Question
HowdoIconfigureorsetupaPowerFlex753orPowerFlex755driveonacentrifugalfanorpumpmotorapplication?
Arethererecommendedsettingsforthisapplication?
Whydoesthemotorsometimesfirststartinthereversedirectiononalargeinertiaload?
Environment
20FPowerFlex753
20GPowerFlex755
Answer
Pumpsarenotusuallyheavydutyapplications.Experienceshowsthatdrivesleftinthefactorydefaultcontrolmode(sensorlessvectorcontrol)
sometimesdonotwanttoacceleratefansorpumpsabove2to3Hz.
Thiscanbecausedbyseveralthings,autotuningnotexecutedordonesoincorrectly,wrongmotordataetc.Aquickandeasyfixistosetthe
driveinaV/Hzregulationmethod.Thisisanidealcontrolmethodforcentrifugaltypeloads.
Findbelowatablewithsomebestpracticesettings.Othercommonparameterslikemotornameplatedataarenotmentionedbutneedtobe
enteredaspartofthestartup.
Parameter
Definition
#
Bestpracticesetting Comment
35
MotorControl
Mode
0=InductionVHz
65
VHzCurve
Custom
orFanpump(inthiscaseP6263notneeded)
62
BreakVoltage
140V
Assuming400VmotorDependingonfanorpumpcurve
63
BreakFrequency 25Hz
306
Dutyrating
NormalDuty
356
FlyingStart
Enhanced
422
Currentlimit1
setto130%ofmotor
FLA
Assuming50Hzmotordependingonfanorpumpcurvenormallykeepbelowminimum
runningspeed
DefaultSetting
Ifstartingintorotatingfan,mustbeset
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/486982
1/3
13/11/2015
486982PowerFlex750Series:CentrifugalFan/PumpSetupGuide
535
AccelTime1
setsubjecttoinertia
537
DecelTime1
setsubjecttoinertia
621
SlipRPMatFLA 0
setsonocurrentlimitappears
SetParameter70toReadyinordertochange.
DISCLAIMER
Thisknowledgebasewebsiteisintendedtoprovidegeneraltechnicalinformationonaparticularsubjectorsubjectsandisnotanexhaustive
treatmentofsuchsubjects.Accordingly,theinformationinthiswebsiteisnotintendedtoconstituteapplication,design,softwareorother
professionalengineeringadviceorservices.Beforemakinganydecisionortakinganyaction,whichmightaffectyourequipment,youshould
consultaqualifiedprofessionaladvisor.
ROCKWELLAUTOMATIONDOESNOTWARRANTTHECOMPLETENESS,TIMELINESSORACCURACYOFANYOFTHEDATACONTAINED
INTHISWEBSITEANDMAYMAKECHANGESTHERETOATANYTIMEINITSSOLEDISCRETIONWITHOUTNOTICE.FURTHER,ALL
INFORMATIONCONVEYEDHEREBYISPROVIDEDTOUSERS"ASIS."INNOEVENTSHALLROCKWELLBELIABLEFORANYDAMAGES
OFANYKINDINCLUDINGDIRECT,INDIRECT,INCIDENTAL,CONSEQUENTIAL,LOSSPROFITORDAMAGE,EVENIFROCKWELL
AUTOMATIONHAVEBEENADVISEDONTHEPOSSIBILITYOFSUCHDAMAGES.
ROCKWELLAUTOMATIONDISCLAIMSALLWARRANTIESWHETHEREXPRESSEDORIMPLIEDINRESPECTOFTHEINFORMATION
(INCLUDINGSOFTWARE)PROVIDEDHEREBY,INCLUDINGTHEIMPLIEDWARRANTIESOFFITNESSFORAPARTICULARPURPOSE,
MERCHANTABILITY,ANDNONINFRINGEMENT.Notethatcertainjurisdictionsdonotcountenancetheexclusionofimpliedwarrantiesthus,
thisdisclaimermaynotapplytoyou.
ThispageisbestviewedinInternetExplorer10,Firefox31,Chrome37,Safari6ornewer.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/486982
2/3
13/11/2015
486982PowerFlex750Series:CentrifugalFan/PumpSetupGuide
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/486982
3/3