From the following test results, determine the voltage regulation of a 2000 V, singlephase synchronous generator delivering a current of 100 A at (i) unity pf, (ii) 0,8 leading
pf and (iii) 0,8 lagging pf. The result :
Full-load current 100 A is produced on short circuit by a field excitation 2,5 A.
An emf 500 V is produced on open-circuit by the same excitation.
Armature resistance is 0,8 , and draw it phasor diagram.
Solution
Single-phase generator
V = 2200 V, Ra = 0.5 , I = 100 A
500 V
ISC
I = 100 A
If
3A
Synchronous impedance
Zs
E1 (occ )
= 500 / 100 = 5
I 1 ( scc )
Synchronous reactance
Zs2 = Ra2 + Xs2
or
X s Z s Ra
Diagram phasor
1/ 2
sin = 0
I Ra = 100 x 0.5 = 50 V
I Xs = 100 x 4.97 = 497 V
E (V cos IRa ) 2 ( IX s ) 2
1/ 2
5309509 = 2304 V
%VR
E V
2304 2200
x100% =
x100%
V
2200
%VR = 4.72 %
ii) Pf 0.8 lead
cos = 0.8 , = 36.87o , sin = 0.6
1/ 2
%VR
E V
1988 2200
x100% =
x100%
V
2200
%VR = - 9.7 %
iii) Pf 0.8 lag
cos = 0.8, sin = 0.6
1/ 2
%VR
E V
2565 2200
x100% =
x100%
V
2200
%VR = 16.6 %
Problem 6
A 3-phase, 800 kVA, 11 kV, star connected synchronous generator has resistance of 1,5
/phase and synchronizing reactance of 25 /phase. Find the percentage regulation for
a load of 600kW at 0,8 leading power factor.
Solution
3 phase generator
S = 800 kVA = 800,000 VA
VLL = 11 kV = 11,000 V
Ra = 1.5 , Xs = 25
Voltage/phase = 11000 /
3 x VLL x I
S=
or
3 = 6350 V
3V LL
800000
3 x11000
= 42 A
I Ra = 42 x 1.5 = 63 V
I Xs = 42 x 25 = 1050 V
Pf 0.8 lead
cos = 0.8 , = 36.87o , sin = 0.6
1/ 2
E V
5837 6350
x100% =
x100%
V
6350
%VR = - 8 %