500 KW Chiller Data Sheet
500 KW Chiller Data Sheet
INFORMATION BULLETIN
Date
23.11.99
Rev. nr.
Discipline :
Section
1.
Page
of
document nr.
9.5.6
INTRODUCTION
The Aggreko -C- range air cooled fluid chillers are designed for water or water-Glycol cooling. All
units are designed for to be located outside. The units are completely assembled with all
interconnection refrigerant piping and internal wiring, ready for installation.
The unit base and frame is of heavy-gauge steel with the dimensions of a standard 20 ft. container.
2.
KEY-DATA
Cooling Capacity
Absorbed Power
Temperature Range
Maximum ambient temp.
Dimensions
length
width
height
Weight
3.
Notes :
IDENTIFICATION
TH
E
PO
W
RE E R
NT & T
AL E M
LE P E
AD R A
ER T U
R
RA
MPE
THE R & TE R
E
DE
P O W L LEA
A
T
REN
TUR
Aggreko
INFORMATION BULLETIN
4.
of
9.5.6
TECHNICAL SPECIFICATIONS
ITEM
UNITS
VALUE
Performance Data
Design Capacity
50/60Hz
Design Operation Fluid Temperature IN / OUT
Minimum / Maximum Outlet Fluid Temperature
Minimum / Maximum Chilled Liquid Temperature Difference
Design Ambient Temperature
Minimum / Maximum Ambient Temperature
kW
C / C
C / C
C / C
C
C / C
497/607
12 / 6
-12 / +15
3.5 / 10.2
35
-18 / +55
l/s
l/s / l/s
litres
kPa
kPa
p.u.
litres
kW
m/h
Pa
10
2.3/3.4
139
0
Compressor
Compressor Type
Number Of Compressors
Number Of Capacity Steps
Evaporator Data
Evaporator Type
Evaporator Material
Design Flow
Minimum / Maximum Flow
Chiller Barrel Capacity
Chiller Barrel Maximum Working Pressure
Design Chiller Barrel Pressure Drop
Chiller Barrel Pressure Drop Factor
Recommended System Water Volume
Condenser Data
Number Of Condenser Fans
kW per Fan
Total Air Volume
External Static Pressure
50/60Hz
Refrigerant Data
Refrigerant Type
Number of Circuits
Refrigerant Charge circuit 1 / 2
Type Of Compressor Oil
Oil Charge circuit 1 / 2
Electrical Data
Design Electrical Supply Voltage
Design Electrical Rating
Design / Maximum Operating Current
Starting Current
Pre-Heating Supply
Recommended Generator Set
Required Cable Size per Phase
Electrical Connection
Noise Data
Sound Pressure Level at 10 metres - Lp(A)
Sound Power Level - Lw(A)
Physical Data
Overall Length
Overall Width
Overall Height
Weight
Fluid Coupling Size
kg / kg
litres
50/60Hz
R22
2
56 / 56
ISO 68
17 / 17
Volts
kVA / kW
Ampere
Ampere
Volts / VA
kVA
mm
400/460 3ph
177 / 151
257 / 354
476
220 / 600
250
240
Busbar M12
dB(A)
dB(A)
69
97
metres
metres
metres
kg
mm / inch
6.0
2.4
2.6
5040
100 / 4"
NOTE: Contact Technical Department If Application Conditions Differs From Design Conditions
Notes :
Aggreko
INFORMATION BULLETIN
5.
of
9.5.6
UNIT PERFORMANCE
based on 50 Hz supply
800
Ambient Temperature C
Cooling Capacity kW
700
20C
30C
600
40C
500
50C
400
300
200
100
-10
-5
10
15
900
Ambient Temperature C
Cooling Capacity kW
800
20C
30C
700
40C
600
50C
500
400
300
200
100
-10
-5
Notes :
10
15
Aggreko
INFORMATION BULLETIN
6.
of
9.5.6
100
50
30
20
40
45
50
35
30
25
20
15
10
10
15
Flow (l/s)
Propylene Glycol
Ethylene Glycol
1.6
1.5
50%
1.4
40%
1.3
30%
1.2
20%
10%
1.1
1
-10
Notes :
1.5
Concentration
Correction Factor
1.7
Correction Factor
Concentration
1.8
1.4
1.3
50%
40%
1.2
30%
20%
1.1
-8
-6
-4
-2
0
2
4
6
Mean Liquid Leaving Temperature C
10%
-12 -10 -8 -6 -4 -2 0
2
4
6
Mean Liquid Leaving Temperature C
Aggreko
The Power and Temperature
Rental Leader
Page
7.
of
INFORMATION BULLETIN
9.5.6
DIMENSIONS
Minimum required Clearance to prevent condenser air recirculation and faulty operation of unit(s) are as
follows: Side to wall 2.5 metres, Rear to wall 2.5 metres, Front to wall 1.5 metres, Top 15 metres.
Distance between adjacent units 3.5 metres. No more then one wall can be higher than the top of the
unit.
FRONT VIEW
Notes :
REAR VIEW