CarboDur Structural Strengthening Systems

Sectiune T
1000 mm

Proprietati sectionale
f c = 27.6 Mpa
414 MPa

100 mm

600 mm

AS = 3 277 mm fy =
h = 600 mm

d = 550 mm

hf = 100 mm

b = 1 000 mm

AV = 142 mm

bw = 300 mm

L = 8.00 m

s = 230 mm
etrieri 10/230 mm

35 mm
300 mm

Incarcari

432
wD = 24 kN/m

wL = 27 kN/m

CarboDur Structural Strengthening Systems

Grinda simplu rezemata:

MD = wD l/ 8 = 192 kN.m

ML = wL l/ 8 = 216 kN.m

Forta taietoare la distanta d de reazem: VD = wD l/ 2 - wD d = 82.8 kN


VL = wL l/ 2 wL d = 93.2 kN
Incarcarile de calcul:

1.4 wD + 1.7 wL = 79.5 kN/m


Mu = 1.4MD + 1.7ML = 636 kNm
Vu = 1.4VD + 1.7VL = 274.3 kNm
1.2(VD + VL) = 211.1 kN

CarboDur Structural Strengthening Systems

Verificarea sectiunii neconsolidate


Axa neutra se afla in inaltimea talpii Consolidarea

cu SikaWrap este posibila

Contributiile betonului si ale armaturii:

d
550
iVni i 0.166 f ' c bw d Av f y 0.85 0.166 27.6 300 550 142 414

s
230

i Vni = 241.8 kN > 1.2 (VD + VL) = 211.1 kN

OK

CarboDur Structural Strengthening Systems

Consolidare cu SikaWrap
cVc+ sVs+ LVL 1.4VD+1.7VL = Vu

cVc c 0.166

sVs s Av f y

f ' c bw d 122.3

kN

d
119 .4 kN
s

V Vu cVc sVs 274.3 122.3 119 .4 32.6 kN


L L

CarboDur Structural Strengthening Systems

Caracteristicile SikaWrap Hex-230C

Tesatura

Rezistenta la
intindere a
fibrelor [MPa]

Modulul de
elasticitate al
fibrelor [MPa]

SikaWrap Hex-230C

3 500

230 000

Grosimea fibrelor Elongatia la rupere


[mm]
a fibrelor [%]

0.13

1.5

Rezistenta necesara la forta taietoare: L VL = 2 tL EL L hc cot


t

V cVc sV s
32.6
u

0.05
L
2E hc cot
2 230000 0.004 341 cot 45
L L

mm de fibre

Se foloseste 1 strat de SikaWrap Hex-230C (aria fibrelor: 0.13 mm)

CarboDur Structural Strengthening Systems

1. Verificarea rezistentei efective la forta taietoare bazata pe rezistenta


betonului
Lc VL = Lc 2 vb Ab = 0.5 2 0.91 (f c)1/2 hc Lb cot
Lc VL = 163 kN > 32.6 kN
OK

2. Verificarea rezistentei efective la forta taietoare bazata pe rezistenta


la intindere a FRP

L VLLc VL = L 2 fLu tL hc cot = 0.45 2 3 500 0.13 341 cot 45


Lc VL = 139.6 kN > 32.6 kN

OK

CarboDur Structural Strengthening Systems

3.Verificarea rezistentei efective la forta taietoare bazata pe rezistenta


la forta taietoare a elementelor Sikadur-330

La

VL = La 2 Ab fa = 0.40 2 341 100 cot 45 15


LaVL = 409.2 kN > 32.6 kN
OK

La

4. Verificarea contributiei de ansamblu a otelului si a elementelor


SikaWrap Hex-230C
V

2/3

119 .4 163
V V

466.5 kN
L 0.85 0.5
S
kN

f 'c bwd

2
3

OK

f ' c bwd

2
27.6 300 550 577.9
3

CarboDur Structural Strengthening Systems

5. Verificarea evitarii cedarii fragile in bielele comprimate din beton


Conform Eurocode 2,

1
V V
f bw0.9d (1 cot )
R Rd 2 2 cd

1 27.6

300 0.9 550 1366 kN
Rd 2 2 1.5

122.3 119 .4 163


V Vc Vs V

618.4 kN
R
L 0.85 0.85 0.5

OK