Professional Documents
Culture Documents
TNK50C Taneko Industrial Generator (TNK JKT)
TNK50C Taneko Industrial Generator (TNK JKT)
TNK50C Taneko Industrial Generator (TNK JKT)
General
Genset Type
Rating
Fuel Consumption
: TNK50CI
: 40kW / 50kVA (Prime Power)
: 44kW / 55kVA (Standby Power)
: 15 l/h (Prime Power), 17 l/h (Standby Power), at 100% Load
Rating Definition
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant
electrical load for limited hours. Limited-Time
Running Power (LTP) is in accordance with
ISO 8528.
Engine Data
Alternator Data
Type
Speed [Rpm]
Frequency (Hz)
No of cylinders
Displacement [l]
Bore/Stroke [mm]
Compression Ratio
Governor
Oil Capacity [l]
:
:
:
:
:
:
:
:
:
4BTA3.9G2
1500
50
4 (inline)
3.9
102 / 120
17.3 : 1
Electronic
9.5
Type
Rated Output [kVA]
Standby AMP
Speed [Rpm]
Frequency [Hz]
Voltage [V]
Insulation
Protection
: STAMFORD UCI224D
: [3Ph, Single Bearing]
: 50
: 79
: 1500
: 50
: 400/230
: Class H
: IP 23
: as Cummins standard
: 7.9 (engine only)
: 12V
: Industrial / residential exhaust silencer
: Steel Channel/Plate construction (incl. daily tank)
: Rubber metal elements
: Engine operating instruction
: Certificate of Origin
: Alternator operating instruction
: Genset Test Report
Genset Controller
DSE7320
Auto Mains (Utility) Failure Control Modules
The DSE7320 is a feature packed Auto Mains (Utility) Failure
Control Module designed to control single diesel or gas genset applications.
KEY FEATURES
-3-phase generator and mains (utility) sensing
-Power monitoring (kW h, kV Ar, kV Ah, kV Ar h)
-Remote communications (RS232 & RS485)
-Configurable inputs/outputs (9/8)
-Fuel usage monitor and low level alarms
-Manual/automatic load transfer.
- Power save mode.
-DSE Configuration Suite PC Software.
-etc
: 1850x970x1530(mm)
: 1170(kg)
OPEN TYPE
Silent Type
Dimension [LxWxH]
Dry Weight
: 2450x1080x1770(mm)
: 1490kg
SILENT TYPE
According to ISO 8528-5. Continuous Power: No time limitation, plus 10% addictional, power for governing purpose only. Prime Power: Average output 80%, no time limitation, plus 5%
addictional power for governing purpose only. Limited Time Running Power: for up to 500 h/year, thereof a maximum of 300 h/year continuous running. In consideration of a generator
efficiency level of 89% - 90% and a power factor of 0.8