253
13122
13122
4028
4028
4169
4083
4083
4169
4083
13249
13249
Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13785
13703
5733
5664
4754
4645
4645
4394
4295
14311
14295
17
13785
13703
5733
5664
4754
4645
4645
4394
4295
14311
14295
13757
13686
5709
5650
4624
4518
4518
4329
4231
14306
14292
13713
13661
5673
5629
4437
4334
4334
4234
4137
14297
14287
13675
13640
5641
5612
4285
4185
4185
4158
4062
14289
14282
13603
13603
5582
5582
4030
3936
3936
4030
3936
14275
14275
18
RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B
RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B
RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B
RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B
74788
74535
13837
13649
11441
11240
11240
10337
10176
34873
34829
26442
26352
7488
7405
4635
4586
4586
4212
4172
15171
15161
26442
26352
7488
7405
4635
4586
4586
4212
4172
15171
15161
26411
26334
7460
7388
4482
4435
4435
4135
4096
15168
15159
26364
26307
7416
7363
4262
4217
4217
4025
3986
15162
15156
26322
26284
7377
7342
4085
4042
4042
3937
3897
15158
15154
26243
26243
7306
7306
3789
3749
3749
3789
3749
15149
15149
74725
74500
12239
12079
9943
9767
9767
8988
8847
30259
30223
26419
26340
6686
6614
4032
3989
3989
3666
3631
13172
13165
26419
26340
6686
6614
4032
3989
3989
3666
3631
13172
13165
26392
26324
6661
6600
3899
3858
3858
3599
3565
13170
13163
26350
26300
6623
6579
3709
3669
3669
3504
3469
13166
13161
26313
26279
6590
6561
3555
3518
3518
3428
3393
13162
13159
26243
26243
6529
6529
3300
3265
3265
3300
3265
13155
13155
74514
74384
8769
8722
12414
11976
11976
11531
11155
30583
30562
26345
26299
4696
4676
4953
4839
4839
4626
4527
13396
13391
26345
26299
4696
4676
4953
4839
4839
4626
4527
13396
13391
26329
26290
4689
4672
4837
4727
4727
4565
4467
13394
13390
26305
26276
4678
4666
4665
4561
4561
4476
4380
13392
13389
26283
26264
4669
4661
4524
4424
4424
4403
4309
13390
13388
26243
26243
4652
4652
4280
4189
4189
4280
4189
13386
13386
77466
77234
12852
12707
12163
11755
11755
11218
10855
33279
33239
27389
27306
6981
6918
4883
4770
4770
4526
4422
14517
14506
19
27389
27306
6981
6918
4883
4770
4770
4526
4422
14517
14506
27360
27290
6959
6905
4754
4643
4643
4461
4358
14513
14504
27317
27265
6926
6886
4568
4461
4461
4367
4265
14508
14501
27278
27244
6896
6870
4417
4313
4313
4291
4191
14503
14498
27206
27206
6842
6842
4164
4066
4066
4164
4066
14494
14494
20
Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary output 10
LEDS,
Standard version include
27/59-Under voltage,Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Setting Dependencies
Enabled, Disabled
Enabled
2 CT/VT CONFIG
Description
Range
Setting
1, 5
Selects whether 1 or 5 Amp terminals are being used for phase inputs
1A
Prime
Prime
Phase CT Ratio
150:1
1, 5
1A
Earth CT Ratio
Measured
Earth CT ratio to scale primary current instruments
PTs
150:1
0~11000 V
110 V
11000V
110V
Range
Setting
Prime
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Range
Setting
RMS, Fundamental
RMS
3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Gn Undervoltage U/V
Gn Overvoltage O/V
Gn Trip Circuit supervision
Gn Close Circuit Supervision
Gn Circuit Breaker Fail Supervision
Gn CT Supervision
Gn VT Supervision
Gn Thermal Overload
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated
at fundamental frequency
21
Prime
4.1.1 51-1
Description
Range
Setting
Gn 51-1 Setting
0.9
Gn 51-1 Char
IEC-NI
NA
NA
4.1.3 50-1
Description
Range
Setting
Gn 50-1 Setting
Gn 50-1 Delay
0.5
4.1.4 50-2
Description
Range
Setting
Gn 50-2 Setting
Gn 50-2 Delay
0.035
5 DERIVED E/F
5.1 51N-1
Description
Range
Setting
Gn 51N-1 Setting
0.15
Gn 51N-1 Char
IEC-NI
NA
NA
5.3 50N-1
Description
Range
Setting
Gn 50N-1 Setting
Gn 50N-1 Delay
0.5s
Gn 51-1 Element
Enabled, Disabled
Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.
Gn 50-1 Element
Enabled, Disabled
Gn 50-2 Element
Enabled, Disabled
Gn 51N-1 Element
Enabled, Disabled
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Pickup level
Gn 50N-1 Element
Enabled, Disabled
22
Enabled
Prime
135
0.6
Enabled
Enabled
Enabled
Prime
450
Prime
900
Prime
22.5
0.15
Enabled
Prime
150
23
Range
Setting
o/v
o/v
Range
Setting
u/v
u/v
Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled
Enabled
Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled
Enabled
Disabled/Enabled
0.05,0.1,0.15,0.90,095,1.0
7,8,9,10,108,109,110
0.03,0.04,..14300,14400
Enabled
Disabled/Enabled
NPS,ZPS
7,8,9,10,108,109,110
0.05,0.1,0.15,0.90,095,1.0
1,2,109,110
0.05,0.1,0.15,0.90,095,1.0
0.05,0.1,0.15,19.90,19.95,20.0
0.03,0.04,..14300,14400
Enabled
Prim Value
126.5
1
12650
5
Any
132
0.5
13200
10
Any
Prime Value
93.5
2
5
9350
88
1
8800
Any
10
Any
0.4 s
Disabled
0.4 s
Disabled
0.10x In
10 V
10s
NPS
7V
0.1x In
15V
0.1x In
10x In
10s
Disabled/Enabled
0.05,0.0551.995,2
0.05,0.0551.995,2
20,25,59995,60000
20,25,59995,60000
Disabled/Enabled
0.1,0.11,2.99,3.0
Disabled,50,.99,100
Relay type SKE11
Located in Bus coupler panel
Range
o
5-90
0-10%
0-99sec
24
Enabled
0.2 xIn
0.05 x In
60ms
120ms
Enabled
1.05 xIn
95
Setting
o
20
unit
deg
5%
0.5 sec
BUSCOUPLER
Panel K7
Over current Non Directional relay with CT,VT, binary input , binary output
& LEDS
Standard version include
50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection
1 SYSTEM CONFIG
Description
Range
Setting
Prime
Description
Range
Setting
Prime
1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7
LV Side
PT rated primary
PT rated Secondary
1A
150:1
0~11000 V
110 V
11000V
110V
Range
Setting
Prime
Range
Setting
Prime
Range
Setting
Prime
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
50, 60
Enabled, Disabled
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7
3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement
Selects
4.1.1whether
51-1 the RMS value used by the 51 & 50 elements is True RMS or only calculated
Description
Gn 51-1 Element
Selects
whether
the 51-1 IDMTL Overcurrent element is enabled
Gn 51-1
Setting
Pickup
level
Gn 51-1
Char
Selects
characteristic
curve
to be IEC or ANSI IDMTL or DTL
Gn 51-1
Time Mult
(IEC/ANSI)
Time
multiplier
(applicable
Gn 51-1
Delay
(DTL) to IEC and ANSI curves but not DTL selection)
Delay
(applicable
only when
DTL is selected for characteristic)
Gn 51-1
Min Operate
Time
RMS, Fundamental
Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,
ANSI-MI,
ANSI-VI,
ANSI-EI
0.025,
0.05
... 1.575,
1.6 IEC-NI
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
Minimum
operate time of element.
4.1.3 50-1
Description
Range
Gn 50-1 Element
Selects
whether
the INST/DTL Overcurrent element is enabled
Gn 50-1
Setting
Pickup
level
Gn 50-1
Delay
Enabled, Disabled
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400
Sets
operate
delay time
4.1.4
50-2
Description
Range
Gn 50-2 Element
Selects
whether
the INST/DTL Overcurrent element is enabled
Gn 50-2
Setting
Pickup
level
Gn 50-2
Delay
Enabled, Disabled
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400
Sets
operate delay
5 DERIVED
E/Ftime
5.1 51N-1
Description
Range
Gn 51N-1 Element
Selects
whether
the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1
Setting
Pickup
level Char
Gn 51N-1
Selects
characteristic
curve(IEC/ANSI)
to be IEC or ANSI IDMTL or DTL
Gn 51N-1
Time Mult
Time
multiplier
(applicable
Gn 51N-1
Delay
(DTL) to IEC and ANSI curves but not DTL selection)
Delay
(applicable
when Time
DTL is selected for characteristic)
Gn 51N-1
Min only
Operate
Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,
ANSI-MI,
ANSI-VI,
ANSI-EI
0.025,
0.05
... 1.575,
1.6 IEC-NI
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20
25
50Hz
Enabled
1A
150:1
Enabled
Enabled
Disabled
Disabled
RMS
Enabled
0.8
IEC-NI
0.45
NA
NA
Setting
Enabled
2.5
0.4
Setting
Enabled
5.5
0.03
Setting
Enabled
0.1
IEC-NI
0.14
NA
NA
120
Prime
375
Prime
825
Prime
15
5.3 50N-1
Description
Gn 50N-1 Element
Selects
whether
the DTL derived Earth fault element is enabled
Gn 50N-1
Setting
Pickup
level Delay
Gn 50N-1
Sets
operate
delay time
Check
synchronisationProtection
25
Relay type: Areva SKE 11
Setting name
Phase angle Setting
Differential Voltage setting
Time set
Range
Enabled, Disabled
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400
Relay type SKE11
Located in Bus coupler panel
Range
o
5-90
0-10%
0-99sec
26
Setting
Enabled
0.9
0.5s
Setting
o
20
Prime
150
unit
deg
5%
0.5 sec
Panel K06
Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary output
10 LEDS
Standard version include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency
7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:
1 SYSTEM CONFIG
Description
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
Range
Setting
Prime
Range
Setting
Prime
0~11000 V
110 V
11000V
110V
Setting
Prime
50, 60
Enabled, Disabled
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
Description
PTs
LV Side
PT rated primary
PT rated Secondary
3 FUNCTION CONFIG
Description
Range
Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
Enabled, Disabled
Range
27
50Hz
Enabled
Enabled
Setting
u/v
u/v
Prime Value
93.5
1.5
5
9350
88
0.75
10
8800
Any
Any
BUS PT2
Panel K09
Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary output
10 LEDS version include
Standard
7SR12 04-2HA12-1CA0
1 SYSTEM CONFIG
Description
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
Range
Setting
Prime
Range
Setting
Prime
0~11000 V
110 V
11000V
110V
Setting
Prime
50, 60
Enabled, Disabled
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
Description
PTs
LV Side
PT rated primary
PT rated Secondary
3 FUNCTION CONFIG
Description
Range
Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
Enabled, Disabled
Range
28
50Hz
Enabled
Enabled
Setting
u/v
u/v
Prime Value
93.5
1.5
5
9350
88
0.75
10
8800
Any
Any
OUTGOING-1 to Auxiliary Transformer Feeder 1500 kVA (VCB 3 & VCB 4) Panels K1, K4 ,K6 and K10
Relay type Siemens Reyrolle 7SR10 03-1HA12-1CA0
7SR1003-1HA12-1CA0
Over current Non Directional relay with CT,VT, binary input , binary output
& LEDS
Standard version include
50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection
1 SYSTEM CONFIG
Description
Range
Setting
Prime
Range
Setting
Prime
CBCT Ratio
50:1
3 FUNCTION CONFIG
Description
Range
Setting
Gn Phase Overcurrent
Gn Derived E/F
Enabled, Disabled
Enabled, Disabled
Enabled
Enabled
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
50, 60
Enabled, Disabled
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
Description
1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7
1, 5
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
50Hz
Enabled
1A
100:1
1A
Range
Setting
Gn 51/50 Measurement
RMS, Fundamental
RMS
4.1.1 51-1
Description
Range
Setting
Gn 51-1 Element
Enabled, Disabled
Enabled
Gn 51-1 Setting
0.9
Gn 51-1 Char
IEC-NI
NA
NA
4.1.3 50-1
Description
Range
Setting
Gn 50-1 Element
Enabled, Disabled
Enabled
Gn 50-1 Setting
Gn 50-1 Delay
0.35
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated
at fundamental frequency
Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.
29
Prime
Prime
Prime
90
0.65
Prime
300
4.1.4 50-2
Description
Range
Setting
Gn 50-2 Element
Enabled, Disabled
Enabled
Gn 50-2 Setting
Gn 50-2 Delay
0.03
5 DERIVED E/F
5.1 51N-1
Description
Range
Setting
Gn 51N-1 Element
Enabled, Disabled
Enabled
Gn 51N-1 Setting
0.1
Gn 51N-1 Char
IEC-NI
NA
NA
5.3 50N-1
Description
Range
Setting
Gn 50N-1 Element
Enabled, Disabled
Enabled
Gn 50N-1 Setting
Gn 50N-1 Delay
0.35s
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Pickup level
Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.
30
Prime
400
Prime
10
0.12
Prime
100
Setting name
Current Set
Time Delay
Standby Earth Fault Protection 51 NS for OUTGOING:
Setting name
Current Set
Time Delay
31
Range
0.1~1 In
0.00..150.00 s
Setting
0.1
1
Prime Value
Range
0.1~1 In
0.00..150.00 s
Setting
0.1
1.25
Prime Value
10
10
OUTGOING-2 to Distribution Transformer Feeder 500 kVA (VCB 2 & VCB5) Panels K2,K3 and K11
Relay type Siemens Reyrolle 7SR10 03-1HA12-1CA0
7SR1003-1HA12-1CA0
Over current Non Directional relay with CT,VT, binary input , binary output
& LEDS
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Setting Dependencies
Enabled, Disabled
Enabled
2 CT/VT CONFIG
Description
Range
Setting
1, 5
1A
Phase CT Ratio
50:1
1, 5
1A
CBCT Ratio
50:1
3 FUNCTION CONFIG
Description
Range
Setting
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled
Enabled
Disabled
Disabled
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT ratio to scale primary current instruments
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Range
Setting
Gn 51/50 Measurement
RMS, Fundamental
RMS
4.1.1 51-1
Description
Range
Setting
Gn 51-1 Element
Enabled, Disabled
Enabled
Gn 51-1 Setting
0.6
Gn 51-1 Char
IEC-NI
NA
NA
4.1.3 50-1
Description
Range
Setting
Gn 50-1 Element
Enabled, Disabled
Enabled
Gn 50-1 Setting
Gn 50-1 Delay
0.35
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated
at fundamental frequency
Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.
32
Prime
Prime
Prime
Prime
Prime
30
0.45
Prime
300
4.1.4 50-2
Description
Range
Setting
Gn 50-2 Element
Enabled, Disabled
Enabled
Gn 50-2 Setting
10
Gn 50-2 Delay
0.03
5 DERIVED E/F
5.1 51N-1
Description
Range
Setting
Gn 51N-1 Element
Enabled, Disabled
Enabled
Gn 51N-1 Setting
0.1
Gn 51N-1 Char
IEC-NI
NA
NA
5.3 50N-1
Description
Range
Setting
Gn 50N-1 Element
Enabled, Disabled
Enabled
Gn 50N-1 Setting
0.8
Gn 50N-1 Delay
Sets operate delay time
0.35s
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Pickup level
Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.
33
Prime
500
Prime
5
0.25
Prime
40
Setting name
Current Set
Time Delay
Standby Earth Fault Protection 51 NS for OUTGOING:
Setting name
Current Set
Time Delay
Range
0.1~1 In
0.00..150.00 s
Setting
0.1
1
Prime Value
Range
0.1~1 In
0.00..150.00 s
Setting
0.1
1
Prime Value
34
35
7SR12 06-2HA12-1CA0
1 SYSTEM CONFIG
Description
Range
System Frequency
Setting Dependencies
Setting
Prime
50, 60
50Hz
Enabled, Disabled
Enabled
Range
Setting
400:1
1, 5
1A
400:1
LV Side
PT rated primary
PT rated Secondary
0~11000 V 3300V
110 V
110V
When enabled only active settings are displayed and all others hidden
2 CT/VT CONFIG
Description
1, 5
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT Ratio
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs
Earth CT Ratio
PTs
3 FUNCTION CONFIG
Description
Range
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Range
Gn 51/50 Measurement
RMS, Fundamental
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated at fundamental
frequency
36
1A
Prime
Setting
Prime
Setting
Prime
Enabled
Enabled
Disabled
Disabled
RMS
4.1.1 51-1
Description
Range
Gn 51-1 Element
Gn 51-1 Setting
Pickup level
Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Setting
Enabled, Disabled
Enabled
0.7
IEC-NI
NA
NA
Prime
280 Amps
0.35
4.1.3 50-1
Description
Range
Gn 50-1 Element
Gn 50-1 Setting
Pickup level
Gn 50-1 Delay
Setting
Enabled, Disabled
Enabled
0.2
Prime
800 Amps
4.1.4 50-2
Description
Range
Gn 50-2 Element
Gn 50-2 Setting
Pickup level
Gn 50-2 Delay
Setting
Enabled, Disabled
Enabled
2.5
0.02
Prime
1000 Amps
5 DERIVED E/F
5.1 51N-1
Description
Range
Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1 Setting
Pickup level
Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Setting
Enabled, Disabled
Enabled
0.07
IEC-NI
NA
NA
Prime
28 Amps
0.1
5.3 50N-1
Description
Range
Gn 50N-1 Element
Gn 50N-1 Setting
Pickup level
Gn 50N-1 Delay
Sets operate delay time
37
Setting
Enabled, Disabled
Enabled
0.7
0.2
Prime
280 Amps
38
Range
Setting
Prime
Value
u/v
u/v
Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled
Enabled
0.4 s
Disabled
Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled
Enabled
0.4 s
Disabled
Disabled/Enabled
0.05,0.1,0.15,0.90,095,1.0
7,8,9,10,108,109,110
0.03,0.04,..14300,14400
Enabled
0.10x In
10 V
10s
Disabled/Enabled
NPS,ZPS
7,8,9,10,108,109,110
0.05,0.1,0.15,0.90,095,1.0
1,2,109,110
0.05,0.1,0.15,0.90,095,1.0
0.05,0.1,0.15,19.90,19.95,20.0
0.03,0.04,..14300,14400
Enabled
NPS
7V
0.1x In
15V
0.1x In
10x In
10s
93.5
2
2805 Volts
5
Any
88
1
10
Any
2640 Volts
Disabled/Enabled
0.05,0.0551.995,2
0.05,0.0551.995,2
20,25,59995,60000
20,25,59995,60000
Enabled
0.2 xIn
0.05 x In
60ms
120ms
Disabled/Enabled
0.1,0.11,2.99,3.0
Disabled,50,.99,100
Enabled
1.05 xIn
95
39
Setting
20o
unit
deg
5%
0.5 sec
BUSCOUPLER
Panel L05
1 SYSTEM CONFIG
Description
Range
System Frequency
Setting Dependencies
Setting
Prime
50, 60
50Hz
Enabled, Disabled
Enabled
Range
Setting
400:1
1, 5
1A
400:1
LV Side
PT rated primary
PT rated Secondary
0~11000 V 11000V
110 V
110V
When enabled only active settings are displayed and all others hidden
2 CT/VT CONFIG
Description
1, 5
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT Ratio
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs
Earth CT Ratio
PTs
3 FUNCTION CONFIG
Description
Range
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Range
Gn 51/50 Measurement
RMS, Fundamental
1A
Prime
Setting
Prime
Setting
Prime
Setting
Prime
Enabled
Enabled
Disabled
Disabled
RMS
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated at fundamental
frequency
4.1.1 51-1
Description
Range
Gn 51-1 Element
Gn 51-1 Setting
Pickup level
Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
40
Enabled, Disabled
Enabled
0.6
IEC-NI
NA
NA
0.05
240 Amps
4.1.3 50-1
Description
Range
Gn 50-1 Element
Gn 50-1 Setting
Pickup level
Gn 50-1 Delay
Setting
Enabled, Disabled
Enabled
0.15
Prime
1600 Amps
4.1.4 50-2
Description
Range
Gn 50-2 Element
Gn 50-2 Setting
Pickup level
Gn 50-2 Delay
Setting
Enabled, Disabled
Enabled
0.03
Prime
2400 Amps
5 DERIVED E/F
5.1 51N-1
Description
Range
Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1 Setting
Pickup level
Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Setting
Enabled, Disabled
Enabled
0.1
IEC-NI
NA
NA
Prime
40 Amps
0.14
5.3 50N-1
Description
Range
Gn 50N-1 Element
Gn 50N-1 Setting
Pickup level
Gn 50N-1 Delay
Sets operate delay time
Check synchronisationProtection 25
Relay type: Areva SKE 11
Setting name
Setting
Enabled, Disabled
Enabled
0.9
0.5s
Setting
Prime
360
5-90 o
0-10%
0-99sec
41
20o
unit
deg
5%
0.5 sec
Panel L06
Over current Directional relay with E4 case,4CT,3VT,6 binary
input 8 binary output 10 LEDS
Standard version include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency
7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:
1 SYSTEM CONFIG
Description
Range
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
Settingthe
Dependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
Description
PTs
50, 60
Enabled, Disabled
50Hz
Enabled
Setting
Prime
Range
Setting
Prime
LV Side
PT rated primary
PT rated Secondary
3 FUNCTION CONFIG
Description
Range
Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
42
0~11000 V 11000V
110 V
110V
Setting
Enabled, Disabled
Range
Enabled
Setting
u/v
u/v
Prime
Prime
Value
93.5
1.5
5
9350 Volts
88
0.75
10
8800 Volts
Sec
Any
Any
Sec
BUS PT1
Panel L04
Over current Directional relay with E4 case,4CT,3VT,6 binary
input 8 binary
output
10 LEDS
Standard
version
include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency
7SR12 04-2HA12-1CA0
1 SYSTEM CONFIG
Description
Range
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
Settingthe
Dependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
Description
PTs
50, 60
Enabled, Disabled
50Hz
Enabled
Setting
Prime
Range
Setting
Prime
LV Side
PT rated primary
PT rated Secondary
3 FUNCTION CONFIG
Description
Range
Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
0~11000 V 11000V
110 V
110V
Setting
Enabled, Disabled
Range
Enabled
Setting
u/v
u/v
93.5
1.5
5
Prime
Prime
Value
Units
9350 Volts
Any
Units
43
88
0.75
10
Any
8800 Volts
Detais
Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Max. starting current (at 80 % Vn)
Starting time (at 100% Vn)
Starting time (at 80% Vn)
Heating Time Constant
Cooling time Constant
Max. blocked rotor time hot @100 %Voltage
Max. blocked rotor time Cold @100% Voltage
Locked rotor Current
Value
500
3.3
111.5
4.5
4.80
1.6
2.9
30
180
12
15
1418
CT/VT CONFIG
Description
Range
Parameter
Thermal Constant T2
Cooling Constant Tr
Thermal Trip
Thermal Alarm
Alarm Threshold
Thermal lockout
Lockout Threshold
Inhibit Trip During Start
Thermal Over load
Reset
3300V
110V
Step
1-360 min
44
0~3300 V
110 V
Value (Range)
1-360 min
1-999 min
0-10
Thermal Constant T1
Prime
1A
160:1
0.2 to 1.5 x In
K Coefficient
Setting
1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7
LV Side
PT rated primary
PT rated Secondary
Enabled/Disabled
Enabled/Disabled
0.2-100 %
Enabled/Disabled
0.2-100 %
Enabled/Disabled
Thermal Model/User Curve
Thermal Model/User Curve
Units
kW
kV
A
xIA
xIA
sec
sec
mins
mins
sec
sec
A
Set
Set unit
1 Value 90 mins
1
360 mins
Enable
Enable
0.01
90 %
Enable
0.01
20 %
Enable
Therma
Therma
0.01
0.73 xIn
20 mins
I>1 Function
Current set I>
I> TMS
I>3Function
Current set I>3
Disabled,DT,IEC S inverse,IEC V
Inverse,IEC
0.08
to 15 inE inverse
0.025-1.2
Enabled/Disabled
0.08 to 15 in
I2> 1 Status
I2> 1 Current Set
I2> 1 Time Delay
I2> 2 Status
I2> 2 Current Set
I2> 2TMS
Disabled,DT
0.05 to 4 In
0.04 to 200 sec
Disabled,IDMT
0.05 to 4 In
0.07 to 2
IN>1 Function
IN>1 Direction
Current set IN>
IN>1 T Delay
Disabled,DT,IEC S inverse,IEC V
Inverse,IEC E inverse
Non-directional,Directional
FWD
0.08 to 32 In
0.04 to 100 s
10 to120 V
IEC V
0.1 Inverse
0.77 xIn
0.025
1.2
0.1
52a,I,52a+I
1 to 5 In
1 to 200 sec
Enabled/Disabled
1 to 5 In
0.1 to 60 sec
Enabled/Disabled
1 to 5
Enabled/Disabled
1 to 5
10 to 120 mins
Enabled/Disabled
1 to 120 mins
1 to 120 mins
45
6.5 xIn
DT
0.025
0.01
0.1 xIn
1s
IDMT
0.05
0.025
0.2 xIn
1
DT
Non
0.01 directio
0.08 xIn
0.1
0.1 s
1
Enabled/Disabled
Prolonged Start
Start criteria
Starting current
Prolonged start time
Stall Detection
Stall setting
Stall Time
Enable
88 V
Enable
I
0.5
1
0.5
1
1
1
1
1
1
3 xIn
1.5 s
Enable
Enable
3 xIn
3s
2 Nos
Enable
3 Nos
10 mins
Enable
2 mins
10 mins
CB Fail 1 status
CB Fail 1Timer
CT Supervision
CTS 1 Status
CTS I VN< Inhibit
CTS1 IN> Set
CTS1 Time Delay
Phase-Neutral,Phse-Phase
Any Phase,Three Phase
Disabled,DT,IDMT
15-120 V
0.04 to 7200 sec
Phase Phase
Any
Phase
DT
1
93 V
0.01
1s
Phase-Neutral,Phse-Phase
Any Phase,Three Phase
Disabled,DT,IDMT
50-200 V
0.04 to 7200 sec
Phase Phase
Any
Phase
DT
1
127 V
0.01
1s
Enabled/Disabled
0 to 10 s
0.01
Enabled/Disabled
0.1 to 0.2 Vn
0.08 to4 In
0 to 10 s
46
0.01
0.01
Enable
0.2 s
Enable
0.05 x Vn
0.2 x In
5s
BUSCOUPLER-1
Relay type Siemens Reyrolle 7SR12 06-2HA12-1CA0
1 SYSTEM CONFIG
Description
Range
Setting
System Frequency
50, 60
50Hz
Setting Dependencies
Enabled, Disabled
Enabled
2 CT/VT CONFIG
Description
Range
Setting
1, 5
1A
Phase CT Ratio
400:1
1, 5
1A
Earth CT Ratio
400:1
PTs
LV Side
PT rated primary
PT rated Secondary
0~11000 V 11000V
110 V
110V
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT ratio to scale primary current instruments
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs
Measured Earth CT ratio to scale primary current instruments
3 FUNCTION CONFIG
Description
Range
Setting
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled
Enabled
Disabled
Disabled
Range
Setting
Gn 51/50 Measurement
RMS, Fundamental
RMS
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated at fundamental
frequency
4.1.1 51-1
Description
Range
Setting
Gn 51-1 Element
Enabled, Disabled
Enabled
Gn 51-1 Setting
0.6
Gn 51-1 Char
IEC-NI
NA
NA
Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.
Range
Setting
Gn 50-1 Element
Enabled, Disabled
Enabled
Gn 50-1 Setting
Gn 50-1 Delay
0.15
Pickup level
4.1.4 50-2
Description
Range
Setting
Gn 50-2 Element
Enabled, Disabled
Enabled
Gn 50-2 Setting
Gn 50-2 Delay
0.03
47
Prime
Prime
Prime
Prime
240
0.05
4.1.3 50-1
Description
Prime
Prime
1600
Prime
2400
48
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
800A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Setting
10
0.025
5
0.2
1
NA
0.05
Standard
Inverse
unit
xIn
s
xIn
s
xIn
s
s
Prime
8000
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
unit
In
s
In
s
Prime
800
Time dial
0.02~1.5
Setting
1
0.2
0.1
NA
Standard
Inverse
0.1
Ie> TMS
49
4000
800
80
Buscoupler
Relay type: ALSTOM P143
SCOPE OF FUNCTION
Address
Compt No:5 FA
Standard version include 50/51/67 -Directional /Non
directional,Instantaneous/ time delayed phase over current (6
stage),50N/51N/67N-Directional /Non directional,Instantaneous/ time
delayed measured earth fault ( 4 stages),64-Restritive earth fault, 51VVoltage controlled over current,27 under voltage,59 -over voltage,37 under
current,46 Negative Phase sequence over current,49 Thermal over load,50
BF Circuit breaker Fail,81U-Under frequency,81O-Overfrequency,81R-rate
of change of frequency Protection,current,60CTS-CT Supervision ,60VTS-VT
Supervision,25-Check synchronising
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
800A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Setting
9
0.015
4
0.15
0.8
NA
0.05
Standard
Inverse
unit
xIn
s
xIn
s
xIn
s
s
Prime
7200
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
unit
In
s
In
s
Prime
640
Time dial
0.02~1.5
Setting
0.8
0.2
0.1
NA
Standard
Inverse
0.15
Ie> TMS
50
3200
640
80
Check synchronisationProtection 25
Relay type: ALSTOM SKE 11
Setting name
Range
Setting
<
5-90 o
20o
^V
t
0-10%
0-99sec
Units
unit
Prim Value
deg
5%
0.5 sec
Setting Title
Fault Records
Function 27
Function 59
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
Parameter
PT rated primary
10..1000 V
PT rated secondary 110..415 V
Value (Range)
415/3 V
110/3 V
Step
PhaseNeutral,PhsePhase
Phase Phase
Any Phase,Three
Phase
Any Phase
V<1 Function
Disabled,DT,IDMT
DT
V<1 VoltageSet
V<1 Time Delay
15-120 V
0.04 to 7200 sec
51
99 V
1s
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Enabled/Disabled
Setting
Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
630A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Setting
10
0.01
4
0.05
1
NA
0.05
Standard
Inverse
unit
xIn
s
xIn
s
xIn
s
s
Prime
6300
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
unit
In
s
In
s
Prime
504
Time dial
0.02~1.5
Setting
0.8
0.05
0.1
NA
Standard
Inverse
0.1
Ie> TMS
52
2520
630
63
2F-B
2R-H
9R-G
Feeder name:
53
Mcomp
CT unit
Mcomp
Relay
setting
12.6-37.8 24
12.6-37.8 24
12.6-37.8 24
54
55
56
57
58
59
REFERENCE DOCUMENTS
3
60
Drawing Title
General Notes on 11 kV and 3.3 kV switch Boards
General Notes on 415 V PMCCs
11 kV Switch Board
GA and Schematic diagram of LT Switchgear Panel at RAW WATER PUMP HOUSE
File reference
Pdf file "LT-DG-LE130733-1-E428 & E431.pdf"
Pdf file "LT-DG-LE130733-3-E448.pdf"
Pdf file "RWPH 11kV HT Panel Latest.pdf"
pdf file "RWPH LT Scheme.pdf"
61
Drawing No
SLEF504 sh1-sh24 revision D
SLEE792 sh1-sh19 revision C
(3) G71550-E8170-U001-C- issue C
LT/DG/LE130733/1/E450/REVD- revision D
5
62
63
Value
110
0.415
197
75
7.2 x IA
6.6X IA
0.63
1.22
90
360
206.85
37
24
20
76
49
40
1418.4
Value
units
kW
V
A
A
sec
sec
min
min
A
sec
sec
sec
sec
sec
sec
A
Units
300 A
1A
197 A
IA x CT ratio
197 x 1/300
0.66 A
197 x 105/100
206.85 A
206.85 x 1/300
0.69 A
7.2X IA
=7.2 x197
1418.4 A
=1418.4x1 /300
4.73 A
=197 x 110 / 100
216.7 A
=216.7x1/300
0.72
0.72
= 1.3 x1418.4
1843.92 A
=1843.92 x1/300
6.15
6.2 A
5
64
Setting Calculation for Distribution Transformers TR3 & TR4 in Raw water Pump house
11 kV
433 V
100/1A
2500 /1A
1600 kVA
Transformer capacity
PT
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
Vp
Vs
65
1600
11
0.433
100/1
CTRP 100
2500/1
CTRS 2500
Z
5.25%
12865
40637
83.97
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 83.97/0.95
97.23
Isfl
0.97
1
1
Normal Inverse
2133.39
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x2133.39/0.95
2470.24
=2470/2500
0.988096421
1
Normal Inverse
40637.00
1599.62
16.00
12865.00
128.65
16 x 1.2=19.2
19.50
8
kVA
kV
kV
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Setting Calculation for Distribution Transformers TR1 & TR2 in Raw water Pump house
11 kV
433 V
150/1A
4000 /1A
2500 kVA
Transformer capacity
PT
Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current
Vp
Vs
66
2500
11
0.433
150/1
CTRP 150
4000/1
CTRS 4000
Z
6.25%
12865
53336
131.21
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 104.97/0.95
151.93
Isfl
1.01
1
1
Normal Inverse
3333.52
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x3333.52.41/0.95
3859.87
=3859.87/4000
0.964966316
1
Normal Inverse
53336.00
2099.50
14.00
12865.00
85.77
14 x 1.2=16.8
17.00
7
kVA
kV
kV
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
13
67
2500 kVA
1600 kVA
4100 kVA
2500 kVA
1600 kVA
4100 kVA
4100/11/1.732
215.2005039
Ip setting
TMS setting
This should be 150 milliseconds greater than fault clearing time of down stream relay
In this case the 2500 kVA Transformer feeder is set at
tms=0.11,Ip=1 and CTR=150/1
Fault current-2099 Amps
0.02
t=tms x ((0.14)/((If/Is)
-1))
t=0.11 x ((0.14)/(2099/150)0.02-1))
required time now
fault current -2099 Amps
0.2842 sec
0.0.4342 sec
CT ratio300/1
tms=t/ ((0.14)/((If/Is)0.02-1))
tms=0.4342/ ((0.14)/(2099/200)0.02-1))
TMS setting
Sending End relay setting details
CT ratio1250/1,plug setting 1.0 and time setting,0.23 and curve :very inverse
The setting proposed at sending end is very high for a load current of 190 A.
68
0.1231
0.13
Amps
10%
15%
20%
+15%
115*11000/100
12650
11000/110
110 x 12650/11000
126.5
+20%
120*11000/100
13200
11000/110
110 x 13200/11000
132
PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at
PT ratio
Relay set voltage 1st element
Undervoltage
In 11 kV switch board ,over voltage 1 Element set at
-15%
85*11000/100
9350
9350/110
110 x9350/11000
93.5
-20%
80*11000/100
8800
11000/110
110 x8800/11000
88
PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at
PT ratio
Relay set voltage 1st element
69
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
70
GRID
RKSR04 OSD2
GRID
cab:IC1
HTP_RWPH_IC1
HTP_RWPH_BUS A
50
51
VCB1
50
51
50
51
50
51
VCB2
HTP_RWPH_BUS B
50
51
VCB3
Cab:TR1_HT
Cab:TR3_HT
TR3
1600 kVA
PT_BC
50
51
PT_IC1
50
51
PTAREA_PMCC_BUS B
50
51
101
RWPH_IC1
50
51
50
51
RWPH_IC2
115
DM PMCC_BUS B
Cab:TR4_LT
PT_OG2
50
51
415V_PMCC_BC
50
51
DM PMCC_BUS A
RWPH PMCC
VCB7
PT_IC2
50
51
97
415V_PMCC_IC2
50
51
Cab:TR4_HT
BD TR2
PT_OG1
50
51
VCB6
TR4
1600 kVA
BD:TR1
50
51
50
51
VCB5
50
51
130
PTAREA_PMCC_BUS A
DM_PMCC_IC
VCB4
82
TR2
2500 kVA
Cab:TR3_LT
PT AREA PMCC
50
51
Cab:TR2_HT
TR1
2500 kVA
34
DM PLANT PMCC
HTP_RWPH_IC2
50
51
50
51
Cab:IC2
HTP_RWPH_BC
HT PANEL RWPH
RKSR02 OSC2
RWPH_PMCC BUS B
RWPH_PMCC BUS A
50
51
RWPH_OG1
50
51
123
124
MLDB1
RWPH_OG2
REV. DATE
TURBINE PUMP
ECO#
DESCRIPTION
DWN APP
Electrical
Electrical One-Line
One-Line Diagram
Diagram
DRAWN BY/DAT E:
DWG No.:
EN G. APP./ DATE:
MFG. APP./DATE :
71
SCALE :
PART No.:
DWG SIZE:
REV.
72
GRID
RKSR04 OSD2
Ik" : 26243.19A
GRID
cab:IC1
50
51
Cab:IC2
HTP_RWPH_BC
HT PANEL RWPH
HTP_RWPH_IC1
VCB1
50
51
50
51
50
51
VCB2
HTP_RWPH_BUS B
Ik" : 25255.43A
50
51
VCB3
Cab:TR1_HT
Cab:TR3_HT
TR3
1600 kVA
82
Ik" : 24762.36A
TR2
2500 kVA
Cab:TR3_LT
BD:TR1
50
51
PT_IC1
Cab:TR4_LT
50
51
101
RWPH_IC1
50
51
50
51
RWPH_PMCC BUS A
Ik" : 32020.46A
50
51
115
DM PMCC_BUS B
Ik" : 38976.89A
Cab:TR4_HT
50
51
50
51
415V_PMCC_BC
50
51
DM PMCC_BUS A
Ik" : 38974.61A
RWPH PMCC
VCB7
PT_OG2
97
415V_PMCC_IC2
50
51
PTAREA_PMCC_BUS B
Ik" : 48187.61A
PT_OG1
50
51
VCB6
PT_IC2
50
51
50
51
50
51
50
51
TR4
1600 kVA
BD TR2
PTAREA_PMCC_BUS A
Ik" : 47529.32A
DM_PMCC_IC
VCB5
130
Ik" : 50126.3A
PT_BC
PT AREA PMCC
50
51
VCB4
Cab:TR2_HT
TR1
2500 kVA
34
Ik" : 49500.52A
DM PLANT PMCC
HTP_RWPH_IC2
50
51
HTP_RWPH_BUS A
Ik" : 25229.69A
50
51
RKSR02 OSC2
Ik" : 26268.82A
RWPH_OG1
50
51
RWPH_OG2
123
124
MLDB1
Ik" : 15595.1A
RWPH_IC2
RWPH_PMCC BUS B
Ik" : 32674.05A
REV. DATE
TURBINE PUMP
Ik" : 16834.86A
ECO#
DESCRIPTION
DWN APP
DWG N o.:
E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :
73
SC ALE :
PART No.:
D WG SIZE :
REV.
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
Pre Fault
Voltage
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
26269
26243
25255
25230
24762
50126
49501
15595
48188
47529
38977
38975
32674
32020
16835
26266
26243
25100
25077
24536
43838
43297
13536
42105
41536
34008
34006
28453
27888
14610
74
0.5 Cycle
Sym.SC
Current
26269
26243
25255
25230
24762
50126
49501
15595
48188
47529
38977
38975
32674
32020
16835
0.5 Cycle
Sym.SC
Current
26266
26243
25100
25077
24536
43838
43297
13536
42105
41536
34008
34006
28453
27888
14610
1 Cycle
Sym.SC
Current
26260
26243
25246
25230
24753
49893
49501
15595
47943
47529
38976
38975
32436
32020
16631
1 Cycle
Sym.SC
Current
26258
26243
25092
25077
24528
43636
43297
13536
41894
41536
34007
34006
28247
27888
14434
3 Cycle
Sym.SC
Current
26253
26243
25240
25230
24747
49725
49501
15595
47768
47529
38976
38975
32266
32020
16488
3 Cycle
Sym.SC
Current
26252
26243
25086
25077
24522
43491
43297
13536
41742
41536
34007
34006
28100
27888
14310
26243
26243
25230
25230
24737
49461
49501
15595
47493
47529
38975
38975
32002
32020
16266
26243
26243
25077
25077
24513
43262
43297
13536
41504
41536
34006
34006
27871
27888
14119
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
26256
26243
24394
24382
23534
55622
55117
10962
48856
48412
39881
39880
24718
24468
11600
Bus Name
Pre Fault
Voltage
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
27230
27206
26071
26049
25495
53329
52808
14912
49728
49163
39779
39777
30511
29917
15958
75
0.5 Cycle
Sym.SC
Current
26256
26243
24394
24382
23534
55622
55117
10962
48856
48412
39881
39880
24718
24468
11600
0.5 Cycle
Sym.SC
Current
27230
27206
26071
26049
25495
53329
52808
14912
49728
49163
39779
39777
30511
29917
15958
1 Cycle
Sym.SC
Current
26252
26243
24390
24382
23529
55433
55117
10962
48691
48412
39881
39880
24627
24468
11542
1 Cycle
Sym.SC
Current
27222
27206
26063
26049
25487
53132
52808
14912
49516
49163
39778
39777
30295
29917
15813
3 Cycle
Sym.SC
Current
26248
26243
24387
24382
23526
55298
55117
10962
48573
48412
39881
39880
24562
24468
11500
3 Cycle
Sym.SC
Current
27216
27206
26058
26049
25481
52990
52808
14912
49365
49163
39778
39777
30141
29917
15711
26243
26243
24382
24382
23522
55084
55117
10962
48386
48412
39880
39880
24460
24468
11435
27206
27206
26049
26049
25472
52764
52808
14912
49124
49163
39777
39777
29899
29917
15554
GRID
RKSR04 OSD2
Ik" : 13121.6A
GRID
cab:IC1
50
51
Cab:IC2
HTP_RWPH_BC
HT PANEL RWPH
HTP_RWPH_IC1
VCB1
50
51
50
51
50
51
VCB2
HTP_RWPH_BUS B
Ik" : 12891.14A
50
51
VCB3
Cab:TR1_HT
Cab:TR3_HT
TR3
1600 kVA
82
Ik" : 12764.27A
TR2
2500 kVA
Cab:TR3_LT
BD:TR1
50
51
PT_IC1
Cab:TR4_LT
50
51
101
RWPH_IC1
50
51
50
51
RWPH_PMCC BUS A
Ik" : 30722.62A
50
51
115
DM PMCC_BUS B
Ik" : 36930.89A
Cab:TR4_HT
50
51
50
51
415V_PMCC_BC
50
51
DM PMCC_BUS A
Ik" : 36923.07A
RWPH PMCC
VCB7
PT_OG2
97
415V_PMCC_IC2
50
51
PTAREA_PMCC_BUS B
Ik" : 45193.14A
PT_OG1
50
51
VCB6
PT_IC2
50
51
50
51
50
51
50
51
TR4
1600 kVA
BD TR2
PTAREA_PMCC_BUS A
Ik" : 44529.89A
DM_PMCC_IC
VCB5
130
Ik" : 46728.76A
PT_BC
PT AREA PMCC
50
51
VCB4
Cab:TR2_HT
TR1
2500 kVA
34
Ik" : 46097.67A
DM PLANT PMCC
HTP_RWPH_IC2
50
51
HTP_RWPH_BUS A
Ik" : 12865.44A
50
51
RKSR02 OSC2
Ik" : 13147.22A
RWPH_OG1
50
51
RWPH_OG2
123
124
MLDB1
Ik" : 15335.34A
RWPH_IC2
RWPH_PMCC BUS B
Ik" : 31381.18A
REV. DATE
TURBINE PUMP
Ik" : 16570.68A
ECO#
DESCRIPTION
DWN APP
DWG N o.:
E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :
76
SC ALE :
PART No.:
D WG SIZE :
REV.
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1
Pre Fault
Voltage
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
0.5 Cycle
Sym.SC
Current
13147
13122
12891
12865
12764
46729
46098
45193
44530
36931
36923
31381
30723
16571
15335
1 Cycle
Sym.SC
Current
13138
13122
12882
12865
12755
46495
46098
44949
44530
36928
36923
31142
30723
16365
15335
0.5 Cycle
Sym.SC
Current
13144
13122
12849
12826
12703
41217
40671
39801
39228
32439
32434
27469
26900
14412
13341
1 Cycle
Sym.SC
Current
13136
13122
12841
12826
12695
41014
40671
39589
39228
32437
32434
27262
26900
14234
13341
77
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1
Pre Fault
Voltage
RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415
0.5 Cycle
Sym.SC
Current
13135
13122
12656
12644
12426
53146
52621
47042
46578
38619
38615
24289
24027
11520
10879
1 Cycle
Sym.SC
Current
13130
13122
12652
12644
12422
52952
52621
46871
46578
38618
38615
24194
24027
11459
10879
0.5 Cycle
Sym.SC
Current
13627
13603
13336
13314
13190
50563
50029
47372
46798
38175
38169
29604
29005
15712
14670
1 Cycle
Sym.SC
Current
13619
13603
13328
13314
13182
50363
50029
47159
46798
38173
38169
29387
29005
15565
14670
78
79
1 SYSTEM CONFIG
Description
System Frequency
Setting Dependencies
Range
Setting
Prime
50, 60
50Hz
Enabled, Disabled
Enabled
Range
Setting
300:1
LV Side
PT rated primary
PT rated Secondary
0~11000 V
110 V
11000V
110V
Setting
Prime
When enabled only active settings are displayed and all others hidden
2 CT/VT CONFIG
Description
1, 5
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT Ratio
1A
Prime
PTs
3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Gn Undervoltage U/V
Gn Overvoltage O/V
Gn Trip Circuit supervision
Gn Close Circuit Supervision
Gn Circuit Breaker Fail Supervision
Gn CT Supervision
Gn VT Supervision
Gn Thermal Overload
Range
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
80
Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement
Range
RMS, Fundamental
Setting
Prime
Setting
Prime
RMS
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency
4.1.1 51-1
Description
Gn 51-1 Element
Gn 51-1 Setting
Pickup level
Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Enabled
0.9
IEC-NI
NA
NA
270
0.13
4.1.3 50-1
Description
Gn 50-1 Element
Gn 50-1 Setting
Pickup level
Gn 50-1 Delay
Range
Setting
Enabled, Disabled
Enabled
0.45
Prime
900
4.1.4 50-2
Description
Gn 50-2 Element
Gn 50-2 Setting
Pickup level
Gn 50-2 Delay
Range
Setting
Enabled, Disabled
Enabled
0.045
Prime
2100
5 DERIVED E/F
5.1 51N-1
Description
Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1 Setting
Pickup level
Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Range
Setting
Enabled, Disabled
Enabled
0.1
IEC-NI
NA
NA
Prime
30
0.25
5.3 50N-1
Description
Gn 50N-1 Element
Gn 50N-1 Setting
Pickup level
Gn 50N-1 Delay
Range
Setting
Enabled, Disabled
Enabled
0.7
0.8s
81
Prime
210
Range
Setting
o/v
o/v
Range
Setting
u/v
u/v
82
Prim
Value
121
1
12100
5
Any
126.5
0.5
12650
10
Any
Prime
Value
99
2
9900
5
Any
93.5
1
10
Any
9350
Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled
Enabled
Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled
Enabled
Disabled/Enabled
0.05,0.1,0.15,0.90,095,1.0
7,8,9,10,108,109,110
0.03,0.04,..14300,14400
Enabled
Disabled/Enabled
NPS,ZPS
7,8,9,10,108,109,110
0.05,0.1,0.15,0.90,095,1.0
1,2,109,110
0.05,0.1,0.15,0.90,095,1.0
0.05,0.1,0.15,19.90,19.95,20.0
Enabled
0.4 s
Disabled
0.4 s
Disabled
0.10x In
10 V
10s
NPS
7V
0.1x In
15V
0.1x In
10x In
0.03,0.04,..14300,14400
Disabled/Enabled
0.05,0.0551.995,2
0.05,0.0551.995,2
20,25,59995,60000
20,25,59995,60000
Disabled/Enabled
0.1,0.11,2.99,3.0
Disabled,50,.99,100
Relay type SKE11
Located in Bus coupler panel
Range
o
5-90
0-10%
0-99sec
83
10s
Enabled
0.2 xIn
0.05 x In
60ms
120ms
Enabled
1.05 xIn
95
Setting
o
20
unit
deg
5%
0.5 sec
BUSCOUPLER
Panel K07
1 SYSTEM CONFIG
Description
System Frequency
Setting Dependencies
Over current Non Directional relay with CT,VT, binary input , binary
output & LEDS
Standard version include
50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection
Range
Setting
Prime
50, 60
50Hz
Enabled, Disabled
Enabled
Range
Setting
300:1
1, 5
1A
300:1
LV Side
PT rated primary
PT rated Secondary
0~11000 V
110 V
11000V
110V
Setting
Prime
When enabled only active settings are displayed and all others hidden
2 CT/VT CONFIG
Description
1, 5
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT Ratio
1A
Prime
Earth CT Ratio
Measured Earth CT ratio to scale primary current instruments
PTs
3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Range
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
84
Enabled
Enabled
Disabled
Disabled
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Range
Gn 51/50 Measurement
RMS, Fundamental
Setting
Prime
Setting
Prime
RMS
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency
4.1.1 51-1
Description
Gn 51-1 Element
Gn 51-1 Setting
Pickup level
Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Enabled
0.8
IEC-NI
NA
NA
240
0.1
4.1.3 50-1
Description
Gn 50-1 Element
Gn 50-1 Setting
Pickup level
Gn 50-1 Delay
Range
Setting
Enabled, Disabled
Enabled
2.5
0.35
Prime
750
4.1.4 50-2
Description
Gn 50-2 Element
Gn 50-2 Setting
Pickup level
Gn 50-2 Delay
Range
Setting
Enabled, Disabled
Enabled
0.03
Prime
1800
5 DERIVED E/F
5.1 51N-1
Description
Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1 Setting
Pickup level
Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Range
Setting
Enabled, Disabled
Enabled
0.12
IEC-NI
NA
NA
Prime
36
0.2
5.3 50N-1
Description
Gn 50N-1 Element
Gn 50N-1 Setting
Pickup level
Gn 50N-1 Delay
Sets operate delay time
Check synchronisationProtection 25
Range
Setting
Enabled, Disabled
Enabled
0.9
0.7
85
Prime
270
5-90 o
0-10%
0-99sec
86
Setting
20o
unit
deg
5%
0.5 sec
Panel K06
7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:
1 SYSTEM CONFIG
Description
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
Description
PTs
3 FUNCTION CONFIG
Description
Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
Range
50, 60
Enabled, Disabled
50Hz
Enabled
Setting
Prime
Range
Setting
Prime
0~11000 V
110 V
11000V
110V
Setting
Prime
LV Side
PT rated primary
PT rated Secondary
Range
Enabled, Disabled
Range
Enabled
Setting
u/v
u/v
87
Prime
Value
93.5
1.5
5
9350
88
0.75
10
8800
Any
Any
BUS PT2
Panel K09
7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:
1 SYSTEM CONFIG
Description
System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG
Description
PTs
3 FUNCTION CONFIG
Description
Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
Range
50, 60
Enabled, Disabled
50Hz
Enabled
Setting
Prime
Range
Setting
Prime
0~11000 V
110 V
11000V
110V
Setting
Prime
LV Side
PT rated primary
PT rated Secondary
Range
Enabled, Disabled
Range
Enabled
Setting
u/v
u/v
88
Prime
Value
93.5
1.5
5
9350
88
0.75
10
8800
Any
Any
OUTGOING-1 to DM Plant Transformer Feeder 1600 kVA & spare (VCB 2, VCB 5 & VCB 7)
Panel Nos K1,K4 and K11
Over current Non Directional relay with CT,VT, binary input , binary
7SR1003-1HA12-1CA0
output & LEDS
Relay type Siemens Reyrolle 7SR1003-1HA20-1CA0
1 SYSTEM CONFIG
Description
System Frequency
Setting Dependencies
Range
Setting
50, 60
50Hz
Enabled, Disabled
Enabled
Range
Setting
100:1
1, 5
1A
100:1
Prime
When enabled only active settings are displayed and all others hidden
2 CT/VT CONFIG
Description
1, 5
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT Ratio
1A
Prime
Earth CT Ratio
Measured Earth CT ratio to scale primary current instruments
3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement
Range
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Range
RMS, Fundamental
Setting
Prime
Setting
Prime
Setting
Prime
Enabled
Enabled
Disabled
Disabled
RMS
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency
4.1.1 51-1
Description
Gn 51-1 Element
Gn 51-1 Setting
Pickup level
Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Enabled
IEC-NI
NA
NA
4.1.3 50-1
89
0.15
100
Description
Gn 50-1 Element
Gn 50-1 Setting
Pickup level
Gn 50-1 Delay
Range
Setting
Enabled, Disabled
Enabled
0.45
90
Prime
600
4.1.4 50-2
Description
Range
Gn 50-2 Element
Gn 50-2 Setting
Pickup level
Gn 50-2 Delay
Setting
Enabled, Disabled
Enabled
19.5
0.02
Prime
1950
5 DERIVED E/F
5.1 51N-1
Description
Range
Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1 Setting
Pickup level
Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Setting
Enabled, Disabled
Enabled
0.1
IEC-NI
NA
NA
Prime
10
0.15
5.3 50N-1
Description
Gn 50N-1 Element
Gn 50N-1 Setting
Pickup level
Gn 50N-1 Delay
Range
Setting
Enabled, Disabled
Enabled
0.35s
Prime
100
Setting name
Range
Setting
Current Set
Time Delay
Sensitive Earth Fault Protection 51NS for OUTGOING:
Setting name
0.1~1 In
0.00..150.00 s
0.1
1
Range
Setting
Current Set
Time Delay
0.1~1 In
0.00..150.00 s
0.1
1
91
Prime
Value
10
Prime
Value
10
1 SYSTEM CONFIG
Description
System Frequency
Setting Dependencies
Range
Setting
50, 60
50Hz
Enabled, Disabled
Enabled
Range
Setting
150:1
1, 5
1A
150:1
Prime
When enabled only active settings are displayed and all others hidden
2 CT/VT CONFIG
Description
1, 5
Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT Ratio
1A
Prime
Earth CT Ratio
Measured Earth CT ratio to scale primary current instruments
3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement
Range
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Range
RMS, Fundamental
Setting
Prime
Setting
Prime
Setting
Prime
Enabled
Enabled
Disabled
Disabled
RMS
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency
4.1.1 51-1
Description
Gn 51-1 Element
Gn 51-1 Setting
Pickup level
Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Range
Enabled, Disabled
Enabled
IEC-NI
NA
NA
4.1.3 50-1
92
0.11
150
Description
Gn 50-1 Element
Gn 50-1 Setting
Pickup level
Gn 50-1 Delay
Range
Setting
Enabled, Disabled
Enabled
0.3
93
Prime
900
4.1.4 50-2
Description
Range
Gn 50-2 Element
Gn 50-2 Setting
Pickup level
Gn 50-2 Delay
Setting
Enabled, Disabled
Enabled
17
0.04
Prime
2550
5 DERIVED E/F
5.1 51N-1
Description
Range
Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1 Setting
Pickup level
Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL
Setting
Enabled, Disabled
Enabled
0.15
IEC-NI
NA
NA
Prime
22.5
0.25
5.3 50N-1
Description
Gn 50N-1 Element
Gn 50N-1 Setting
Pickup level
Gn 50N-1 Delay
Sets operate delay time
Restricted Earth Fault Protection 64R for OUTGOING:
7SR11 03-3HA12-1AA0
7SR11 03-3HA12-1AA0 Standard Version:
Range
Setting
Enabled, Disabled
Enabled
0.65
Prime
150
Setting name
Range
Setting
Current Set
Time Delay
Standby Earth Fault Protection 51 NS for OUTGOING:
Setting name
0.1~1 In
0.00..150.00 s
0.1
1
Range
Setting
Current Set
Time Delay
0.1~1 In
0.00..150.00 s
0.1
1
94
Prime
Value
15
Prime
Value
15
95
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Setting
Enabled/Disabled Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
4000
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Setting
5.5
0.037
3
0.15
1
NA
0.06
96
unit
xIn
s
xIn
s
xIn
s
s
Prime
22000
12000
4000
IEC Curve
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Standard
Inverse
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
Time dial
0.02~1.5
Setting
1
0.5
0.1
NA
Standard
Inverse
0.25
Ie> TMS
97
unit
In
s
In
s
Prime
4000
400
Buscoupler
Relay type: SIEMENS 7SR22
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase over
current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault, 51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
25-Check synchronising
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Setting
Enabled/Disabled Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
4000A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Setting
5
0.015
2.5
0.1
0.8
NA
0.05
Standard
Inverse
98
unit
xIn
s
xIn
s
xIn
s
s
Prime
20000
10000
3200
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
Setting
0.7
0.1
0.07
NA
Standard
Inverse
0.08
unit
In
s
In
s
Prime
2800
Set Value
Set unit
280
Time dial
Ie> TMS
0.02~1.5
Under Voltage Protection:27
Relay type: ALSTOM P94VB
Standard version include
27 under voltage,
59 -over voltage,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function 27
Function 59
Setting Range
Setting
Enabled/Disabled Enabled
Title Setting
Range
Setting
PT rated primary
PT rated secondary
10..1000 V
110..415 V
Value (Range)
415/ 3 V
110/ 3 V
Step
Parameter
PhaseNeutral,PhsePhase
Any Phase,Three
Phase
Phase -Phase
V<1 Function
Disabled,DT,IDMT
DT
V<1 VoltageSet
V<1 Time Delay
15-120 V
0.04 to 7200 sec
99
Any Phase
99 V
1s
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Setting
Enabled/Disabled Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
630A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Setting
9
0.03
6
0.4
1
NA
0.15
Standard
Inverse
100
unit
xIn
s
xIn
s
xIn
s
s
Prime
5670
3780
630
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
Time dial
0.02~1.5
Ie> TMS
101
Setting
1.5
0.35
0.15
NA
Standard
Inverse
0.15
unit
In
s
In
s
Prime
945
94.5
SCOPE OF FUNCTION
Address
Compt No:
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase
over current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault, 51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
25-Check synchronising
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Setting
Enabled/Disabled Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
2500
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Setting
5
0.015
3
0.3
1
NA
0.08
102
unit
xIn
s
xIn
s
xIn
s
s
Prime
12500
7500
2500
IEC Curve
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Standard
Inverse
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
Time dial
0.02~1.5
Setting
1
0.2
0.1
NA
Standard
Inverse
0.1
Ie> TMS
103
unit
In
s
In
s
Prime
2500
250
Buscoupler
Relay type: ALSTOM P143
SCOPE OF FUNCTION
Address
Compt No:
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase
over current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault, 51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
25-Check synchronising
Setting Title
Fault Records
Function 50/51
Function 50N/51N
Setting Range
Setting
Enabled/Disabled Enabled
Title Setting
Range
Setting
10..50000 A
1A/5A
2500A
1A
Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Setting
4
0.015
2
0.2
0.7
NA
0.05
104
unit
xIn
s
xIn
s
xIn
s
s
Prime
10000
5000
1750
IEC Curve
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)
Standard
Inverse
Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s
Setting
0.7
0.1
0.07
NA
Standard
Inverse
0.08
Time dial
Ie> TMS
0.02~1.5
Under Voltage Protection:27
Relay type: ALSTOM P94VB
Standard version include
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 27
Function 59
Other functions are disabled
Power System Data 1
Title Setting
Range
PTs
PT rated primary
10..1000 V
PT rated secondary 110..415 V
Parameter
Value (Range)
Setting
415/3 V
110/3 V
Step
V<1 Function
Disabled,DT,IDMT
DT
V<1 VoltageSet
V<1 Time Delay
15-120 V
0.04 to 7200 sec
105
175
Setting
Enabled
PhaseNeutral,PhsePhase
Any Phase,Three
Phase
Prime
1750
unit
In
s
In
s
Any Phase
93 V
1s
10000
1000
100
PT_OG1
RWPH_OG1
Time in Seconds
10
RWPH_IC
HTP_RWPH_IC1
VCB3
.01
.1
PT_IC1
.5
10
100
Current in Amperes X 100
Time-Current Characteristic Curves
3 - Grid-HTPANEL-VCB3-PTIC1-PTOG1-RWPHIC1-RWPHOG1
1000
10000
03-15-2015
23:03:44
sagardighi_rwph
106
10000
1000
100
RWPH_OG1
RWPH_IC1
10
PT_OG1
Time in Seconds
PT_IC1
VCB3
.01
.1
HTP_RWPH_IC1
.5
10
100
Current in Amperes X 100
Time-Current Characteristic Curves
3 - Grid-HTPANEL-VCB3-PTIC1-PTOG1-RWPHIC1-RWPHOG1
1000
10000
03-15-2015
23:08:00
sagardighi_rwph
107
108
109