FLOW CONTROL

USING REFORMULATED TANGENT METHOD


1ST READING
PVi = 40.0%
PVf = 50.0%
= 87
= 89
MV = 10.0%
a=

10
17 mm

b=

60 s
50 mm

Dead time, Td

= (50-40)

b
a

Td = (PVf PVi)

60
50
10
17

1
1

tan tan

1
1

tan87 tan 89

= 0.713s

Time constant, Tc
Tc = (PVf PVi)

= (50-40)

= 0.356s

b
a
60
50
10
17

[ ]
1
tan

1
tan 89 )

Response rate, RR
RR =

tan a
MV b
10
tan 89 17
10 60
50

= 2.8 /s
Tuning Rules:
Ziegler- Nichols:
For PI mode
P = 111.1 RR Td
= 221.80%
I = 3.33 Td
= 2.374s

Cohen-Coon:
=

Td
Tc
0.713
0.356

= 2.00

For PI mode

P=

100
RR Td

1+
11

= 168.93 %

[ ]

11
Td
11
1+
15
1+

I = 3.33

= 1.138s

2nd READING
PVi = 50.0%
PVf = 60.0%
= 88
= 89
MV = 10.0%
a=

10
17 mm

b=

60 s
50 mm

Dead time, Td
Td = (PVf PVi)

b
a

1
1

tan tan

= (60-50)

60
50
10
17

1
1

tan88 tan 89

= 0.356s

Time constant, Tc

b
a

Tc = (PVf PVi)

= (60-50)

60
50
10
17

= 0.356s

Response rate, RR
RR =

tan a
MV b
10
tan 89 17
10 60
50

= 2.8 /s

Tuning Rules:
Ziegler- Nichols:
For PI mode
P = 111.1 RR Td
= 110.74%
I = 3.33 Td

[ ]
1
tan

1
tan 89 )

= 1.185s

Cohen-Coon:
=

Td
Tc
0.356
0.356

= 1.00

For PI mode

P=

100
RR Td

1+
11

= 91.37%

[ ]

11
Td
11
1+
15
1+

I = 3.33

= 0.746s

3rd READING
PVi = 60.0%

PVf = 70.0%
= 88
= 89
MV = 10.0%
a=

10
17 mm

b=

60 s
50 mm

Dead time, Td

= (60-50)

b
a

Td = (PVf PVi)

60
50
10
17

1
1

tan tan

1
1

tan88 tan 89

= 0.356s

Time constant, Tc
Tc = (PVf PVi)

= (60-50)

= 0.356s

Response rate, RR
RR =

tan a
MV b

b
a
60
50
10
17

[ ]
1
tan

1
tan 89 )

10
tan 89 17
10 60
50

= 2.8 /s

Tuning Rules:
Ziegler- Nichols:
For PI mode
P = 111.1 RR Td
= 110.74%
I = 3.33 Td
= 1.185s

Cohen-Coon:
=

Td
Tc
0.356
0.356

= 1.00

For PI mode

P=

100
RR Td

1+
11

= 91.37%

[ ]

11
Td
11
1+
15
1+

I = 3.33

= 0.746s