CHAPTER 3

RESULTS AND DISCUSSION


A. External Cooling Load Calculation
EXTERNAL WALL
WALL CLTD

# OF
HOUR
12
13
14
15
CLTD CORRECTION=CLTD+(25.518)+(42.2-29.4)
CORRECT CLTD
# OF
HOUR
12
13
14
15

PEAKS
AT 15 SC
SHGFm
AREA
WALLaxFACING
AREA
WINDO
W
NE
SHGFm
SC 57.063
AREA
ax
NW
NE
142
0.64 38.592
17.67
SE
142
0.64 1.782
SE
23.4
SW

NE

NW

SE

SW

22
22
23
24

11
13
14
17

31
14
35
35

14
17
22
28

NE

NW

SE

SW

42.3
42.3
43.3
44.3

31.3
33.3
34.3
37.3

51.3
34.3
55.3
55.3

34.3
34.3
34.3
34.3

Qsg=(SHGFmax*SC*A
MATERI REA)
WAL CLT

REFERE CORRE
L
D
NCE
CT
NO.
TABLE
CLTD
CONCR
7
24
TABLE
44.3
Qsg=(SHGFmax*SC*
ETE AREA)
8.3A
CONCR
7
17
TABLE
37.3
1605.85
ETE 161.95
8.3A
CONCR
7
35
TABLE
55.3
ETE
8.3A
38.49
CONCR
7
28
TABLE
34.3
ETE
8.3A
TOTAL HEAT GAIN OF THE EXTERNAL WALL
AL

U
FACT
OR
0.18

HEAT
GAIN(Q=U*A*CLTD)
(WATTS)
455.020362

0.18

259.106688

0.18

232.9236

0.18

237.63726
1184.68791

TOTAL HEAT GAIN =1767.8W


B. Internal Cooling Load Calculation
C. LIGHT

LIGHT

14

LIGHT WITH ILLUMINATION

10

Recessed fluorescent luminaire


without lens

Space
Fraction
0.64
0.4

LIGHT WITH ILLUMINATION


ro
0.49
0.17
0.09
0.05
0.03
0.02
0.02
0.01
0.01

radiation
0.61
0.61
0.61
0.61
0.61
0.61
0.61
0.61
0.61

448
WATTS
320
WATTS
radiatio
n
0.48
0.61

qll
1091.2
1091.2
1091.2
1091.2
1091.2
1091.2
1091.2
1091.2
1091.2
Q1total

LIGHT
ql=4489(3.41)
(100%)=1527.68

convective radiation
light
qc=(1527.68)
(0.64)=977.72

light with illumination

light with illumination

qll=q18=320(3.14)
(100%)=1091.2

qc=(1091.2)
(0.40)=436.48

Q=(ro*radiation*qll)
326.15968
113.15744
59.90688
33.2816
19.96896
13.31264
13.31264
6.65632
6.65632
592.41248

LIGHT
ro

radiation

0.49

0.48

0.17

0.48

0.09

0.48

0.05

0.48

0.03

0.48

0.02

0.48

0.02

0.48

0.01

0.48

0.01

0.48

ql
1527.6
8
1527.6
8
1527.6
8
1527.6
8
1527.6
8
1527.6
8
1527.6
8
1527.6
8
1527.6
8
Q2total

Q(light and light with illumination)


qc=(1527.68)(0.64)=977.72
qc=(1091.2)(0.40)=436.48
Q1total=592.41248
Q2total=652.624896
Q(light and light with
illumination)total=2659.238

Q=(ro*radiation*ql)
359.310336
124.658688
65.995776
36.66432
21.998592
14.665728
14.665728
7.332864
7.332864
652.624896

operation is from 6:00am to 6:00 pm


assume 26% of the cooling load from
lightning is directly absorbed in the
return air stream without becoming room
load
Q(light room)=2659.2389(0.74)=1967.863btu/hr
1967.836btu/hr(0.293w/btu/hr)=576.576watts

Degree of Activity

Office Work

Heat Gain From


Occupants (Table 4.7)

150 W

Number of Occupants
CLF:
Sensible
Latent
Sensible Load
Latent Load
Total Load

350
0.71
1
37275
Watts
52500
Watts
89775
Watts

Total Loads
A. External, q= 2952.48791 W
B. Internal, q= 95672.576 W
Total loads = 98625.06391 W

PEOPLE
APPLIANCE
S

COMPUTER
LAPTOP
PRINTER
CELING FAN
DISPENSER
OVEN
REF
TOTAL

(N)# OF
APPLIANCES
3
45
2
12
3
1
1

WATTAGE(
W)
220
36
43
40
575
400
350

Ql=N*
W
660
1620
86
480
1725
400
350
5321