DTR/SR

Fiche de rglage de la
protection 7SS52x

Poste OUALILI
Diffrentielle
Barres 225 kV

FR_7SS52x
Indice : A
Page : 1/1

Groupe protection general : Groupe Power System


N
Paramtre
6106
Minimum duration of TRIP command
6318
Control release for bay units
5103
Automatic acknowledgement of LED
5111A
Language of bay units

Valeur
0,10 sec
Released
YES
English

Groupe Bus Bar Protection : Groupe Bus zone


N
Paramtre
6101
Stabilizing factor selective
6102
Diff-current threshold - selective

Valeur
0,50
1,2 I/Ino

Groupe Bus Bar Protection : Groupe Check zone


N
Paramtre
6103
Stabilizing factor check zone
6104
Diff-current threshold check zone

Valeur
0,50
1,2 I/Ino

Groupe Breaker Failure protection : Groupe Breaker Failure


N
Paramtre
6201
Stabilizing factor BF protection
6202A
Is< SV.EF
3911
Current threshold of back-up breaker fail. prot
xx20
T-BF-1P
xx21
T-BF-3P
xx25
T-TRIP repeat

Valeur
0,50
5 I / In
0,2 I / In
0,2 s
0,2 s
0s

Groupe monitoring : Groupe general


N
Paramtre
6305
Blocking mode on failure

Valeur
Bus zone and phase selective

Groupe Monitoring : Groupe Idiff Superv


N
Paramtre
6306
Differential current supervision
6307
Time delay for diff-current supervision
6308
Limit value diff-current supervision-BZ
6309
Limit value diff-current supervision-CZ
6310
Diff-current supervision mode-BZ
6311
Diff-current supervision mode-CZ

Valeur
ON
10,00 sec
0,10 I/Ino
0,10 I/Ino
Blocking during the fault
Alarm without blocking

Groupe Monitoring : Groupe Isolator Superv


N
Paramtre
6301
Max . isolator operating time
6303
Treatment isolator status on DC fail
6304
Treatment isolator status not plausible
6302
Reaction on isolator malfunction
Groupe Monitoring : Groupe CB Test
N
Paramtre
6316
Limit value for circuit breaker test
Elabore par :
Nom :
Date :
Signature :

Valide par :
Nom :
Date :
Signature :

Valeur
15,00 sec
ON
ON
Alarm without blocking
Valeur
0,1 I / In
Affiche par :
Nom :
Date :
Signature :