WHY A COOLING TOWER ?
Water is the most universally used fluid
to evacuate heat generated in
machines and production processes.
But the warm water must be disposed
off.
This can be done in different ways: it
can be drained into river of a sewer.
This is very expensive dus to the cost
of fresh water, the sewage cast and
the cost of the water treatment neces-
sary to bring the water quality within
the limits for sewage water.
(One could try to recuperate heat from
the water through heat exchangers,
but this is usually not an economically
feasible installation due to generally
low temperature differences. Recycling
of the water, after cooling process, is
certainly the mostefficient Way to treat
cooling water.
The equipment used therefore is the
COOLING TOWER
OPERATING PRINCIPLE
The cooling tower is a’water to air” heat
exchanger in which the water to be
cooled is in direct contact with the air.
The air, as it travelling through the
cooling tower, is heated and saturated
with water, The main part of the cooling
process in cooling tower is achieved
through evaporation
The efficiency of the evaporation
process is directly linked to the concept
of the heal exchange surface, also
called the fill pack.
The hot water is evenly distributed in
the cooling tower above the fill pack,
The pump head required at the water
inlet is very low. In the fill pack the
water is thoroughly mixed with the air,
Fresh air is continuously drawn into the
bottom of the tower.
The air moves in counterflow with the
water through the tower and is.
ejected into the atmosphere at high
speed. The amount of water evapo-
rated is approximately 1 to 3 % of the
circulating waterfiow, depending on
the operating conditions. Each liter of
water evaporated eliminates 2500 KJ
ies to become your
ntribute to a cleaner
industrial enviroment for
the 21st century ”a
HAMON,
HAMON COOLING TOWERS -VAP TYPE
The combination of water which is fully saturated
with oxygen an in which dissolved salts are con-
centrated, together with warm and moist air, make
the operating conditions in the cooling tower
aggressive and even corrosive. Hamon, the world
leader in evaporative cooling technology, has
develop an FRP cooling tower range that can
handle this harsh conditions.
The VAP cooling tower presents the following
unique customer benefits :
- Extremely long lifetime
- Minimal investment.
- Solid and simple design.
- Minimal running and maintain costs.
- Guaranteed thermal performance.
DESCRIPTION
The VAP is an induced draft counterfiow cooling tower
offering remarkable thermal performanca. The overall use
of plastic materials gives to these cooling towers an excep-
tional resistance to corrosion and reduces significantly all
maintenance cost. The low specific weight of FRP also
allow to use simple supporting structures and make
hoisting maneuvers less difficult.
VAP cooling towers can be very well integrated inte the
‘overall architectural lines and buildings, independent of
‘whether they are installed on the roof or at ground level.
“We offer you complete and optimal solution
for a long-term economical operation
while preserving your
water source. ”VAP TYPE
The VAP tower consist mainly of the following components :
41. Casing
The casing is formed by FRP self-supporting panels. The normal colour is white or
sey, but other colour is available on request. Between the panels, a polyethylene seal
and stainless steel bolts and nuts form a watertight joint,
heat exchange surface. The patented specific form of these sheets is designed by
HAMON to combine high thermal performance with a low air side pressure drop, and
avoid premature fill pack clogging by providing a wide passage for solids in suspenstan,
3. The Water Distribution
‘Good water distribution is essential fer the optimal operation of the cooling tower.
Water distribution made of PVE pipe, non-clogging spray nozzles, made of polypropyl
ene and polyamide, distribute the water evenly over the surface area. Only a small
head (+/- 8 kPa) is required at the cooling tower inlet flange:
2. The Fill Pack
(a) PVC thermoformed sheets are assembled in solid un-deformable blocks which form the
4, The Drift Eliminators
In order to eliminate water loss by drift, the cooling tower is equipped with drift elimina-
tors. These consist of PVC extruded sheets, assembled with polypropylene spacer to
form light-weight and easily handle sections. The standard eliminators reduce water
loss by drift to lass than 0.1 % of the circulating waterflow.
5. The Fan - Motor Assembly
‘The fan-motor assembly is installed on a het dip galvanized steel frame on top of the
cooling tower. An aluminium alloy axial fan with variable pitch at stand-stil, is directly
coupled to a squirrel cage low speed ( 600 to 1000 rpm ) motor. The motor is TEFC IP 55
ndard with class F insulation. The direct coupling forms a maintenance-free transmission
in, Only the model VAP 303 and VAP 323 requires site assembly of
. The basin has all necessary connections such as the water
to avoid water loss through the air inlet section of the VAP.
led on concrete site-constructed basin. in that case,
ian to design and construct this basin.
yy saving
amperature fill pack for water inlet lemperatures up to 700C.
5a
HAMON,
VAP TYPE
Make up water
(On recirculation circuits, the Susp
solids. content increases due to the eva
oration of pure water in the cooling tower.
Aregular drain, or blow-down, is needed
to keep the total suspended solids con-
centration in the water within acceptable
values, hence avoiding logging,
‘Make-up water required is equal to the
some of evaporated water plus blow
down and drift lost.
‘Concentration factor depends from
make-up water quality and the water
treatment of the circuit. Ask HAMON for
more details.
Delivery
‘VAP cooling towers are delivered fully assembled with
lbasin, ready for installation. For models 303 and 323, the
FRP basin must be assembled on site. The cooling tower
‘can be delivered in bulk for site assembly, detailed
‘assembly instructions are supplied with the unit.
Installation
VAP cooling towers can be installed on concrete slab or
‘on steel structure. The low weight of the VAP allows a
light supporting structure. In case of bulk supply, the
customer can easily assemble the WAP by bolting all
elements together.
Hydraulic and electrical connections
Alter erection of the cooling tower, all piping must be
connected. Hot water inlet, cold water outlet, make up
and overflow connecting piping must be supported sep
arately from the cooling tower without inducing stresses
to the cooling tower structure.
The electrical connections must be executed according
to national and local rules.
Cold weather operation
During cold weather, provisions will be made to avoid
freezing in the fill pack or water basin, Partial or total
by-pass of the cooling tower, two speed motors and
electrical heaters are the most commonly used. In any
is not recommend to allow outlet cold water
temperatures to fall below 5°C. HAMON's cooling tower
specialists will advise you when needed.HAMON COOLING TOWERS - RMP TYPE
‘The RMP type are the "PANELLED
MODULAR" cooling towers of Hamon
package cooling towers range.
‘The RMP cooling towers type cover the
medium and high capacity range. They are
suitable for the most of the industrial
applications.
‘The preassembled designed are easily
packed in the ISO sized containers, in order
to reduce freight cost.
‘The RMP casing consist of 12 standardized
factory fully preassembled steel framed
panels. They are fitted together on site by
bolting, and connected to strong central
framework.
‘The RMP is an induced draft counterfiow
type.The RMP cooling tower take advantage
of the large experience of HAMON in
thermal research and in the fields of
thermoplastic flings. All frameworks are
made of hot dipped galvanized steel, giving
the RMP cooling towers a high resistance
against corrosion.
“The HAMON Group more
than 100 years of experience in
water cooling”RMP TYPE
1. Construction
‘The RMP casing basically includes modular
steel framed panels delivered with integrated
corrugated FRP cladding. FRP cladding can
also being installed.on site” Only two kinds of
panels are needed for the whole RMP range.
Each panels includes the air inlet section and
the wall section in one part. The panels are
connected with strong steel beams to central
framework. This framework is designed to
support the main static and dynamic loads of
the structure: and of the mechanical equipment
3. Mechanical Equipment
On the top of unit, the mechanical equipment setis
settled on central framework, which consist of :
~ One axial fan
- One right angle gearbox, specially
designed for cooling tower application.
- One drive shaft
- One electrical motor TEFC, IP 55, class F
insulation
4, Access
‘An inspection door located on one side of
the casing, allows inside access for
maintenance. A cage ladder is provided from
basin curb to the access door, in conformity
with the safety regulations and standard.
Stairways also available as option.
2. Infill and water distribution sytem
‘The RMP cooling towers are equipped with:
- Ahot water distribution network, whose distribu-
tion pipes are PVG made. These pipes are fitied
with large orifice spray nozzles operating under
low pressure (approx.0,4m WC). The water distr-
bution is self draining by gravity.
- The fill, which consists of modules of factory
glued PVC sheets. The designed of this infill
combines high thermal performance and low
pressure drop far the highest efficiency. The cor-
rugations are vertical to reduse fouling risk and
motor absorbed power. When many cells have to
be dispatched, the infil sheets can be delivered
to be glued on site. This option reduces again the
volume and the cost of the freight.
~Ahigh efficient PVG drift eliminator system to
reduve drift losses
5. Basin
Due to the large dimensions of these towers,
the cold water basin shall be designed in
concrete. HAMON provides the necessary
guideline drawing for the basin eivil works, with
‘oads and anchoring positions indicated.TECHNICAL DATA-RMP TYPE
RMP
TYPE
2UAF 22.
AF 22,
WA.
2OaraT
AF a7
WAFS
BARAT
SSAF a7
BAF AS.
BEAR SS
42 AF 3714.2
4RAFAT.14,3
2A 45 14.2
a2 AF AS 14.3
4QAFS5.14.3
QAP TS.14.3
BRRRSeRSsseseeRe
SPEPPERPELZZERZE
Shipping ‘Operational
‘Weight Weight
6850 Kg 9650 Ko,
8400 Kg 12500 Kg
9350 Kg 14250 Kg
Note : All data are given as an indication.
‘They can be changed. without prior notice
Roler io the documents of the offer
Note:: The Value in this table are budgetary purposes. Always contact HAMON for confirmationa
AMON,
TECHNICAL DATA-VAP TYPE
Alm)
Bin)
cam)
Dimm
Etmm)
F trp
G (mm)
Shipping
‘weight (kg) lace
Operational
‘weight (ka)
Installed power (kW)
RPM
Fan
Diameter (mm)
Sound pressure level
atm +. 2.dB(8)"
(1) Remark :Low noise VAP'S" type cooling towers are available on request.aOR)
Td)
Telp.
ed
aa)
rr) een)